Plan Review Details - Permit 11060763
Plan Review Stops For Permit 11060763
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2011-08-08 Cont ID  
Sent By jwitmer Date 2011-08-08 Time 07:59 Rev Time 0.50
Received By jwitmer Date 2011-08-08 Time 07:58 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-07-07 Cont ID  
Sent By jwitmer Date 2011-07-07 Time 10:08 Rev Time 1.30
Received By jwitmer Date 2011-07-07 Time 10:08 Sent To  
Notes
2011-07-07 11:06:30BUILDING PLAN REVIEW
 PERMIT: 11060763
 ADD: 417 BUNKER RD
 CONT: WATSON GENERAL CONTRACTING
 TEL: (561)762-8471
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PLANS DO NOT PROVIDE IF THIS IS A CHANGE OF
 OCCUPANCY, OR TO WHAT DESIGN CRITERIA THIS PLAN WAS
 DESIGNED TOO? 2007/09 EXISTING BLDG CODE 2007/09
 EXISTING BLDG CODE 101.5.(101.5.1-101.5.3) OR CHAPTER 9
 CHANGE OF OCCUPANCY.
  
 2) THE PERMIT APPLICATION INDICATES UNDER DESCRIPTION
 OF WORK INTERIOR RENOVATIONS W/ AC & ELECTRIC. PLANS
 ARE NOT CLEAR OTHER THAN NEW ENTRY DOORS AND A NEW
 UNISEX RESTROOM WHAT OTHER WORK IS TO BE COMPLETED
 UNDER THIS PERMIT FOR BUILDING? PLEASE REVIEW 2004
 106.3.5 MINIMUM CRITERIA BUILDING PLAN REVIEW. MINIMUM
 BUILDING TYPE, FIRE SPRINKLERED, OCCUPANCY, OCCUPANCY
 LOADS, MIXED USE BLDG IS THE OCCUPANCIES SEPERATED OR
 NON-SEPERATED, PROVIDE A LIFE SAFETY PLAN WITH
 FURNISHINGS. PROVIDE A NARRATIVE AS TO WHAT WORK IS TO
 BE ACCOMPLISHED UNDER THIS PERMIT.
  
 3) NEW UNISEX RESTROOM DETAIL PROVIDED ON SHEET 2 IS
 FOR NEW TOILET STALL CONSTRUCTION, NOT FOR A TOLIET
 ROOM, PLEASE REVIEW SECTION 11-4.16 WATER CLOSETS IN
 TOLIET ROOMS, NOT STALLS, 11-4.16.2 CLEAR FLOOR SPACE
 DIRECTS YOU TO FIGURE #28. THE DESIGNER OF RECORD WILL
 NEED TO INDICATE THE CLEAR FLOOR SPACE, IF A FORWARD
 APPROACH OR SIDE APPROACH, NOTE THE INSWING DOOR CAN
 NOT SWING INTO THE CLEAR FLOOR SPACE.
  
 4) SHEET A1 INDICATES A NEW ENTRY DOOR BUT NO
 INFORMATION IS PROVIDED AS TO IS THE FRONT ENTRY
 ACCESSIBLE 11-4.14 ENTRANCES.
  
 5) SHEET A1 & A2 INDICATES A PAIR OF NEW IMPACT RATED
 DOORS MISSING PRODUCT APPROVALS. FL BLD CODE 1609.6.2.2
 COMPONENTS & CLADDING, PROVIDE 2 COPIES OF PRODUCT
 TESTING REPORTS, MISSING REPORTS ARE AS FOLLOWS:
 EXTERIOR GLAZED DOORS.
  
 6) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL. PLEASE ALSO NOTE
 TYPE OF HARDWARE TO BE INSTALLED ON DOUBLE INSWING
 DOORS.
  
 7) DEPENDING ON THE OCCUPANT LOADS TO BE DETERMINED THE
 MAIN EXITING DOORS MAY NEED TO BE OUTSWING DOORS IF THE
 OCCUPANT LOADS ARE 50 OR MORE, PLEASE REVIEW 2007/09
 FBC/B 108.1.2.
  
 8) PLANS INDICATE A PAIR OF POCKET DOORS BETWEEN RETAIL
 ROOM # 2 &3, IT IS NOT CLEAR IF THIS IS EXISTING OR NEW
 WORK, NOR DO WE KNOW THE DESIGN CRITERIA METHOD UNDER
 THE 2007/09 EXISTING BUILDING CODE, BUT IF THIS
 CONDITION IS NEW WORK PLEASE REVIEW 1008.1.2 EGRESS
 DOORS SHALL BE SIDE SWINGING.
  
 9) PLEASE PROVIDE ADDITIONAL INFORMATION ON THE
 GARDRAIL SYSTEM TO THE A/C MEZANINE LEVEL. THE
 MANUFACTURING PLANT THAT WAS THERE BEFORE DID HAVE A
 FACTORY OCCUPANCY CLASSIFICATION WHERE THE PUBLIC WAS
 NOT ALLOWED INTO THE PLANT. THIS DID ALLOW FOR THE 21
 INCH CLEAR SPACE OR MIDRAIL AS DEPICTED ON SHEET A2.
 THE ISSUE AT HAND ARE SINCE THE PUBLIC WILL BE PASSING
 BY THESE STAIRS, HOW OR WHAT WILL BLOCK, LOCK OFF THE
 STAIRS TO THE GENERAL PUBLIC?
 2007/09 1013.3 EXCEPTION #3.
  
 10) THIS COMMENT IS A ACCESSIBILITY COMMEENT AS WELL AS
 A REQUIREMENT THAT WILL BE STATED FROM YOUR PLUMBING
 PLAN REVIEWER, PLANS ARE MISSING AN ACCESSIBLE DRINKING
 FOUNTAIN 11-4.15.
  
 11) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER C.B.O.
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: (561)805-6715
 FAX:(561)805-6731
 E-MAIL: [email protected]
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2011-08-08 Cont ID  
Sent By rlecky Date 2011-08-08 Time 15:14 Rev Time 0.00
Received By rlecky Date 2011-08-08 Time 14:53 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2011-07-25 Cont ID  
Sent By rlecky Date 2011-07-25 Time 12:24 Rev Time 0.00
Received By rlecky Date 2011-07-25 Time 11:49 Sent To  
Notes
2011-07-25 12:25:17SPECIFY ON THE PLANS HOW THE LIGHTING WILL BE
 CONTROLLED USING MOTION SENSORS OR SIMILAR TECHNIQUES
 AS REQUIRED BY THE FLORIDA BUILDING CODE. AUTOMATIC
 LIGHTING CONTROL FBC 13-415.ABC.1.1; AUTOMATIC SPACE
 CONTROL FBC 13-415 ABC.1.2; ADDITIONAL CONTROLS
 13-412.ABC.1.3
  
 SPECIFY ON THE PLANS WHAT ELECTRICAL SYSTEMS AND
 DEVICES ARE EXISTING AND WHICH ARE BEING ADDED. PROVIDE
 A PANEL SCHEDULE SHOWING THE ELECTRICAL CIRCUITS FOR
 ALL EXISTING AND NEW EQUIPMENT. NEC 215.5
  
 VERIFY THE ELECTRICAL SERVICE AND EQUIPMENT HAS A
 SUFFICIENT INTERRUPTING RATING FOR THE AVAILABLE FAULT
 CURRENT. NEC 110.9
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 561-805-6718
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2011-08-05 Cont ID  
Sent By wjolin Date 2011-08-05 Time 13:00 Rev Time 0.00
Received By wjolin Date 2011-08-05 Time 11:47 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2011-07-06 Cont ID  
Sent By wjolin Date 2011-07-06 Time 16:17 Rev Time 0.00
Received By wjolin Date 2011-07-06 Time 15:24 Sent To  
Notes
2011-07-06 16:17:02417 BUNKER ROAD
 PERMIT #11060763
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THIS RENOVATION APPEARS TO BE A CHANGE OF OCCUPANCY
 FROM INDUSTRIAL/FACTORY TO STORAGE AND MERCANTILE.
 DESIGN SHALL CONFORM TO THE FLORIDA FIRE PREVENTION
 CODE 2007 EDITION: NFPA 1 AND NFPA 101 - 2006 EDITION
 WITH FLORIDA AMENDMENTS.
  
 STRUCTURES WITH LIGHT FRAME FLOOR/ROOF TRUSS
 CONSTRUCTION SHALL BE IDENTIFIED WITH A SIGN AFFIXED TO
 THE BUILDING. THE SIGN SHALL FEATURE A MALTESE CROSS
 8-INCHES WIDE AND 8-INCHES TALL AND BE OF A BRIGHT RED
 REFLECTIVE COLOR AND BEAR THE APPROPRIATE LETTERS "RF"
 DESIGNATION PER FLORIDA STATUTE 633.027 AND FLORIDA
 ADMINISTRATIVE CODE 69A-60.0081.
  
 DOORS IN THE MEANS OF EGRESS SHALL BE SIDE SWINGING.
  
 PROVIDE A DOOR SCHEDULE. INDICATE DOOR HARDWARE.
  
 DOOR IS REQUIRED TO SWING IN THE DIRECTION OF EGRESS
 TRAVEL FOR AN OCCUPANT LOAD OF 50 OR GREATER PERSONS
 PER SECTION 7.2.1.4.2 OF THE FLORIDA FIRE PREVENTION
 CODE: NFPA 101 - LIFE SAFETY CODE.
  
 EXTINGUISHERS SHALL HAVE A MINIMUM RATING OF 2A:10BC
 AND SHALL BE TAGGED BY A LICENSED FIRE EXTINGUISHER
 COMPANY.
  
 THE RELEASING MECHANISM ON ALL DOORS SHALL OPEN THE
 DOOR WITH NOT MORE THAN ONE RELEASING OPERATION. THE
 RELEASING MECHANISM SHALL HAVE AN OBVIOUS METHOD OF
 OPERATION THAT IS READILY OPERATED UNDER ALL LIGHTING
 CONDITIONS. THE RELEASING DEVICE SHOULD BE CAPABLE OF
 BEING OPERATED WITH ONE HAND AND SHOULD NOT REQUIRE
 TIGHT GRASPING, TIGHT PINCHING OR TWISTING OF THE WRIST
 TO OPERATE PER SECTION 7.2.1.5.9 OF NFPA 101 FLORIDA
 EDITION 2007.
  
 THE EXISTING MEZZANINE AND STAIR APPEAR TO HAVE BEEN
 CONSTRUCTED WITHOUT A PERMIT AS STAIRS AND MEZZANINE
 GUARDS DO NOT COMPLY WITH THE FLORIDA FIRE PREVENTION
 CODE. STAIRS, MEZZANINES, AND EGRESS COMPONENTS SHALL
 CONFORM TO THE LIFE SAFETY REQUIREMENTS OF CHAPTER 7 OF
 NFPA 101 FLORIDA 2007 EDITION.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 INDICATE WHAT TYPES OF MATERIALS WILL BE STORED AND HOW
 THE MATERIALS WILL BE STORED (RACK, PALLET, SOLID,
 ETC.). PROVIDE STORAGE LAYOUT PLAN.
  
 PROVIDE BUILDING ADDRESS VISIBLE FROM THE STREET.
 NUMBERS SHALL BE AT LEAST SIX-INCHES IN HEIGHT AND
 SHALL CONTRAST THE BACKGROUND (REFERENCE: SECTION
 10.12.1.2 OF THE FLORIDA FIRE PREVENTION CODE ? NFPA
 1).
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-08-08 Cont ID  
Sent By rlecky Date 2011-08-08 Time 15:15 Rev Time 0.00
Received By rlecky Date 2011-07-28 Time 17:39 Sent To  
Notes
2011-07-29 17:39:42*****************EXPEDITED*****************
 B--14

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-07-25 Cont ID  
Sent By rlecky Date 2011-07-25 Time 12:28 Rev Time 0.00
Received By rlecky Date 2011-06-29 Time 15:03 Sent To  
Notes
2011-06-29 15:03:52B10

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status P Date 2011-08-12 Cont ID  
Sent By shill Date 2011-08-12 Time 15:22 Rev Time 0.00
Received By hmoser Date 2011-08-12 Time 15:22 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2011-09-06 Cont ID  
Sent By shill Date 2011-09-06 Time 12:15 Rev Time 0.00
Received By shill Date 2011-09-06 Time 12:15 Sent To  
Notes
2011-09-06 12:16:30OK TO ISSUE W/PROVISO PER HM
 PLAN SUBMITTED UNDER 11080552 (FILED UNDER MASTER
 11060763, INCLUDES ELECTRICAL FOR LOFT)
  
  
 ****PROVISO****
 ****REVISION REQUIRED****
 ****ISSUED AT CONTRACTOR'S RISK****
  
 SHOW COMPLIANCE WITH FBC MECHANICAL 403
  
 LETTER SUBMITTED APPEARS TO PROVIDE ASHRAE 62
 CALCULATIONS. FOR RETAIL SPACE, OUTDOOR AIR IS TO BE
 DETERMINED BASED ON OCCUPANCY LEVEL AND FLOOR AREA
 (ONLY FLOOR AREA WAS USED).
  
 LETTER SUBMITTED IS NOT SIGNED AND SEALED, FS471.
 PLEASE INCORPORATE OUTDOOR AIR CALCULATIONS INTO THE
 PLAN.
  
 PLAN IS TO SHOW HOW OUTDOOR AIR WILL BE SUPPLIED (WHICH
 UNITS, CFM PER UNIT).
  
 INCORPORATE WIND DESIGN CRITERIA INTO THE PLAN.
  
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status N Date 2011-08-12 Cont ID  
Sent By shill Date 2011-08-12 Time 15:28 Rev Time 0.00
Received By shill Date 2011-08-12 Time 15:28 Sent To  
Notes
2011-08-12 15:31:42PROVISO - MECHANICAL PLANS TO BE SUBMITTED WITH
 MECHANICAL PERMIT APPLICATION FOR REVIEW
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2011-08-08 Cont ID  
Sent By shill Date 2011-08-08 Time 12:49 Rev Time 0.00
Received By hmoser Date 2011-08-08 Time 12:49 Sent To  
Notes
2011-08-08 13:06:45****CORRECTIONS****
 11060763
  
 1-2. ADDRESSED.
  
 3. SHOW COMPLIANCE WITH VENTILATION RATES REQUIRED BY
 FBC MECHANICAL 403, FBC EXISTING BUILDING 909. NOT
 ENOUGH INFORMATION PROVIDED REGARDING PREVIOUS USE AND
 PROPOSED USE TO DETERMINE REQUIREMENTS OR COMPLIANCE.
  
 2ND REVIEW, COMMENT NOT ADDRESSED. A NOTE ON THE PLAN
 WAS ADDED WHICH STATES THAT "OUTDOOR FRESHAIR WAS
 CALCULATED AT THE FOLLOWING UNDER TABLE 6-1 MINIMUM
 VENTILATION RATES IN BREATHING ZONES." SHOW COMPLIANCE
 BY PROVIDING CALCULATIONS, SEE FBC MECHANICAL 403.
  
 4. SEE FIRE COMMENTS REGARDING PERMITTING OF THE LOFT.
 PLEASE ADDRESS AS THE PLAN SUBMITTED PROPOSES TO USE
 THIS AREA FOR MECHANICAL EQUIPMENT. FBC MECHANICAL
 302.1.
  
 2ND REVIEW, COMMENT NOT ADDRESSED. RESPONSE LETTER
 STATES THAT THIS IS CLOSED OFF. THE LOFT, WHICH IS
 PROPOSED TO BE USED FOR MECHANICAL EQUIPMENT AND
 MAINTENANCE, HAS NOT BEEN PERMITTED OR INSPECTED. THIS
 MAY BE INCLUDED IN SCOPE OF WORK UNDER THIS PERMIT;
 INCLUDE ALL STRUCTURAL INFORMATION AND REVISE VALUE.
  
 5. PROVIDE MANUFACTURER SPECIFICATIONS WHICH SHOW THAT
 INTERIOR INSTALLATION OF MECHANICAL EQUIPMENT IS
 PERMITTED, FBC MECHANICAL 304.1. IF INTERIOR
 INSTALLATION OF EQUIPMENT IS ALLOWED PER MANUFACTURER
 SPECIFICATIONS, PROVIDE INFORMATION REGARDING HOW THE
 FAN DISCHARGE (EXHAUST) AIR WILL BE ADDRESSED, FBC
 MECHANICAL CHAPTER 5.
  
 2ND REVIEW, THIS WAS ADDRESSED BY MOVING THE ACU TO THE
 ROOF. A NOTE WAS ADDED WHICH STATES THAT THE ROOFTOP
 UNITS WILL BE ANCHORED TO THE ROOF JOISTS. PROVIDE A
 DETAIL FOR A CURB OR PROVIDE THE ROOF STAND PRODUCT
 APPROVAL. INCLUDE A STATEMENT THAT ATTACHMENT DETAIL
 COMPLIES WITH WIND DESIGN CRITERIA OF 140MPH.
  
 6-7. ADDRESSED.
  
 8. HORN AND STROBE NOTIFICATION REQUIRED, FBC M 606.4.
  
 2ND REVIEW, RESPONSE LETTER STATES THAT A STROBE IS NOT
 REQUIRED. PLEASE SEE FBC M 606.4.1, SUPERVISION AND
 REVISE PLAN TO SHOW COMPLIANCE.
  
 9-11. ADDRESSED.
  
 NEW COMMENT:
  
 12. PLEASE EXPLAIN, WHO IS "RICHARD A. JEMISON"? IT IS
 NOT CLEAR WHY THE PLANS STATE THAT THIS INDIVIDUAL
 DESIGNED THE JOB BUT FREDERICK D SHAFFER SIGNED AND
 SEALED THE PLAN. PLEASE SHOW HOW MR. JEMISON IS
 LICENSED TO DESIGN THIS SCOPE OF WORK UNDER FS 471,
 481, 489 OR OTHER FLORIDA STATUTE. THIS APPEARS TO BE
 SPECIFICALLY PROHIBITED.
  
 HAROLD MOSER, MECHANICAL PLANS EXAMINER
 561-805-6732
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2011-07-13 Cont ID  
Sent By shill Date 2011-07-13 Time 09:00 Rev Time 0.00
Received By hmoser Date 2011-07-12 Time 11:42 Sent To  
Notes
2011-07-13 09:01:03****CORRECTIONS****
 11060763
  
 1. PROVIDE HEAT LOAD CALCULATIONS, FBC MECHANICAL 312.
  
 2. PROVIDE AN EQUIPMENT SCHEDULE, FBC 106.
  
 3. SHOW COMPLIANCE WITH VENTILATION RATES REQUIRED BY
 FBC MECHANICAL 403, FBC EXISTING BUILDING 909. NOT
 ENOUGH INFORMATION PROVIDED REGARDING PREVIOUS USE AND
 PROPOSED USE TO DETERMINE REQUIREMENTS OR COMPLIANCE.
  
 4. SEE FIRE COMMENTS REGARDING PERMITTING OF THE LOFT.
 PLEASE ADDRESS AS THE PLAN SUBMITTED PROPOSES TO USE
 THIS AREA FOR MECHANICAL EQUIPMENT. FBC MECHANICAL
 302.1.
  
 5. PROVIDE MANUFACTURER SPECIFICATIONS WHICH SHOW THAT
 INTERIOR INSTALLATION OF MECHANICAL EQUIPMENT IS
 PERMITTED, FBC MECHANICAL 304.1. IF INTERIOR
 INSTALLATION OF EQUIPMENT IS ALLOWED PER MANUFACTURER
 SPECIFICATIONS, PROVIDE INFORMATION REGARDING HOW THE
 FAN DISCHARGE (EXHAUST) AIR WILL BE ADDRESSED, FBC
 MECHANICAL CHAPTER 5.
  
 6. FAN SHUTDOWNS REQUIRED, FBC M 606.4.
  
 7. DUCT SMOKE DETECTORS REQUIRED, FBC M 606.2.1.
  
 8. HORN AND STROBE NOTIFICATION REQUIRED, FBC M 606.4.
  
 9. CONDITIONED SPACE (SEE DEFINITIONS) TO COMPLY WITH
 REQUIREMENTS OF FBC 13 101.3, FBC 13 101.4. NOT ENOUGH
 INFORMATION PROVIDED TO DETERMINE COMPLIANCE OR
 REQUIREMENTS.
  
 9. THE FACT THAT THE SYSTEM IS FOR DEHUMIDIFICATION
 ONLY IS NOTED. IF COMPLIANCE IS NOT SHOWN FOR A SPACE
 COOLING SYSTEM, THE DESCRIPTION FOR THE PROJECT WILL BE
 MODIFIED TO INCLUDE THIS INFORMATION AND WILL BE
 AVAILABLE AS PUBLIC RECORD.
  
 10. SHOW COMPLIANCE WITH REQUIREMENTS OF FBC 13 407,
 HUMIDITY CONTROL.
  
 11. NO THERMOSTATS SHOWN. SEE FBC 13 1-01.5.7, FBC 13
 407AB, IT IS NOT CLEAR HOW HEAT WILL BE REGULATED.
  
 12. NOT ENOUGH INFORMATION PROVIDED TO DETERMINE CODE
 COMPLIANCE.
  
 HAROLD MOSER, MECHANICAL PLANS EXAMINER
 561-805-6732
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2011-08-01 Cont ID  
Sent By lwagner Date 2011-08-01 Time 13:33 Rev Time 0.00
Received By lwagner Date 2011-08-01 Time 13:15 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2011-07-13 Cont ID  
Sent By lwagner Date 2011-07-13 Time 09:36 Rev Time 0.00
Received By lwagner Date 2011-07-12 Time 14:08 Sent To  
Notes
2011-07-12 14:51:11FBC PLUMBING 2007 REVIEW #1
 DENIED:
  
 1. 403.1 MINIMUM FIXTURES FOR MERCANTILE AND STORAGE -
 1 DRINKING FOUNTAIN IS REQUIRED.
  
 2. 403.1 MINIMUM FIXTURES FOR STORAGE - 1 SERVICE SINK
 IS REQUIRED.
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  

Review Stop Z ZONING
Rev No 1 Status N Date 2011-07-22 Cont ID  
Sent By astelly Date 2011-07-22 Time 10:59 Rev Time 0.00
Received By astelly Date 2011-07-22 Time 10:59 Sent To  
Notes
***NONE***