Plan Review Details - Permit 11060408
Plan Review Stops For Permit 11060408
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2011-06-23 Cont ID  
Sent By jgomez Date 2011-06-23 Time 11:20 Rev Time 0.00
Received By jgomez Date 2011-06-23 Time 11:20 Sent To  
Notes
2011-06-23 11:24:19BUILDING REPAIRS APPROVED WITH PROVISO:
  
 1- WORK NEEDS TO BE DONE BY LICENSED CONTRACTOR.
  
 2- PROVIDE PRODUCT APPROVALS (2 COPIES) FOR WINDOWS.
  
 3- CLOSING FRONT PORCH AND INSTALLING NEW STEPS ARE NOT
 REPAIRS. SEPARATE PERMIT WITH PLANS AND DETAILS IS
 REQUIRED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-06-22 Cont ID  
Sent By jgomez Date 2011-06-22 Time 10:14 Rev Time 0.00
Received By jgomez Date 2011-06-22 Time 10:14 Sent To  
Notes
2011-06-22 10:15:15***DENIED:
 1) OWNER SUBMITTED PERMITS 10110532 AND 10110533 TO
 ADDRESS RED-TAGS BY TOM MOORE. AFTER ALL REVIEWS WERE
 DONE, COMMENTS WERE NEVER ADDRESSED BY THE OWNER TO
 OBTAIN THE PERMITS. THIS NEW PERMIT APPLICATION DOESN'T
 REFLECT THE SCOPE OF WORK REQUIRED TO SATISFY THE
 COMMENTS REQUIRED BY ALL THE TRADES WHEN THE FIRST
 REVIEW WAS DONE. NEED PLANS FOR REVIEW. SEC. 106.1 CITY
 AMENDMENTS TO FBC. COORDINATE WITH ITEM #3) BELOW.
  
 2) NEED CONTRACTORS TO APPLY FOR ALL PERMITS. TOTAL
 SCOPE OF WORK IS MORE THAN $5000. BROKER CAN'T APPLY AS
 AN OWNER/BUILDER. SEC. 489.103(17)
  
 3) SEE CHECKLIST BELOW FOR ITEMS THAT NEED TO BE
 ADDRESSED ON PREVIOUS PERMIT NUMBERS 10110532 AND
 10110533. PROVIDE ALL THE REQUIRED INFORMATION.
  
 4) NEED A SEPARATE PERMIT APPLICATION FOR EACH
 BUILDING. (MAIN HOUSE AND REAR BUILDING). SAME PLANS
 MAY BE USED, BUT NEED SEPARATE PERMIT APPLICATIONS.
 SEC. 106.1.3 CITY AMENDMENTS TO FBC.
  
  
 ***THE FOLOWING IS THE ORIGINAL CHECKLIST THAT WAS
 NEVER ADDRESSED TO OBTAIN THE PERMITS:
  
 RESIDENTIAL (R3) ALTERATION/RENOVATION BUILDING REVIEW
 CHECKLIST (COPY OF ORIGINAL CHECKLIST).
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 ***NOTE: SINCE SAME PLANS ARE SUBMITTED FOR REAR
 BUILDINGS AND MAIN RESIDENCE AND TWO DIFFERENT PERMIT
 APPLICATIONS ARE PROVIDED, THEN THESE COMMENTS APPLY
 FOR BOTH PERMIT APPLICATIONS. ADDRESS COMMENTS FOR REAR
 BUILDINGS AND FOR MAIN RESIDENCE ACCORDINGLY.
  
 1- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTE.
 ***NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK
 UP.
  
 2- AFTER PLANS ARE REVISED BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD) TO VERIFY IF IMPACT FEES ARE
 DUE. BRING BACK STAMPED PLANS AND COPY OF PAID RECEIPT
 IF FEES ARE DUE.
  
 3- NEED TO PROVIDE EMERGENCY EGRESS FROM BEDROOM. SEC.
 R310 OF 2007 FLORIDA RESIDENTIAL CODE.
  
 4- PROVIDE ENERGY CALCULATIONS. SEC. N1100.3 OF 2007
 FLORIDA RESIDENTIAL CODE CHAPTER 11. MAKE SURE CORRECT
 UPDATED FORM IS PROVIDED.
  
 5- ENGINEER OF RECORD TO SPECIFY ON PLANS TYPE OF
 ALTERATION AS REQUIRED BY SEC. 401.4 OF 2007
 FBC-EXISTING BUILDING.
  
 6- BATHROOM IS MISSING THE DIMENSIONS. SEC. R307.1.
  
 7- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9B-72 FOR:
 A) ALL WINDOWS TO BE INSTALLED.
 B) ALL EXTERIOR DOORS TO BE INSTALLED.
 C) WINDOW MULLIONS AS SHOWN ON PLANS.
 C) SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS.
 D) ROOF SHINGLES.
 E) FLAT ROOF. IDENTIFY APPROVED ASSEMBLY TO BE USED AND
 PROVIDE CORRESPONDING RAS 117 CALCULATIONS. SEE GENERAL
 LIMITATION #7 TO SEE IF SIGNED AND SEALED RAS 117
 CALCULATIONS ARE REQUIRED.
  
 8- SPECIFY HURRICANE OPENING PROTECTION AS REQUIRED BY
 SEC. R301.2.1.2 OF 2007 FLORIDA RESIDENTIAL CODE AND
 SEC. 606.4 OF 2007 FLORIDA BUILDING CODE-EXISTING.
 SPECIFY IF PROVIDING DOORS AND WINDOWS WITH IMPACT
 GLASS OR IF PROVIDING STORM SHUTTERS. STORM SHUTTERS
 REQUIRE PRODUCT APPROVAL AND COMPLETE INSTALLATION
 SCHEDULE.
  
 9- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS PRIOR
 TO SUBMITTAL. SEC. 106.3.3 CITY AMENDMENTS TO FBC.
  
 10- EXTERIOR ELEVATIONS SHOW ROOF OUTLOOKERS. WALL
 SECTION A/A1 SHOWS FASCIA BOARD. REVISE AS REQUIRED TO
 MATCH. SEC. 106.1.1 CITY AMENDMENTS TO FBC.
  
 11- VALUE DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUE TO INCLUDE ALL LABOR, MATERIALS AND
 ENGINEERING FEES. REVISE AS REQUIRED BY SEC. 108.3 CITY
 AMENDMENTS TO FBC. SPECIFY VALUE FOR THE REAR BUILDINGS
 AND VALUE FOR THE MAIN RESIDENCE ON CORRESPONDING
 PERMIT APPLICATION. VALUE TO INCLUDE ALL MATERIALS,
 LABOR AND ENGINEERING FEES.
  
 12- WALL SECTION A/A1:
 A) INSTALLING R30 INSULATION DOESN'T ALLOW THE
 CROSS-VENTILATION REQUIRED BY SEC. R806 BECAUSE THERE
 IS NO ROOM. THE THICKNESS OF R-30 WILL FILL THE 2X10
 JOIST, THEREFORE LEAVING NO ROOM FOR AIR CIRCULATION.
 REVISE AS REQUIRED.
  
 B) 2X10 JOIST BLOCKING DOESN'T ALLOW THE CROSS
 VENTILATION REQUIRED BY SEC. R806. THERE IS NO ROOM FOR
 AIR CIRCULATION. REVISE AS REQUIRED.
  
 C) SPECIFY THE HURRICANE JOIST CONNECTORS TO VERIFY
 COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. R301.
  
 D) UPLIFT LOAD CALCULATIONS: CLARIFY WHY LATERAL LOADS
 ARE N.A. SEC. R301.
  
 13- SHEET A-1:
 A) SPECIFY SAFETY GLASS ON BATHROOM. SEC. R308.4.
  
 B) REVISE SCOPE OF WORK NOTES: * THERE IS STRUCTURAL
 WORK ON THIS PROJECT. NOTE #2 SAYS NO. REVISE AS
 REQUIRED.
  
 ** NOTE #5 SAYS NO WORK ON MAIN HOUSE. PERMIT
 APPLICATION CALLS FOR RENOVATION/REPAIRS, ETC.
 COORDINATE SCOPE OF WORK WITH CONTRACTOR. REVISE AS
 REQUIRED TO MATCH.
  
 14- SHEET A-2:
 A) PROVIDE SMOKE ALARM ON OFFICE/BEDROOM. SEC. R313.
 THIS ROOM HAS THE LAYOUT OF A BEDROOM ALSO.
  
 B) WOOD FRAMING DETAIL, WALL SECTION A/A-2 AND WOOD
 WALL INFILL DETAIL NEED TO SPECIFY 2 LAYERS OF WATER
 VAPOR BARRIER AS REQUIRED BY SEC. R703.6.3.
  
 15- WALL SECTION A/A-2:
 A) SPECIFY TRUSS CONNECTORS. SEC. R301.
  
 B) SHOW DOUBLE TOP PLATES. SEC. 106.1.1 CITY AMENDMENTS
 TO FBC.
  
 C) COORDINATE WALL SHEATHING NAILING SPACING WITH
 SPECIFICATIONS SHOWN ON WOOD FRAMING DETAIL AND WOOD
 WALL INFILL DETAIL. SEC. 106.1.1 CITY AMENDMENTS TO
 FBC.
  
 D) SPECIFY HOW PROVIDING WALL WOOD FRAMING FRAMING
 MEMBERS PROTECTION AGAINST DECAY AS REQUIRED BY SEC.
 R319.1.
  
 E) SPECIFY THE CLEARANCE FROM GRADE TO THE STUCCO TO
 VERIFY COMPLIANCE WITH THE TERMITE PROTECTION AS
 REQUIRED BY SEC. R704.
  
 16- SHEET A-3:
 A) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR NEW
 ENTRY STAIR LANDING AND STAIRS TO SHOW COMPLIANCE WITH
 SEC. R311 AND R312. INCLUDE ALL THE REQUIRED
 DIMENSIONS.
  
 B) SPECIFY SAFETY GLASS ON BATHROOM WINDOW IF THE
 WINDOW IS GOING TO BE REPLACED. SEC. R308.4.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712
  
  
2011-06-17 09:44:58INCOMING SENT TO JULIOS' DESK. JW

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2011-06-23 Cont ID  
Sent By rlecky Date 2011-06-23 Time 10:26 Rev Time 0.00
Received By rlecky Date 2011-06-23 Time 10:26 Sent To  
Notes
2011-06-23 10:27:01SCOPE OF WORK DID NOT INCLUDE ELECTRIC AT THIS TIME.

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2011-06-23 Cont ID  
Sent By jpapa Date 2011-06-23 Time 11:53 Rev Time 0.00
Received By jpapa Date 2011-06-23 Time 11:53 Sent To  
Notes
2011-06-23 11:55:20***PROVISOS***
  
 !. STUCCO REPAIR SHALL MATCH THE EXISTING TEXTURE.
 2. THE FRONT PORCH SHALL NOT BE ENCLOSED. HISTORIC
 PRESERVATION BOARD APPROVAL IS REQUIRED FOR A CHANGE IN
 OPENINGS ON THE MAIN FA?ADE OF A DESIGNATED HISTORIC
 STRUCTURE. PLEASE CONTACT THE HISTORIC PRESERVATION
 DIVISION FOR APPLICATION REQUIREMENTS.
 3. A DETAILED WINDOW AND DOOR SCHEDULE AND PRODUCT
 APPROVAL SHALL BE SUBMITTED AND APPROVED BY THE
 HISTORIC PRESERVATION DIVISION PRIOR TO REMOVAL,
 ALTERATION OF WINDOW OPENINGS OR INSTALLATION OF
 REPLACEMENT PRODUCTS. VINYL WINDOW PRODUCT ARE NOT
 PERMITTED WITHIN HISTORIC DISTRICTS.
  
 FOR MORE INFORMATION, PLEASE CONTACT JILLIAN PAPA,
 HISTORIC PRESERVATION PLANNER AT 561-822-1454.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-06-23 Cont ID  
Sent By jgomez Date 2011-06-23 Time 12:08 Rev Time 0.00
Received By jgomez Date 2011-06-23 Time 11:25 Sent To  
Notes
2011-06-23 09:16:35PLANS ON SHELF R3 FOR REVIEW.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status N Date 2011-06-23 Cont ID  
Sent By jgomez Date 2011-06-23 Time 11:25 Rev Time 0.00
Received By jgomez Date 2011-06-23 Time 11:25 Sent To  
Notes
2011-06-23 11:26:14ONLY REPAIRS AT THIS TIME.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2011-06-22 Cont ID  
Sent By jgomez Date 2011-06-22 Time 16:34 Rev Time 0.00
Received By jgomez Date 2011-06-22 Time 16:34 Sent To  
Notes
2011-06-22 16:34:37AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD) TO VERIFY IF IMPACT FEES ARE
 DUE. BRING BACK STAMPED PLANS AND COPY OF PAID RECEIPT
 IF FEES ARE DUE

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2011-06-23 Cont ID  
Sent By jgomez Date 2011-06-23 Time 11:26 Rev Time 0.00
Received By jgomez Date 2011-06-23 Time 11:26 Sent To  
Notes
2011-06-23 11:27:29NO MECHANICAL WORK. ONLY BUILDING REPAIRS.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2011-06-22 Cont ID  
Sent By jgomez Date 2011-06-22 Time 16:31 Rev Time 0.00
Received By jgomez Date 2011-06-22 Time 16:31 Sent To  
Notes
2011-06-22 16:32:19RESIDENTIAL (R3) ALTERATION/RENOVATION MECHANICAL
 REVIEW CHECKLIST.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- NO INFORMATION SUBMITTED FOR REVIEW. NEED COMPLETE
 PLANS AND A/C LOAD CALCULATIONS.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop P PLUMBING
Rev No 2 Status N Date 2011-06-23 Cont ID  
Sent By jgomez Date 2011-06-23 Time 11:27 Rev Time 0.00
Received By jgomez Date 2011-06-23 Time 11:27 Sent To  
Notes
2011-06-23 11:28:13NO PLUMBING WORK. ONLY BUILDING REPAIRS.

Review Stop P PLUMBING
Rev No 1 Status F Date 2011-06-22 Cont ID  
Sent By jgomez Date 2011-06-22 Time 16:29 Rev Time 0.00
Received By jgomez Date 2011-06-22 Time 16:29 Sent To  
Notes
2011-06-22 16:30:42RESIDENTIAL (R3) ALTERATION/RENOVATION PLUMBING REVIEW
 CHECKLIST.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- SHEET A-1: PLUMBING RISER DIAGRAM IS MISSING THE
 CLOTHES WASHER.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop Z ZONING
Rev No 1 Status P Date 2011-06-23 Cont ID  
Sent By jpapa Date 2011-06-23 Time 11:56 Rev Time 0.00
Received By jpapa Date 2011-06-23 Time 11:56 Sent To  
Notes
2011-06-23 12:01:18***PROVISOS***
  
 1. ZONING APPROVAL GRANTED TO REPAIR WORK ONLY. NEW
 WORK MUST BE REVIEWED FOR COMPLIANCE WITH THE ZLDRS.
 TWO COPIES OF A SURVEY SHALL BE SUBMITTED WITH PLANS
 DEPICTING PROPOSED NEW WORK.
  
 2. IN THE EVENT THAT THE VALUE OF THE CONSTRUCTION
 EXCEEDS 50% OF THE STRUCTURE'S VALUE ACCORDING TO THE
 P.B.C. PROPERTY APPRAISER'S OFFICE PURSUANT TO SECTION
 94-441(C)(2) OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS (ZLDR), THE LANDSCAPE ON THE SITE SHALL BE
 IN COMPLIANCE WITH ALL APPLICABLE REGULATIONS FOUND IN
 ARTICLE XIV OF THE ZLDR. IF THE SITE CONFORMS TO
 ARTICLE XIV, THEN TWO (2) COPIES OF A LANDSCAPE PLAN
 DEMONSTRATING COMPLIANCE SHALL BE INCLUDED WITH THE
 PERMIT RE-SUBMITTAL. IF THE SITE DOES NOT CONFORM TO
 ARTICLE XIV, THEN PRIOR TO THE ZONING APPROVAL OF THIS
 PERMIT A SEPARATE LANDSCAPE PERMIT AND IRRIGATION
 PERMIT SHALL BE SUBMITTED SHOWING MATERIAL TO BRING THE
 SITE INTO CONFORMITY.
  
 FOR MORE INFORMATION, PLEASE CONTACT JILLIAN PAPA,
 HISTORIC PRESERVATION PLANNER AT 561-822-1454.