Plan Review Details - Permit 11070027
Plan Review Stops For Permit 11070027
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2011-08-18 Cont ID  
Sent By rmcdouga Date 2011-08-18 Time 09:27 Rev Time 0.00
Received By rmcdouga Date 2011-08-18 Time 07:48 Sent To Z
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-07-13 Cont ID  
Sent By rmcdouga Date 2011-07-13 Time 15:22 Rev Time 0.00
Received By rmcdouga Date 2011-07-13 Time 15:22 Sent To  
Notes
2011-07-13 15:32:562007 FBC W/2009 REVISIONS
  
 DENIED BY BUILDING
  
 1) SUBMIT TWO COPIES OF ENERGY CALCULATION FORMS FOR
 THE ADDITION AS REQUIRED BY N1100.03. THE FORMS ARE
 REQUIRED TO BE SIGNED BY THE PREPARER AND THE
 OWNER/AGENT.
  
 2) SHOW COMPLIANCE WITH FBC R320 FOR PROTECTION AGAINST
 TERMITES.
  
 3) THE WALL SECTION 2 ON SHEET A1 IS REQUIRED TO HAVE
 FIRE BLOCKING WHERE THE NEW WALL INTERSECTS THE CEILING
 PER FBC R602.1.2.
  
 4) TWO COPIES OF THE PRODUCT APPROVALS ARE REQUIRED.
 PLEASE SUBMIT AN ADDITIONAL COPY OF THE WINDOW AND DOOR
 PRODUCT APPROVALS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2011-08-15 Cont ID  
Sent By rlecky Date 2011-08-15 Time 12:48 Rev Time 0.00
Received By rlecky Date 2011-08-15 Time 12:48 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2011-07-07 Cont ID  
Sent By rlecky Date 2011-07-07 Time 15:42 Rev Time 0.00
Received By rlecky Date 2011-07-07 Time 15:09 Sent To  
Notes
2011-07-07 15:39:10INDICATE THE SIZE, RATING, LOCATION OF THE EXISTING
 SERVICE, MAIN DISCONNECT AND PANELBOARD. NEC 215.5
 ALL NEW GENERAL PURPOSE OUTLETS MUST BE AFCI PROTECTED.
 NEC 210.12
 NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11
 REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE DETECTORS. IF THE
 RESIDENCE HAS GAS APPLIANCES, AN ATTACHED GARAGE OR A
 FIRE PLACE A CARBON MONOXIDE DETECTOR IS REQUIRED
 WITHIN TEN FEET OF EACH ROOM USED FOR SLEEPING. FBC
 R313
 ADDITIONAL RECEPTACLES REQUIRED IN THE BEDROOMS AND
 HALLWAY. ADD RECEPTACLES SO THAT NO WALL SPACE IS MORE
 THAN 6 FEET FROM A RECEPTACLE AND ALL WALL SPACES MORE
 THAN 2 FEET IN WIDTH HAVE A RECEPTACLE. NEC 210.52
 A GFCI PROTECTED RECEPTACLE IS REQUIRED OUTSIDE AT
 ENTRANCE. NEC 210.52 (E) 210.8(A)
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 561-805-6718
  

Review Stop HIST HISTORICAL
Rev No 3 Status P Date 2011-08-18 Cont ID  
Sent By jpapa Date 2011-08-18 Time 11:45 Rev Time 0.00
Received By jpapa Date 2011-08-18 Time 11:45 Sent To  
Notes
2011-08-18 11:46:39PROVISO:
  
 WINDOW AND DOOR GLAZING SHALL FEATURE CLEAR GLASS. NO
 TINT.
  
 FOR MORE INFORMATION, CONTACT JILLIAN PAPA, HISTORIC
 PRESERVATION PLANNER AT 561-822-1454.

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2011-07-18 Cont ID  
Sent By jpapa Date 2011-07-18 Time 14:50 Rev Time 0.00
Received By jpapa Date 2011-07-18 Time 14:50 Sent To  
Notes
2011-07-18 14:56:48PROVISO:
  
 1. PVC (VINYL) PRODUCT SHALL NOT BE PERMITTED.
 ALUMINUM, ALUMINUM CLAD OR WOOD PRODUCTS ARE
 ACCEPTABLE.
 2. THE WINDOWS AND DOORS SHALL FEATURE WHITE FRAMES
 WITH CLEAR GLAZING; NO ADDITIONAL TINING OR
 GRAY/COLORED GLASS SHALL BE PERMITTED.
  
 FOR MORE INFORMATION, PLEASE CONTACT JILLIAN PAPA,
 HISTORIC PRESERVATION PLANNER AT 561-822-1454.

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2011-07-08 Cont ID  
Sent By jpapa Date 2011-07-08 Time 15:21 Rev Time 0.00
Received By jpapa Date 2011-07-08 Time 15:21 Sent To  
Notes
2011-07-08 15:24:07THE SUBJECT PROPERTY IS LOCATED IN THE NORTHWOOD HILLS
 HISTORIC DISTRICT. A CERTIFICATE OF APPROPRIATENESS
 APPLICATION MUST BE APPROVED BY THE HISTORIC
 PRESERVATION DIVSION PRIOR TO BUILDING PERMIT. TO
 OBTAIN AN APPLICATION, GO TO
 HTTP://WPB.ORG/HIST_PRES/APPLICATIONS/ OR CONTACT
 JILLIAN PAPA, HISTORIC PRESERVATION PLANNER, AT
 561-822-1454.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-08-18 Cont ID  
Sent By rmcdouga Date 2011-08-18 Time 11:59 Rev Time 0.00
Received By rmcdouga Date 2011-08-05 Time 10:02 Sent To  
Notes
2011-08-05 10:02:36R3

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-08-05 Cont ID  
Sent By shill Date 2011-07-18 Time 10:01 Rev Time 0.00
Received By shill Date 2011-07-06 Time 10:21 Sent To  
Notes
2011-07-06 10:21:50SENT TO SHELF R3 FOR REVIEW BY ALL TRADES.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2011-09-14 Cont ID  
Sent By rmcdouga Date 2011-09-14 Time 12:34 Rev Time 0.00
Received By rmcdouga Date 2011-09-14 Time 12:34 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2011-07-13 Cont ID  
Sent By rmcdouga Date 2011-07-13 Time 14:10 Rev Time 0.00
Received By rmcdouga Date 2011-07-13 Time 14:10 Sent To  
Notes
2011-07-13 14:12:05A PALM BEACH COUNTY IMPACT FEE REVIEW IS REQUIRED.

Review Stop P PLUMBING
Rev No 2 Status P Date 2011-08-18 Cont ID  
Sent By rmcdouga Date 2011-08-18 Time 07:36 Rev Time 0.00
Received By rmcdouga Date 2011-08-18 Time 07:36 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2011-07-13 Cont ID  
Sent By rmcdouga Date 2011-07-13 Time 13:57 Rev Time 0.00
Received By rmcdouga Date 2011-07-13 Time 13:57 Sent To  
Notes
2011-07-13 14:09:442007 FBC W/2009 REVISIONS
  
 DENIED BY PLUMBING
  
 1) THE BATHROOM FIXTURES ARE NOT PROPERLY VENTED. IN
 HORIZONTAL WET-VENT SYSTEMS, NOT MORE THAN ONE
 WET-VENTED FIXTURE DRAIN SHALL DISCHARGE UPSTREAM OF
 THE DRY-VENTED FIXTURE DRAIN CONNECTION PER FBCR
 P3108.2.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop Z ZONING
Rev No 3 Status P Date 2011-08-18 Cont ID  
Sent By jpapa Date 2011-08-18 Time 11:46 Rev Time 0.00
Received By jpapa Date 2011-08-18 Time 11:46 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2011-07-18 Cont ID  
Sent By jpapa Date 2011-07-08 Time 15:20 Rev Time 0.25
Received By jpapa Date 2011-07-18 Time 14:32 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2011-07-08 Cont ID  
Sent By jpapa Date 2011-07-08 Time 14:53 Rev Time 0.00
Received By jpapa Date 2011-07-08 Time 15:17 Sent To  
Notes
2011-07-08 15:20:33INSUFFICIENT INFORMATION SUBMITTED TO COMPLETE PLAN
 REVIEW. PLEASE SUBMIT 2 COPIES OF A PROPERTY SURVEY
 REFLECTING THE EXISTING CONDITIONS.
  
 FOR MORE INFORMATION, PLEASE CONTACT JILLIAN PAPA,
 HISTORIC PRESERVATION PLANNER AT 561-822-1454.