Plan Review Details - Permit 11060793
Plan Review Stops For Permit 11060793
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2011-08-22 Cont ID  
Sent By jwitmer Date 2011-08-22 Time 11:43 Rev Time 0.77
Received By jwitmer Date 2011-08-22 Time 11:43 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-07-13 Cont ID  
Sent By jwitmer Date 2011-07-13 Time 08:22 Rev Time 0.77
Received By jwitmer Date 2011-07-13 Time 08:22 Sent To  
Notes
2011-07-13 08:36:59BUILDING PLAN REVIEW
 PERMIT: 11060793
 ADD: 1401 VILLAGE BLVD # 1715
 CONT: AMERICAN STANDARD CONSTRUCTION
 TEL: (954)655-5111
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) CONTRACTOR TO TAKE RESPONSIBILITY FOR PLANS, PRINT
 NAME, SIGN NAME AND PRINT LICENSE NUMBER ON PLANS.
  
 2) TO BRING IN VERIFICATION OF NEW OWNERS, PALM BEACH
 COUNTY INDICATES A DIFFERNT OWNER TO THIS UNIT.
  
 3) CONTRACTOR TO INDICATE COMPLIANCE WITH:
 3A) DRYWALL THICKNESS FOR TENANT SEPERATION WALLS AND
 CEILING.
 708.1 GENERAL. THE FOLLOWING WALL ASSEMBLIES SHALL
 COMPLY WITH THIS SECTION: (7). WALL SEPARATING
 INDIVIDUAL TENANT SPACES.
 708.3 FIRE-RESISTANCE RATING. FIRE PARTITIONS SHALL
 HAVE A FIRE-RESISTANCE RATING OF NOT LESS THAN 1 HOUR.
 709.3 FIRE-RESISTANCE RATING. (FLOOR/CEILING
 ASSEMBLIES) A 1-HOUR FIRE-RESISTANCE RATING IS REQUIRED
 FOR SMOKE BARRIERS.
  
 4) 1207.2 AIR-BORNE SOUND. WALLS, PARTITIONS AND
 FLOOR/CEILING ASSEMBLIES SEPARATING DWELLING UNITS FROM
 EACH OTHER OR FROM PUBLIC OR SERVICE AREAS SHALL HAVE A
 SOUND TRANSMISSION CLASS (STC) OF NOT LESS THAN 50 (45
 IF FIELD TESTED) FOR AIR-BORNE NOISE WHEN TESTED IN
 ACCORDANCE WITH ASTM E 90. PENETRATIONS OR OPENINGS IN
 CONSTRUCTION ASSEMBLIES FOR PIPING; ELECTRICAL DEVICES;
 RECESSED CABINETS; BATHTUBS; SOFFITS; OR HEATING,
 VENTILATING OR EXHAUST DUCTS SHALL BE SEALED, LINED,
 INSULATED OR OTHERWISE TREATED TO MAINTAIN THE REQUIRED
 RATINGS. THIS REQUIREMENT SHALL NOT APPLY TO DWELLING
 UNIT ENTRANCE DOORS; HOWEVER, SUCH DOORS SHALL BE TIGHT
 FITTING TO THE FRAME AND SILL.
  
 5) 1207.3 STRUCTURE-BORNE SOUND. FLOOR/CEILING
 ASSEMBLIES BETWEEN DWELLING UNITS OR BETWEEN A DWELLING
 UNIT AND A PUBLIC OR SERVICE AREA WITHIN THE STRUCTURE
 SHALL HAVE AN IMPACT INSULATION CLASS (IIC) RATING OF
 NOT LESS THAN 50 (45 IF FIELD TESTED) WHEN TESTED IN
 ACCORDANCE WITH ASTM E 492.
  
 JAMES A. WITMER
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2011-08-19 Cont ID  
Sent By rlecky Date 2011-08-19 Time 11:46 Rev Time 0.00
Received By rlecky Date 2011-08-19 Time 11:40 Sent To  
Notes
2011-08-19 11:54:37PLAN REVISION INDICATES TJE SCOPE OF WORK IS LIMITED TO
 REPAIR AND REPLACEMENT OF EXISTING RECEPTACLES AND
 SWITCHES.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2011-07-18 Cont ID  
Sent By rlecky Date 2011-07-18 Time 15:36 Rev Time 0.00
Received By rlecky Date 2011-07-18 Time 15:32 Sent To  
Notes
2011-07-18 15:36:01ELECTRICAL PLAN REQUIRED.
  
 INDICATE THE SIZE, RATING, VOLTAGE, LOCATION OF THE
 EXISTING SERVICE, MAIN DISCONNECTS AND PANELBOARD.
 PROVIDE PANEL SCHEDULES AND LOAD CALCULATION. PROVIDE
 AN ELECTRICAL RISER DIAGRAM. INCLUDE NEW AND EXISTING
 LOADS. NEC 215.5
 PROVIDE DEDICATED 20 AMP BRANCH CIRCUITS AS REQUIRED
 FOR BATH ROOM AND KITCHEN AREAS. NEC 210.11
 ADD RECEPTACLES SO THAT NO WALL SPACE IS MORE THAN 6
 FEET FROM A RECEPTACLE AND ALL WALL SPACES MORE THAN 2
 FEET IN WIDTH HAVE A RECEPTACLE. NEC 210.52
 RECEPTACLES ARE REQUIRED IN HALLWAYS. NEC 210.52 (H)
 GFCI PROTECTED RECEPTACLES ARE REQUIRED ON THE
 BALCONIES. NEC 210.52(E)
 ALL GENERAL PURPOSE OUTLETS INCLUDING THOSE IN THE
 BEDROOMS AND SMOKE ALARMS MUST BE AFCI PROTECTED. NEC
 210.12(B)
 NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11
 AT LEAST ONE WALL SWITCH-CONTROLLED LIGHTING OUTLET IS
 REQUIRED IN EVERY HABITABLE ROOM. NEC 210.70 (A)(1).
 REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE DETECTORS. IF THE
 RESIDENCE HAS GAS APPLIANCES, AN ATTACHED GARAGE OR A
 FIRE PLACE A CARBON MONOXIDE DETECTOR IS REQUIRED
 WITHIN TEN FEET OF EACH ROOM USED FOR SLEEPING. FBC
 R313
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 561-805-6718
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-08-22 Cont ID  
Sent By jwitmer Date 2011-08-22 Time 11:43 Rev Time 0.00
Received By jwitmer Date 2011-08-16 Time 09:28 Sent To  
Notes
2011-08-19 11:55:41SENT TO JW DESK.
2011-08-16 09:29:10INCOMING SENT TO R. LECKY DESK. JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-08-19 Cont ID  
Sent By rlecky Date 2011-07-25 Time 10:09 Rev Time 0.00
Received By rlecky Date 2011-06-30 Time 15:33 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2011-07-15 Cont ID  
Sent By lwagner Date 2011-07-15 Time 13:01 Rev Time 0.00
Received By lwagner Date 2011-07-15 Time 12:58 Sent To  
Notes
2011-07-15 13:03:21OK IF FOR FIXTURE REPLACEMENT ONLY. PLANS REQUIRED IF
 ANY PIPE CHANGES INVOLVED.

Review Stop Z ZONING
Rev No 1 Status P Date 2011-07-25 Cont ID  
Sent By lfranco Date 2011-07-25 Time 13:49 Rev Time 0.00
Received By lfranco Date 2011-07-25 Time 13:49 Sent To  
Notes
2011-07-25 13:55:16PLANNING AND ZONING: **** *ZONING REVIEW NOT REQUIRED:
 INTERIOR WORK ONLY AND THE VALUE OF PROPOSED WORK DOES
 NOT EXCEED 50% OF THE IMPROVEMENT VALUE.