Plan Review Details - Permit 11070150
Plan Review Stops For Permit 11070150
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2011-08-12 Cont ID  
Sent By rmcdouga Date 2011-08-12 Time 16:54 Rev Time 0.00
Received By rmcdouga Date 2011-08-12 Time 16:54 Sent To Z
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-07-21 Cont ID  
Sent By rmcdouga Date 2011-07-21 Time 15:22 Rev Time 0.00
Received By rmcdouga Date 2011-07-21 Time 15:22 Sent To  
Notes
2011-07-21 15:30:392007 FBC W/2009 REVISIONS
  
 DENIED BY BUILDING
  
 1) THE EXPOSURE CATEGORY ON THE ENGINEER'S DRAWINGS IS
 INCORRECT. THE FLAGPOLE IS LOCATED WITHIN 100 FEET OF
 AN OPEN AREA OF ROUGHNESS C-TYPE TERRAIN THAT EXTENDS
 MORE THAN 600 FEET AND HAS A WIDTH OF GREATER THAN 150
 FEET. THE CORRECT EXPOSURE CATEGORY IS "C". SEE FBC
 1609.4.2 AND 1609.4.3.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-08-12 Cont ID  
Sent By rmcdouga Date 2011-08-12 Time 16:55 Rev Time 0.00
Received By rmcdouga Date 2011-08-11 Time 17:27 Sent To  
Notes
2011-08-11 17:27:09TO ZONING
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-07-21 Cont ID  
Sent By rmcdouga Date 2011-07-21 Time 15:30 Rev Time 0.00
Received By rmcdouga Date 2011-07-08 Time 13:28 Sent To  
Notes
2011-07-11 13:28:54TO ZONING BOX

Review Stop Z ZONING
Rev No 2 Status P Date 2011-08-17 Cont ID  
Sent By eschneid Date 2011-08-17 Time 16:00 Rev Time 0.75
Received By eschneid Date 2011-08-17 Time 16:00 Sent To PC
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2011-07-19 Cont ID  
Sent By eschneid Date 2011-07-19 Time 08:59 Rev Time 0.75
Received By eschneid Date 2011-07-13 Time 14:29 Sent To B
Notes
2011-07-19 09:25:32FAILED
  
 1) THE INSTALLATION OF THE FLAG POLE IS AN AMENDMENT TO
 THE APPROVED SITE AND LANDSCAPE PLANS AND THEREFORE
 REQUIRES THE APPROVAL OF A MINOR PLANNED DEVELOPMENT
 AMENDMENT PRIOR TO ZONING APPROVAL OF THE BUILDING
 PERMIT.
  
 2) SHOWING THE FLAGPOLE LOCATION ON A COPY OF THE PLAT
 IS NOT ACCEPTABLE. THE FLAGPOLE SHALL BE SHOWN ON A
 COPY OF THE SITE PLAN FOR THE GUARDHOUSE (APPROVED BY
 PERMIT NUMBER 01031027) INCLUDING DIMENSIONS TO THE
 CURBS, GUARDHOUSE AND PROPERTY LINES.
  
 3) THE AERIALS OF THE SITE SHOW TREES AND LANDSCAPE IN
 ALL OF THE ISLANDS NEAR THE GUARDHOUSE. SHOW A
 LANDSCAPE PLAN WHICH VERIFIES THAT THE PROPOSED
 FLAGPOLE WILL NOT INTERFERE WITH THE EXISTING TREES.
 TREES MAY NOT BE REMOVED FOR THE INSTALLATION OF THE
 FLAGPOLE UNLESS THEY ARE RELOCATED/REPLACED ELSEWHERE
 ON SITE.
  
 4) PROVIDE THE HEIGHT OF THE "BRASS ACORN FINIAL" ON
 TOP OF THE FLAGPOLE.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  