Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2011-07-05 Cont ID  
Sent By wjolin Date 2011-07-05 Time 12:59 Rev Time 0.00
Received By wjolin Date 2011-07-05 Time 12:49 Sent To M
Notes
2011-07-05 12:58:38901 45TH STREET
 PERMIT #11060458
 MASTER #11010154
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 *****PROVISO*****
  
 INDICATE ON SHEET FP4.0 THE METHOD BEING USED TO
 ACCOMPLISH SHUNT TRIPPING THE POWER TO THE ELEVATOR
 UPON ACTIVATION OF A SPRINKLER LOCATED IN THE ELEVATOR
 MACHINE ROOM. POWER SHUNT TRIP SHALL BE ACCOMPLISHED
 WITH HEAT DETECTORS LOCATED WITHIN 2 FEET OF SPRINKLERS
 OR A FLOW SWITCH DEVICE WITHOUT TIME DELAY
 CAPABILITIES.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2011-06-27 Cont ID  
Sent By wjolin Date 2011-06-27 Time 08:16 Rev Time 0.00
Received By wjolin Date 2011-06-27 Time 07:42 Sent To M
Notes
2011-06-27 08:15:57901 45TH STREET (OPERATING ROOM, 3RD FL, ELEVATOR
 MACHINE ROOM)
 PERMIT #11060458
 MASTER #11010154
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 HYDRAULIC CALCULATIONS NOT SUBMITTED.
  
 SCOPE OF WORK INDICATES CHANGES TO THE THIRD FLOOR AND
 ELEVATOR MACHINE ROOM. PLANS SHOWING THIS WORK DO NOT
 APPEAR TO HAVE BEEN SUBMITTED.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-07-06 Cont ID  
Sent By shill Date 2011-07-06 Time 13:15 Rev Time 0.00
Received By shill Date 2011-07-05 Time 12:49 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-06-27 Cont ID  
Sent By hmoser Date 2011-06-27 Time 13:20 Rev Time 0.00
Received By hmoser Date 2011-06-20 Time 13:47 Sent To  
Notes
2011-06-20 13:47:51SENT TO FIRE BOX FOR REVIEW.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2011-07-06 Cont ID  
Sent By shill Date 2011-07-06 Time 13:15 Rev Time 0.00
Received By hmoser Date 2011-07-06 Time 12:23 Sent To  
Notes
2011-07-06 13:15:53OK PER HM

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2011-06-27 Cont ID  
Sent By hmoser Date 2011-06-27 Time 13:16 Rev Time 0.00
Received By hmoser Date 2011-06-27 Time 13:06 Sent To  
Notes
2011-06-27 13:20:13PLANS DENIED
 THIRD FLOOR AND ELEVATOR MACHINE ROOM WERE NOT
 SUBMITTED WITH THE PLANS.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved