Plan Review Details - Permit 11060651
Plan Review Stops For Permit 11060651
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2011-08-02 Cont ID  
Sent By shill Date 2011-08-02 Time 11:06 Rev Time 0.00
Received By shill Date 2011-08-02 Time 11:06 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2011-07-11 Cont ID  
Sent By shill Date 2011-07-11 Time 15:29 Rev Time 0.00
Received By shill Date 2011-07-11 Time 15:29 Sent To  
Notes
2011-07-11 15:43:45****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. DESIGN PRESSURES WERE NOT SPECIFIED. A TABLE WAS
 PROVIDED, BUT THIS PARCEL IS LOCATED IN EXPOSURE C.
 THEREFORE, THE FACTORS IN FBC RESIDENTIAL R 301.2(3)
 ARE TO BE APPLIED. DESIGN PRESSURES WILL EXCEED
 +-40PSF. PLEASE REVISE INSTALLATION SCHEDULE.
  
 2. BOTTOM SUBSTRATE AND SIDE SUBSTRATES (FOR HORIZONTAL
 INSTALLATIONS) ARE MASONRY (FILLED CELLS). CONCRETE
 SPECIFIED ON INSTALLATION SCHEDULE. EITHER REVISE OR
 PROVIDE INFORMATION AS TO HOW IT HAS BEEN DETERMINED
 THAT THE SUBSTRATE IS CONCRETE. PLEASE REVISE
 INSTALLATION SCHEDULE.
  
 3. SEE OPENING 4, 114" OPENINGS INSTALLED HORIZONTALLY
 WITH A 3.5" EDGE DISTANCE EXCEEDS 10'. THIS IS NOT
 PERMITTED IN THE PRODUCT APPROVAL. PLEASE ADDRESS.
  
 AN ATTEMPT WAS MADE TO REDLINE THE INSTALLATION
 SCHEDULE, BUT IT IS NOT CLEAR WHETHER OR NOT THIS
 PRODUCT COMPLIES WITH THE REQUIREMENTS OF THE SITE/WIND
 RESISTANCE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-06-27 Cont ID  
Sent By shill Date 2011-06-27 Time 12:04 Rev Time 0.00
Received By shill Date 2011-06-27 Time 12:03 Sent To  
Notes
2011-06-27 12:08:11****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. TWO COMPLETE SETS OF PERMIT DOCUMENTS REQUIRED.
 PLEASE BE ADVISED THAT, IF TWO SETS ARE NOT SUBMITTED,
 ADDITIONAL FEES WILL BE CHARGED.
  
 2. DIRECT MOUNT PROPOSED; THE NAMING CONVENTION SHOULD
 CORRELAT WITH THE ANCHOR CHARTS ON PAGE 7. IT APPEARS
 THAT THIS IS SECTION 1.
  
 3. PANEL MATES ARE PROPOSED AS FASTENER, PLEASE ADVISE
 AS TO WHERE THIS IS LOCATED IN THE PRODUCT APPROVAL.
  
 4. NO EDGE DISTANCE OR SHUTTER GLASS SEPARATION
 INFORMATION WAS PROVIDED. PLEASE REVISE THE FORM.
 PLEASE ALSO SEE THE CHART ON SHEET 7; EDGE DISTANCE
 LESS THAN 3 1/2" REQUIRES A FACTOR TO BE APPLIED TO THE
 ANCHOR SPACING IN THE CHARTS.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2011-08-02 Cont ID  
Sent By shill Date 2011-08-02 Time 11:06 Rev Time 0.00
Received By shill Date 2011-07-27 Time 16:55 Sent To  
Notes
2011-07-27 16:55:34SENT TO SAMANTHA'S DESK FOR REVIEW.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-08-02 Cont ID  
Sent By shill Date 2011-08-02 Time 11:07 Rev Time 0.00
Received By shill Date 2011-07-08 Time 10:35 Sent To  
Notes
2011-07-08 10:35:24TO SH DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-06-27 Cont ID  
Sent By shill Date 2011-06-27 Time 12:08 Rev Time 0.00
Received By shill Date 2011-06-24 Time 15:39 Sent To  
Notes
2011-06-24 15:40:21BUILDING UNDER 5 K