Plan Review Details - Permit 11060750
Plan Review Stops For Permit 11060750
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2011-09-08 Cont ID  
Sent By shill Date 2011-09-08 Time 12:48 Rev Time 0.00
Received By shill Date 2011-09-08 Time 12:48 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2011-08-24 Cont ID  
Sent By shill Date 2011-08-24 Time 15:00 Rev Time 0.00
Received By shill Date 2011-08-24 Time 15:00 Sent To  
Notes
2011-08-24 15:00:43****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. PROVIDE A COPY OF THE RECORDED UNITY OF TITLE,
 FBC708.
  
 THIS MAY BE PROVIDED VIA EMAIL IF ALL OTHER TRADES PASS
 REVIEW.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-07-05 Cont ID  
Sent By shill Date 2011-07-05 Time 09:35 Rev Time 0.00
Received By shill Date 2011-07-05 Time 09:35 Sent To  
Notes
2011-07-05 09:57:06****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. PROVIDE A COPY OF THE RECORDED UNITY OF TITLE,
 FBC708.
  
 THIS MAY BE PROVIDED VIA EMAIL IF ALL OTHER TRADES PASS
 REVIEW.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2011-08-16 Cont ID  
Sent By rlecky Date 2011-08-16 Time 10:48 Rev Time 0.00
Received By rlecky Date 2011-08-16 Time 10:48 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2011-07-13 Cont ID  
Sent By rlecky Date 2011-07-13 Time 09:13 Rev Time 0.00
Received By rlecky Date 2011-07-13 Time 10:47 Sent To  
Notes
2011-07-13 09:15:08ELECTRICAL PLAN INSUFFICIENTLY DETAILED TO APPROVE FOR
 CONSTRUCTION. PLEASE PROVIDE THE FOLLOWING:
  
 INDICATE THE SIZE, RATING, VOLTAGE, LOCATION OF THE
 EXISTING SERVICE, MAIN DISCONNECTS AND PANELBOARD.
 PROVIDE PANEL SCHEDULES AND LOAD CALCULATION. PROVIDE
 AN ELECTRICAL RISER DIAGRAM. INCLUDE NEW AND EXISTING
 LOADS. NEC 215.5
 PROVIDE DEDICATED 20 AMP BRANCH CIRCUITS AS REQUIRED
 FOR BATH ROOM AND KITCHEN AREAS. NEC 210.11
 ADD RECEPTACLES SO THAT NO WALL SPACE IS MORE THAN 6
 FEET FROM A RECEPTACLE AND ALL WALL SPACES MORE THAN 2
 FEET IN WIDTH HAVE A RECEPTACLE. NEC 210.52
 RECEPTACLES ARE REQUIRED IN HALLWAYS. NEC 210.52 (H)
 GFCI PROTECTED RECEPTACLES ARE REQUIRED ON THE
 BALCONIES. NEC 210.52(E)
 ALL GENERAL PURPOSE OUTLETS INCLUDING THOSE IN THE
 BEDROOMS AND SMOKE ALARMS MUST BE AFCI PROTECTED. NEC
 210.12(B)
 NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11
 AT LEAST ONE WALL SWITCH-CONTROLLED LIGHTING OUTLET IS
 REQUIRED IN EVERY HABITABLE ROOM. NEC 210.70 (A)(1).
 REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE DETECTORS. IF THE
 RESIDENCE HAS GAS APPLIANCES, AN ATTACHED GARAGE OR A
 FIRE PLACE A CARBON MONOXIDE DETECTOR IS REQUIRED
 WITHIN TEN FEET OF EACH ROOM USED FOR SLEEPING. FBC
 R313
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 561-805-6718
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2011-07-05 Cont ID  
Sent By wjolin Date 2011-06-30 Time 15:45 Rev Time 0.00
Received By wjolin Date 2011-06-30 Time 15:45 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-08-24 Cont ID  
Sent By shill Date 2011-09-08 Time 12:40 Rev Time 0.00
Received By shill Date 2011-08-16 Time 09:21 Sent To  
Notes
2011-08-19 12:10:228/19 MECHANICAL PLAN ROUTED TO B6
2011-08-18 17:38:51PLUMBING PLAN ROUTED TO B6
  
2011-08-16 09:21:45INCOMING SENT TO B-6. JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-07-13 Cont ID  
Sent By shill Date 2011-07-13 Time 12:55 Rev Time 0.00
Received By shill Date 2011-06-29 Time 15:49 Sent To  
Notes
2011-06-29 15:50:22*********************EXPEDITED************************
 B--6

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2011-08-24 Cont ID  
Sent By shill Date 2011-08-24 Time 15:01 Rev Time 0.00
Received By shill Date 2011-08-24 Time 15:01 Sent To  
Notes
2011-08-24 15:01:44OK PER HM

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2011-07-06 Cont ID  
Sent By shill Date 2011-07-06 Time 12:32 Rev Time 0.00
Received By shill Date 2011-07-06 Time 12:32 Sent To  
Notes
2011-07-06 12:36:27****CORRECTIONS****
  
 1. A MECHANICAL SUB PERMIT HAS BEEN REQUESTED
 (MECHANICAL CONTRACTOR SIGNED ON TO MASTER PERMIT
 APPLICATION) BUT NO MECHANICAL PLANS SUBMITTED. EITHER
 SUBMIT PLANS FOR REVIEW OR PLEASE ADVISE AND THE
 MECHANICAL SUB PERMIT 11060752 WILL BE VOIDED (PLANS
 AND APPLICATION TO BE SUBMITTED AFTER ISSUANCE OF
 MASTER PERMIT).
  
 2. WHEN SUBMITTING MECHANICAL PLANS, PLEASE NOTE THAT
 AN EXHAUST FAN IS SHOWN ON ELECTRICAL SHEETS BUT
 VENTILATION NOT ADDRESSED FOR THE PROPOSED STEAM AREA
 (ROOM MARKED "HER BATH," NEW SHOWER AREA). FBC
 MECHANICAL 403.
  
 HAROLD MOSER, MECHANICAL PLANS EXAMINER
 561-805-6732
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2011-08-24 Cont ID  
Sent By lwagner Date 2011-08-24 Time 15:09 Rev Time 0.00
Received By lwagner Date 2011-08-24 Time 14:36 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2011-07-12 Cont ID  
Sent By lwagner Date 2011-07-12 Time 13:03 Rev Time 0.00
Received By lwagner Date 2011-07-12 Time 11:32 Sent To  
Notes
2011-07-12 13:00:33FBC PLUMBING 2007 REVIEW #1
 DENIED:
  
 1. A PLUMBING SUB PERMIT HAS BEEN REQUESTED (PLUMBING
 CONTRACTOR IS SIGNED ON TO MASTER PERMIT APPLICATION)
 BUT NO PLUMBING PLANS WERE SUBMITTED. PLEASE EITHER
 SUBMIT PLANS FOR REVIEW OR ADVISE AND THE PLUMBING SUB
 PERMIT 11060753 WILL BE VOIDED (PLANS AND APPLICATION
 TO BE SUBMITTED AFTER ISSUANCE OF MASTER PERMIT).
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  
  

Review Stop Z ZONING
Rev No 1 Status N Date 2011-07-13 Cont ID  
Sent By aaponte Date 2011-07-13 Time 13:21 Rev Time 0.00
Received By aaponte Date 2011-07-13 Time 13:21 Sent To  
Notes
2011-07-13 13:21:45ALL INTERIOR-RESIDENTIAL USE.