Plan Review Details - Permit 11060648
Plan Review Stops For Permit 11060648
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2011-08-04 Cont ID  
Sent By rlecky Date 2011-08-04 Time 10:53 Rev Time 0.00
Received By rlecky Date 2011-08-04 Time 10:53 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2011-07-05 Cont ID  
Sent By rlecky Date 2011-07-05 Time 12:03 Rev Time 0.00
Received By rlecky Date 2011-07-05 Time 11:56 Sent To  
Notes
2011-07-05 12:05:48 
 PROVIDE ELECTRICAL RISER PLAN SHOWING OVERHEAD SERVICE,
 CONDUIT, WIRE AND GROUNDING.
 RECEPTACLES IN KITCHEN AREAS SHALL BE GFCI PROTECTED.
 NEC 210.8
 REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE DETECTORS WITH BATTER BACK
 UP. HOMES WHICH FEATURE GAS APPLIANCES, AN ATTACHED
 GARAGE OR A FIRE PLACE REQUIRE A CARBON MONOXIDE
 DETECTOR WITHIN TEN FEET OF EACH ROOM USED FOR
 SLEEPING. FBC R313
 PROVIDE AN INTERSYSTEM BONDING STRIP AT THE SERVICE
 GROUND. NEC 250.94
 RECEPTACLES MUST BE ARC FAULT CIRCUIT PROTECTED AND
 TAMPER RESISTANT. NEC 406.11, NEC 210-12 (B)
 A GFCI PROTECTED RECEPTACLE IS REQUIRED AT MAIN
 ENTRANCE. NEC 210.52
  
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 561-805-6718
  
  
  
2011-06-24 15:41:44UNDER 5 K ELECTRIC

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-08-04 Cont ID  
Sent By rlecky Date 2011-08-04 Time 10:53 Rev Time 0.00
Received By rlecky Date 2011-08-02 Time 15:33 Sent To  
Notes
2011-08-02 15:33:45TO ELECTRIC BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-07-05 Cont ID  
Sent By rlecky Date 2011-07-05 Time 12:18 Rev Time 0.00
Received By rlecky Date 2011-06-24 Time 15:42 Sent To  
Notes
2011-06-24 15:42:43UNDER 5 K ELECTRIC