Plan Review Details - Permit 11060441
Plan Review Stops For Permit 11060441
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2011-06-23 Cont ID  
Sent By jwitmer Date 2011-06-23 Time 15:48 Rev Time 0.00
Received By jwitmer Date 2011-06-23 Time 10:46 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2011-07-21 Cont ID  
Sent By rlecky Date 2011-07-21 Time 14:58 Rev Time 0.00
Received By rlecky Date 2011-07-21 Time 14:00 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2011-07-19 Cont ID  
Sent By rlecky Date 2011-07-19 Time 16:41 Rev Time 0.00
Received By rlecky Date 2011-07-19 Time 15:58 Sent To  
Notes
2011-07-19 16:49:34REQUIRES ELECTRICAL SCHEMATIC SHOWING BRANCH CIRCUITS,
 DISCONNECTS, CIRCUITRY, EQUIPMENT GROUNDING, GFCI
 PROTECTION. NEC 680.21
 GENERAL PURPOSE GFCI RECEPTACLE REQUIRED FOR SERVICE.
 NEC 680.22
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 561-805-6718
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2011-07-14 Cont ID  
Sent By mgonzale Date 2011-07-14 Time 15:58 Rev Time 0.50
Received By mgonzale Date 2011-07-14 Time 15:58 Sent To  
Notes
2011-07-14 15:58:34PASSED.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-07-21 Cont ID  
Sent By rlecky Date 2011-07-21 Time 14:58 Rev Time 0.00
Received By rlecky Date 2011-07-21 Time 13:57 Sent To  
Notes
2011-07-21 13:57:27TO ELECTRIC

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-07-19 Cont ID  
Sent By lmartine Date 2011-07-14 Time 15:26 Rev Time 0.00
Received By lmartine Date 2011-06-20 Time 08:50 Sent To  
Notes
2011-06-20 08:50:10C11
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2011-06-28 Cont ID  
Sent By lwagner Date 2011-06-28 Time 11:19 Rev Time 0.00
Received By lwagner Date 2011-06-28 Time 11:19 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2011-07-11 Cont ID  
Sent By ajones Date 2011-07-11 Time 10:56 Rev Time 0.00
Received By ajones Date 2011-07-11 Time 10:56 Sent To  
Notes
2011-07-11 11:12:471. PURSUANT TO THE DRAINAGE EASEMENT AGREEMENT SIGNED
 ON 2/4/2005, THE POOL DECK IS PERMITTED WITHIN THE
 DRAINAGE EASMENT.
  
 2. A FENCE PERMIT SHALL BE SUBMITTED PRIOR TO FINAL
 INSPECTION.
  
 3. A LANDSCAPE PERMIT MUST BE SUBMITTED, ISSUED,
 INSTALLED AND INSPECTED PRIOR TO THE ISSUANCE OF A CO.
  
 4. PRIOR TO THE ZONING INSPECTION, PLEASE CLARIFY WHAT
 "PA" STANDS FOR ON THE PLANS.
  

Review Stop Z ZONING
Rev No 1 Status F Date 2011-06-29 Cont ID  
Sent By eschneid Date 2011-06-29 Time 08:55 Rev Time 0.75
Received By eschneid Date 2011-06-29 Time 08:55 Sent To  
Notes
2011-06-29 09:51:19FAILED
  
 PLEASE RESPOND TO COMMENTS IN WRITING.
  
 1) THE POOL DECK IS SHOWN WITHIN THE OKEECHOBEE
 BOULEVARD DRAINAGE EASEMENT. PRIOR TO ZONING APPROVAL
 OF THE PERMIT, SUBMIT EITHER AN EASEMENT RELEASE FROM
 PALM BEACH COUNTY TO ALLOW THE POOL DECK WITHIN THE
 DRAINAGE EASEMENT, OR REVISE THE PLANS TO MOVE THE DECK
 OUT OF THE DRAINAGE EASEMENT.
  
 2) PRIOR TO ZONING APPROVAL OF THE PERMIT, SUBMIT A
 FENCE PERMIT FOR THE PERIMETER FENCE AND GATES. PLEASE
 NOTE THAT THE LOCATION OF THE PERIMETER FENCE SHOWN ON
 THE PLANS ENCROACHES INTO THE DRAINAGE EASEMENT AND
 THUS REQUIRES AN EASEMENT RELEASE FROM PALM BEACH
 COUNTY.
  
 3) THE OAKTON COMMONS CPD REGULATIONS REQUIRE THAT
 MECHANICAL EQUIPMENT BE SCREENED BY A VISUALLY OPAQUE
 BARRIER OR EQUIVALENT LANDSCAPE MATERIAL. PRIOR TO
 ZONING APPROVAL OF THIS PERMIT, SUBMIT DETAILS ON HOW
 THE SCREENING WILL BE ACHIEVED. IF IT WILL BE THROUGH
 THE USE OF AN OPAQUE FENCE, PLEASE INCLUDE THAT
 INFORMATION WITH THE FENCE PERMIT. PLEASE NOTE THAT THE
 POOL EQUIPMENT PAD APPEARS TO ENCROACH THE DRAINAGE
 EASEMENT, SO THIS SHOULD BE INCLUDED ON ANY PALM BEACH
 COUNTY EASEMENT RELEASE.
  
 4) PLEASE CLARIFY WHAT "PA." STANDS FOR ON THE PLANS
 (SHOWN OUTSIDE THE EDGE OF THE DECK).
  
 5) WHY IS THE SAFETY EQUIPMENT BEING PROPOSED ON THE
 FENCE WHERE IT WILL BLOCK THE VIEW OF THE LAKE? IT
 SEEMS THAT IT WOULD BE BETTER LOCATED ON THE POOL
 EQUIPMENT FENCE.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  
  