Plan Review Details - Permit 11060458
| Plan Review Stops For Permit 11060458 |
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2011-07-05 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2011-07-05 |
Time |
12:59 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2011-07-05 |
Time |
12:49 |
Sent To |
M |
|
| Notes |
| 2011-07-05 12:58:38 | 901 45TH STREET | | | PERMIT #11060458 | | | MASTER #11010154 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | *****PROVISO***** | | | | | | INDICATE ON SHEET FP4.0 THE METHOD BEING USED TO | | | ACCOMPLISH SHUNT TRIPPING THE POWER TO THE ELEVATOR | | | UPON ACTIVATION OF A SPRINKLER LOCATED IN THE ELEVATOR | | | MACHINE ROOM. POWER SHUNT TRIP SHALL BE ACCOMPLISHED | | | WITH HEAT DETECTORS LOCATED WITHIN 2 FEET OF SPRINKLERS | | | OR A FLOW SWITCH DEVICE WITHOUT TIME DELAY | | | CAPABILITIES. | | | | | | WESLEY JOLIN | | | WEST PALM BEACH FIRE RESCUE | | | FIRE & LIFE SAFETY PLAN REVIEW | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2011-06-27 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2011-06-27 |
Time |
08:16 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2011-06-27 |
Time |
07:42 |
Sent To |
M |
|
| Notes |
| 2011-06-27 08:15:57 | 901 45TH STREET (OPERATING ROOM, 3RD FL, ELEVATOR | | | MACHINE ROOM) | | | PERMIT #11060458 | | | MASTER #11010154 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | HYDRAULIC CALCULATIONS NOT SUBMITTED. | | | | | | SCOPE OF WORK INDICATES CHANGES TO THE THIRD FLOOR AND | | | ELEVATOR MACHINE ROOM. PLANS SHOWING THIS WORK DO NOT | | | APPEAR TO HAVE BEEN SUBMITTED. | | | | | | WESLEY JOLIN | | | WEST PALM BEACH FIRE RESCUE | | | FIRE & LIFE SAFETY PLAN REVIEW |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2011-07-06 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2011-07-06 |
Time |
13:15 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2011-07-05 |
Time |
12:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2011-06-27 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2011-06-27 |
Time |
13:20 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2011-06-20 |
Time |
13:47 |
Sent To |
|
|
| Notes |
| 2011-06-20 13:47:51 | SENT TO FIRE BOX FOR REVIEW. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2011-07-06 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2011-07-06 |
Time |
13:15 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2011-07-06 |
Time |
12:23 |
Sent To |
|
|
| Notes |
| 2011-07-06 13:15:53 | OK PER HM |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2011-06-27 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2011-06-27 |
Time |
13:16 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2011-06-27 |
Time |
13:06 |
Sent To |
|
|
| Notes |
| 2011-06-27 13:20:13 | PLANS DENIED | | | THIRD FLOOR AND ELEVATOR MACHINE ROOM WERE NOT | | | SUBMITTED WITH THE PLANS. | | | PLAN REVIEW BY HAROLD MOSER 561-805-6732 | | | [email protected] |
|
|
|