| Plan Review Stops For Permit 11060784 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2011-06-30 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2011-06-30 |
Time |
10:43 |
Rev Time |
0.55 |
| Received By |
jwitmer |
Date |
2011-06-30 |
Time |
10:43 |
Sent To |
|
|
| Notes |
| 2011-06-30 10:43:18 | BUILDING PROVISO: | | | | | | 2007/09 FBC-B 712.6 FIRE WALLS, FIRE BARRIERS, FIRE | | | PARTITIONS, SMOKE BARRIERS AND SMOKE PARTITIONS OR ANY | | | OTHER WALL REQUIRED TO HAVE PROTECTED OPENINGS SHALL BE | | | EFFECTIVELY AND PERMANENTLY IDENTIFIED WITH SIGNS OR | | | STENCILING IN A MANNER ACCEPTABLE TO THE AUTHORITY | | | HAVING JURISDICTION. SUCH IDENTIFICATION SHALL BE ABOVE | | | ANY DECORATIVE CEILING AND IN CONCEALED SPACES. | | | SUGGESTED WORDING FOR FIRE AND SMOKE BARRIERS: "FIRE | | | AND SMOKE BARRIER - PROTECT ALL OPENINGS." | | | | | | 2007/09 FBC-B-M 607.4 ACCESS AND IDENTIFICATION. FIRE | | | AND SMOKE DAMPERS SHALL BE PROVIDED WITH AN APPROVED | | | MEANS OF ACCESS, LARGE ENOUGH TO PERMIT INSPECTION AND | | | MAINTENANCE OF THE DAMPER AND ITS OPERATING PARTS. THE | | | ACCESS SHALL NOT AFFECT THE INTEGRITY OF | | | FIRE-RESISTANCE-RATED ASSEMBLIES. THE ACCESS OPENINGS | | | SHALL NOT REDUCE THE FIRE-RESISTANCE RATING OF THE | | | ASSEMBLY. ACCESS POINTS SHALL BE PERMANENTLY IDENTIFIED | | | ON THE EXTERIOR BY A LABEL HAVING LETTERS NOT LESS THAN | | | 0.5 INCH (12.7 MM) IN HEIGHT READING: FIRE/SMOKE | | | DAMPER, SMOKE DAMPER OR FIRE DAMPER. ACCESS DOORS IN | | | DUCTS SHALL BE TIGHT FITTING AND SUITABLE FOR THE | | | REQUIRED DUCT CONSTRUCTION. | | | |
|
|
|