Plan Review Details - Permit 11070051
| Plan Review Stops For Permit 11070051 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2011-07-14 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2011-07-14 |
Time |
11:15 |
Rev Time |
0.77 |
| Received By |
jwitmer |
Date |
2011-07-14 |
Time |
11:15 |
Sent To |
|
|
| Notes |
| 2011-07-14 11:16:14 | BUILDING PROVISO: | | | 1) 2007/09 FBC-B TABLE 1017.1 FOOTNOTE ?C? | | | C. IN BUILDINGS PROTECTED THROUGHOUT BY AN APPROVED, | | | SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE | | | WITH SECTION 903, CORRIDOR WALLS SHALL NOT | | | BE REQUIRED TO BE RATED, PROVIDED THAT SUCH WALLS FORM | | | SMOKE PARTITIONS IN ACCORDANCE WITH THE FLORIDA FIRE | | | PREVENTION CODE. | | | | | | 710.4 CONTINUITY. SMOKE PARTITIONS SHALL EXTEND FROM | | | THE TOP OF THE FOUNDATION OR FLOOR BELOW TO THE | | | UNDERSIDE OF THE FLOOR OR ROOF SHEATHING, DECK OR SLAB | | | ABOVE OR TO THE UNDERSIDE OF THE CEILING ABOVE WHERE | | | THE CEILING MEMBRANE IS CONSTRUCTED TO LIMIT THE | | | TRANSFER OF SMOKE. | | | | | | 712.6 FIRE WALLS, FIRE BARRIERS, FIRE PARTITIONS, SMOKE | | | BARRIERS AND SMOKE PARTITIONS OR ANY OTHER WALL | | | REQUIRED TO HAVE PROTECTED OPENINGS SHALL BE | | | EFFECTIVELY AND PERMANENTLY IDENTIFIED WITH SIGNS OR | | | STENCILING IN A MANNER ACCEPTABLE TO THE AUTHORITY | | | HAVING JURISDICTION. SUCH IDENTIFICATION SHALL BE ABOVE | | | ANY DECORATIVE CEILING AND IN CONCEALED SPACES. | | | SUGGESTED WORDING FOR FIRE AND SMOKE BARRIERS: "FIRE | | | AND SMOKE BARRIER - PROTECT ALL OPENINGS." | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2011-07-12 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2011-07-12 |
Time |
14:10 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2011-07-12 |
Time |
14:10 |
Sent To |
|
|
| Notes |
| 2011-07-12 14:23:07 | PROVISO: | | | | | | LIGHTING MUST BE CONTROLLED USING MOTION SENSORS OR | | | SIMILAR TECHNIQUES. FBC 13-412.ABC.1.3 ADDITIONAL | | | CONTROLS | | | | | | ROBERT LECKY | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2011-07-15 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2011-07-15 |
Time |
09:59 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2011-07-15 |
Time |
09:11 |
Sent To |
|
|
| Notes |
| 2011-07-15 09:59:12 | 7643-7645 SOUTH DIXIE HIGHWAY | | | PERMIT #11070051 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | ALL DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS | | | OF NFPA 241. | | | | | | FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING | | | DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A | | | FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN | | | 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE | | | PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST | | | BE APPROVED AND SUBMITTED IN WRITING TO THE OFFICE OF | | | THE FIRE MARSHAL. | | | | | | PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY | | | RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING | | | NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM | | | WWW.KNOXBOX.COM. | | | | | | PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH | | | EXIT SIGNS. | | | | | | EMERGENCY PLAN TO BE DEVELOPED AND POSTED IN BUILDING | | | PRIOR TO OCCUPANCY. | | | | | | EMERGENCY EGRESS DRILLS SHALL BE CONDUCTED MONTHLY. ALL | | | DRILLS SHALL BE SOUNDED ON THE FIRE ALARM SYSTEM. | | | | | | ARTWORK AND TEACHING MATERIALS ATTACHED TO THE WALLS | | | SHALL NOT EXCEED 50 PERCENT OF THE INDIVIDUAL WALL | | | AREA. | | | | | | WESLEY JOLIN | | | WEST PALM BEACH FIRE RESCUE | | | FIRE & LIFE SAFETY PLAN REVIEW | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2011-07-15 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2011-07-15 |
Time |
11:11 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2011-07-06 |
Time |
15:40 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
N |
Date |
2011-07-15 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2011-07-15 |
Time |
12:44 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2011-07-15 |
Time |
12:44 |
Sent To |
|
|
| Notes |
| 2011-07-15 12:44:56 | NOT REQUIRED PER PHONE CONVERSATION WITH MICHELLE AT | | | PBC. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2011-07-12 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2011-07-12 |
Time |
15:34 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2011-07-12 |
Time |
15:26 |
Sent To |
P |
|
| Notes |
| 2011-07-12 15:28:27 | APPROVED WITH EXCEPTION: | | | | | | PAGE M-1 FAN SCHEDULE CALLS FOR 6 FANS AT 750 CFM EACH. | | | PER PHONE CONVERSATION WITH MANUEL GONZALEZ, THIS IS AN | | | ERROR. THE SCHEDULE IS SUPPOSED TO SAY 50 CFM FOR EACH | | | FAN. SEE EMAIL ATTACHED TO MAIN PERMIT RECORD. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2011-07-13 |
|
|
Cont ID |
|
| Sent By |
lwagner |
Date |
2011-07-13 |
Time |
09:27 |
Rev Time |
0.00 |
| Received By |
lwagner |
Date |
2011-07-13 |
Time |
07:41 |
Sent To |
|
|
| Notes |
|
|
|