| Plan Review Stops For Permit 11060799 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2011-07-11 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2011-07-11 |
Time |
14:37 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2011-07-11 |
Time |
14:37 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2011-07-06 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2011-07-06 |
Time |
08:51 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2011-07-05 |
Time |
13:59 |
Sent To |
|
|
| Notes |
| 2011-07-05 15:42:04 | 1/0 CONDUCTORS ARE REQUIRED FOR SIX SERVICE FEEDERS TO | | | TWO 150 AMP PANELS. NEC T. 310.16, 310.15 (B)(6) | | | THE LOAD CALCULATION IS MISSING THE GENERAL LIGHTING | | | LOAD AS PART OF THE CALCULATION. NEC 220.82 | | | PROVIDE AN INTERSYSTEM BONDING STRIP AT THE SERVICE | | | GROUND. NEC 250.94 | | | | | | ROBERT LECKY | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2011-07-11 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2011-07-11 |
Time |
14:37 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2011-07-08 |
Time |
11:38 |
Sent To |
|
|
| Notes |
| 2011-07-11 11:39:23 | TO R LECKY |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2011-07-06 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2011-07-06 |
Time |
08:51 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2011-06-30 |
Time |
15:15 |
Sent To |
|
|
| Notes |
| 2011-06-30 15:16:12 | INCOMING SENT TO ELECTRIC < $5,000.00 JW |
|
|
|