Plan Review Details - Permit 11070051
Plan Review Stops For Permit 11070051
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2011-07-14 Cont ID  
Sent By jwitmer Date 2011-07-14 Time 11:15 Rev Time 0.77
Received By jwitmer Date 2011-07-14 Time 11:15 Sent To  
Notes
2011-07-14 11:16:14BUILDING PROVISO:
 1) 2007/09 FBC-B TABLE 1017.1 FOOTNOTE ?C?
 C. IN BUILDINGS PROTECTED THROUGHOUT BY AN APPROVED,
 SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE
 WITH SECTION 903, CORRIDOR WALLS SHALL NOT
 BE REQUIRED TO BE RATED, PROVIDED THAT SUCH WALLS FORM
 SMOKE PARTITIONS IN ACCORDANCE WITH THE FLORIDA FIRE
 PREVENTION CODE.
  
 710.4 CONTINUITY. SMOKE PARTITIONS SHALL EXTEND FROM
 THE TOP OF THE FOUNDATION OR FLOOR BELOW TO THE
 UNDERSIDE OF THE FLOOR OR ROOF SHEATHING, DECK OR SLAB
 ABOVE OR TO THE UNDERSIDE OF THE CEILING ABOVE WHERE
 THE CEILING MEMBRANE IS CONSTRUCTED TO LIMIT THE
 TRANSFER OF SMOKE.
  
 712.6 FIRE WALLS, FIRE BARRIERS, FIRE PARTITIONS, SMOKE
 BARRIERS AND SMOKE PARTITIONS OR ANY OTHER WALL
 REQUIRED TO HAVE PROTECTED OPENINGS SHALL BE
 EFFECTIVELY AND PERMANENTLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE AUTHORITY
 HAVING JURISDICTION. SUCH IDENTIFICATION SHALL BE ABOVE
 ANY DECORATIVE CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING FOR FIRE AND SMOKE BARRIERS: "FIRE
 AND SMOKE BARRIER - PROTECT ALL OPENINGS."
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2011-07-12 Cont ID  
Sent By rlecky Date 2011-07-12 Time 14:10 Rev Time 0.00
Received By rlecky Date 2011-07-12 Time 14:10 Sent To  
Notes
2011-07-12 14:23:07PROVISO:
  
 LIGHTING MUST BE CONTROLLED USING MOTION SENSORS OR
 SIMILAR TECHNIQUES. FBC 13-412.ABC.1.3 ADDITIONAL
 CONTROLS
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 561-805-6718
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2011-07-15 Cont ID  
Sent By wjolin Date 2011-07-15 Time 09:59 Rev Time 0.00
Received By wjolin Date 2011-07-15 Time 09:11 Sent To  
Notes
2011-07-15 09:59:127643-7645 SOUTH DIXIE HIGHWAY
 PERMIT #11070051
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 ALL DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS
 OF NFPA 241.
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE APPROVED AND SUBMITTED IN WRITING TO THE OFFICE OF
 THE FIRE MARSHAL.
  
 PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY
 RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING
 NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM
 WWW.KNOXBOX.COM.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 EMERGENCY PLAN TO BE DEVELOPED AND POSTED IN BUILDING
 PRIOR TO OCCUPANCY.
  
 EMERGENCY EGRESS DRILLS SHALL BE CONDUCTED MONTHLY. ALL
 DRILLS SHALL BE SOUNDED ON THE FIRE ALARM SYSTEM.
  
 ARTWORK AND TEACHING MATERIALS ATTACHED TO THE WALLS
 SHALL NOT EXCEED 50 PERCENT OF THE INDIVIDUAL WALL
 AREA.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-07-15 Cont ID  
Sent By lmartine Date 2011-07-15 Time 11:11 Rev Time 0.00
Received By lmartine Date 2011-07-06 Time 15:40 Sent To  
Notes
2011-07-06 16:04:20B--4

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2011-07-15 Cont ID  
Sent By lmartine Date 2011-07-15 Time 12:44 Rev Time 0.00
Received By lmartine Date 2011-07-15 Time 12:44 Sent To  
Notes
2011-07-15 12:44:56NOT REQUIRED PER PHONE CONVERSATION WITH MICHELLE AT
 PBC.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2011-07-12 Cont ID  
Sent By rregueir Date 2011-07-12 Time 15:34 Rev Time 0.00
Received By rregueir Date 2011-07-12 Time 15:26 Sent To P
Notes
2011-07-12 15:28:27APPROVED WITH EXCEPTION:
  
 PAGE M-1 FAN SCHEDULE CALLS FOR 6 FANS AT 750 CFM EACH.
 PER PHONE CONVERSATION WITH MANUEL GONZALEZ, THIS IS AN
 ERROR. THE SCHEDULE IS SUPPOSED TO SAY 50 CFM FOR EACH
 FAN. SEE EMAIL ATTACHED TO MAIN PERMIT RECORD.

Review Stop P PLUMBING
Rev No 1 Status P Date 2011-07-13 Cont ID  
Sent By lwagner Date 2011-07-13 Time 09:27 Rev Time 0.00
Received By lwagner Date 2011-07-13 Time 07:41 Sent To  
Notes
***NONE***