Plan Review Details - Permit 11060364
Plan Review Stops For Permit 11060364
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2011-07-08 Cont ID  
Sent By rmcdouga Date 2011-07-07 Time 07:57 Rev Time 0.00
Received By rmcdouga Date 2011-07-07 Time 07:32 Sent To Z
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-06-20 Cont ID  
Sent By rmcdouga Date 2011-06-20 Time 16:17 Rev Time 0.00
Received By rmcdouga Date 2011-06-20 Time 07:46 Sent To  
Notes
2011-06-20 15:31:392007 FBC W/2009 REVISIONS
  
 DENIED BY BUILDING
  
 1) SPECIFY THE DESIGN CRITERIA ON THE PLANS PER FBC R
 301. THE WINDSPEED IS 140 MPH AND THE EXPOSURE CATEGORY
 IS B.
  
 2) PROVIDE THE ROOF SCUPPER AND SECONDARY SCUPPER
 SIZING CALCULATIONS IN ACCORDANCE WITH FBC PLUMBING
 1106.7 AND 1107. INCLUDE HALF THE VERTICAL WALL AREA OF
 THE PARAPET WALL WITH THE ROOF AREA PER FBC R 1106.4.
 FBC R1107.3 STATES THAT SCUPPERS SHOULD NOT HAVE AN
 OPENING DIMENSION OF LESS THAN 4 INCHES.
  
 3) SHOW COMPLIANCE WITH FBC R 313.4 WHICH REQUIRES A
 CARBON MONOXIDE DETECTOR WITHIN 10 FEET OF EACH ROOM
 USED FOR SLEEPING PURPOSES.
  
 4) SHOW COMPLIANCE WITH FBC R 320 FOR TERMITE
 PROTECTION.
  
 5) SHOW COMPLIANCE WITH FBC R320.7 FOR THE SCUPPERS TO
 EMPTY INTO DOWNSPOUTS THAT DISCHARGE AT LEAST ONE FOOT
 FROM THE STRUCTURE SIDE WALL.
  
 6) SHOW COMPLIANCE WITH FBC R 703.6.3 WHICH REQUIRES A
 BOND BREAK BETWEEN THE EXTERIOR STUCCO AND THE
 WATER-RESISTIVE BARRIER.
  
 7) SHOW COMPLIANCE WITH FBC R 803.2.3.1 WHICH REQUIRES
 8D RING SHANK NAILS FOR FASTENING THE ROOF SHEATHING.
 (SHEET 2)
  
 8) SHOW COMPLIANCE WITH FBC R 408.1 UNDER FLOOR SPACE
 VENTILATION AND R408.4 ACCESS TO UNDER FLOOR SPACE.
  
 9) SHOW COMPLIANCE WITH FBC R 806.1 FOR ATTIC
 VENTILATION AND R 807.1 FOR ATTIC ACCESS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2011-06-20 Cont ID  
Sent By rmcdouga Date 2011-06-20 Time 09:53 Rev Time 0.00
Received By rmcdouga Date 2011-06-20 Time 09:53 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2011-06-15 Cont ID  
Sent By jpapa Date 2011-06-15 Time 14:51 Rev Time 0.25
Received By jpapa Date 2011-06-15 Time 14:51 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-07-07 Cont ID  
Sent By rmcdouga Date 2011-07-07 Time 07:57 Rev Time 0.00
Received By rmcdouga Date 2011-06-30 Time 16:09 Sent To  
Notes
2011-06-30 16:09:59INCOMING SENT TO R MC DOUGALS DESK. JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-06-20 Cont ID  
Sent By rmcdouga Date 2011-06-20 Time 16:17 Rev Time 0.00
Received By rmcdouga Date 2011-06-16 Time 08:22 Sent To  
Notes
2011-06-16 08:22:34R-5

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2011-07-07 Cont ID  
Sent By rmcdouga Date 2011-07-07 Time 07:12 Rev Time 0.00
Received By rmcdouga Date 2011-07-07 Time 07:12 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2011-06-20 Cont ID  
Sent By rmcdouga Date 2011-06-20 Time 07:46 Rev Time 0.00
Received By rmcdouga Date 2011-06-20 Time 06:54 Sent To  
Notes
2011-06-20 09:04:422007 FBC W/2009 REVISIONS
 DENIED BY MECHANICAL
  
 1) THE RETURN AIR TRANSFER DUCT FROM THE MASTER SUITE
 IS REQUIRED TO BE ONE AND ONE HALF TIMES THE CROSS
 SECTIONAL AREA OF THE SUPPLY DUCT ENTERING THE ROOM.
 THE PLANS SPECIFY A 10" SUPPLY FOR THE MASTER SUITE
 WHICH WILL REQUIRE 14" DIAMETER TRANSFER DUCT.
  
 2) THE EQUIPMENT SIZING CALCULATIONS SPECIFIES A LATENT
 COOLING EQUIPMENT TOTAL LOAD OF 29272 BTUH ( 2.5 TON)
 AND A TOTAL CAPACITY OF 3.0 TON. THE EXISTING UNIT IS
 2.5 TON. PLEASE CORRECT THE FORM.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status P Date 2011-06-17 Cont ID  
Sent By rmcdouga Date 2011-06-17 Time 13:25 Rev Time 0.00
Received By rmcdouga Date 2011-06-17 Time 13:25 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2011-07-08 Cont ID  
Sent By jpapa Date 2011-07-08 Time 13:56 Rev Time 0.00
Received By jpapa Date 2011-07-08 Time 13:57 Sent To  
Notes
2011-07-08 14:10:11PROVISO:
  
 ZONING APPROVAL SHALL BE CONTINGENT UPON DEMOSTRATED
 COMPLIANCE WITH SECTION 94-442 (B)(2)A OF THE ZONING
 AND LAND DEVELOPMENT REGULATIONS THROUGH LANDSCAPING
 PERMIT NO. 11060790. FOR MORE INFORMATION, PLEASE
 CONTACT JILLIAN PAPA, HISTORIC PRESERVATION PLANNET AT
 561-822-1454.

Review Stop Z ZONING
Rev No 1 Status F Date 2011-06-15 Cont ID  
Sent By jpapa Date 2011-06-15 Time 14:51 Rev Time 0.00
Received By jpapa Date 2011-06-15 Time 15:03 Sent To  
Notes
2011-06-15 15:03:30FAILED. LANDSCAPE COMPLIANCE MUST BE DEMOSTRATED.
  
 THE VALUE OF THE CONSTRUCTION ($144,900) EXCEEDS 50% OF
 THE STRUCTURE'S VALUE ($81,057) ACCORDING TO THE P.B.C.
 PROPERTY APPRAISER'S OFFICE; THEREFORE, PURSUANT TO
 SECTION 94-441(C)(2) OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS (ZLDR), THE LANDSCAPE ON THE SITE SHALL BE
 IN COMPLIANCE WITH ALL APPLICABLE REGULATIONS FOUND IN
 ARTICLE XIV OF THE ZLDR. IF THE SITE CONFORMS TO
 ARTICLE XIV, THEN TWO (2) COPIES OF A LANDSCAPE PLAN
 DEMONSTRATING COMPLIANCE SHALL BE INCLUDED WITH THE
 PERMIT RE-SUBMITTAL. IF THE SITE DOES NOT CONFORM TO
 ARTICLE XIV, THEN PRIOR TO THE ZONING APPROVAL OF THIS
 PERMIT A SEPARATE LANDSCAPE PERMIT AND IRRIGATION
 PERMIT SHALL BE SUBMITTED SHOWING MATERIAL TO BRING THE
 SITE INTO CONFORMITY.
  
 PLEASE CONTACT JILLIAN PAPA, HISTORIC PRESERVATION
 PLANNER AT 561 822-1454 FOR MORE INFORMATION.