 REVIEW COMMENTS - FIRE DEPARTMENT
  
 ELEVATOR RECALL IS NOT REQUIRED; HOWEVER, A HEAT
 DETECTOR OR FLOW SWITCH WITHOUT TIME DELAY IS NEEDED TO
 SHUNT TRIP POWER TO THE ELEVATOR PRIOR TO SPRINKLER
 ACTIVATION IN THE ELEVATOR MACHINE ROOM.
  
 FIRE ALARM NOTES #14: DUCT SMOKE DETECTORS SHALL
 INITIATE A GENERAL FIRE ALARM CONDITION PER LOCAL CODE
 AMENDMENTS.
  
 VOICE EVACUATION MESSAGE SHALL STATE AN EMERGENCY HAS
 BEEN REPORTED AND ALL OCCUPANTS ARE TO LOCATE THE
 NEAREST EXIT AND EVACUATE THE BUILDING.
  