| Plan Review Stops For Permit 11060364 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2011-07-08 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2011-07-07 |
Time |
07:57 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2011-07-07 |
Time |
07:32 |
Sent To |
Z |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2011-06-20 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2011-06-20 |
Time |
16:17 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2011-06-20 |
Time |
07:46 |
Sent To |
|
|
| Notes |
| 2011-06-20 15:31:39 | 2007 FBC W/2009 REVISIONS | | | | | | DENIED BY BUILDING | | | | | | 1) SPECIFY THE DESIGN CRITERIA ON THE PLANS PER FBC R | | | 301. THE WINDSPEED IS 140 MPH AND THE EXPOSURE CATEGORY | | | IS B. | | | | | | 2) PROVIDE THE ROOF SCUPPER AND SECONDARY SCUPPER | | | SIZING CALCULATIONS IN ACCORDANCE WITH FBC PLUMBING | | | 1106.7 AND 1107. INCLUDE HALF THE VERTICAL WALL AREA OF | | | THE PARAPET WALL WITH THE ROOF AREA PER FBC R 1106.4. | | | FBC R1107.3 STATES THAT SCUPPERS SHOULD NOT HAVE AN | | | OPENING DIMENSION OF LESS THAN 4 INCHES. | | | | | | 3) SHOW COMPLIANCE WITH FBC R 313.4 WHICH REQUIRES A | | | CARBON MONOXIDE DETECTOR WITHIN 10 FEET OF EACH ROOM | | | USED FOR SLEEPING PURPOSES. | | | | | | 4) SHOW COMPLIANCE WITH FBC R 320 FOR TERMITE | | | PROTECTION. | | | | | | 5) SHOW COMPLIANCE WITH FBC R320.7 FOR THE SCUPPERS TO | | | EMPTY INTO DOWNSPOUTS THAT DISCHARGE AT LEAST ONE FOOT | | | FROM THE STRUCTURE SIDE WALL. | | | | | | 6) SHOW COMPLIANCE WITH FBC R 703.6.3 WHICH REQUIRES A | | | BOND BREAK BETWEEN THE EXTERIOR STUCCO AND THE | | | WATER-RESISTIVE BARRIER. | | | | | | 7) SHOW COMPLIANCE WITH FBC R 803.2.3.1 WHICH REQUIRES | | | 8D RING SHANK NAILS FOR FASTENING THE ROOF SHEATHING. | | | (SHEET 2) | | | | | | 8) SHOW COMPLIANCE WITH FBC R 408.1 UNDER FLOOR SPACE | | | VENTILATION AND R408.4 ACCESS TO UNDER FLOOR SPACE. | | | | | | 9) SHOW COMPLIANCE WITH FBC R 806.1 FOR ATTIC | | | VENTILATION AND R 807.1 FOR ATTIC ACCESS. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2011-06-20 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2011-06-20 |
Time |
09:53 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2011-06-20 |
Time |
09:53 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
1 |
Status |
P |
Date |
2011-06-15 |
|
|
Cont ID |
|
| Sent By |
jpapa |
Date |
2011-06-15 |
Time |
14:51 |
Rev Time |
0.25 |
| Received By |
jpapa |
Date |
2011-06-15 |
Time |
14:51 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2011-07-07 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2011-07-07 |
Time |
07:57 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2011-06-30 |
Time |
16:09 |
Sent To |
|
|
| Notes |
| 2011-06-30 16:09:59 | INCOMING SENT TO R MC DOUGALS DESK. JW |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2011-06-20 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2011-06-20 |
Time |
16:17 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2011-06-16 |
Time |
08:22 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2011-07-07 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2011-07-07 |
Time |
07:12 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2011-07-07 |
Time |
07:12 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2011-06-20 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2011-06-20 |
Time |
07:46 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2011-06-20 |
Time |
06:54 |
Sent To |
|
|
| Notes |
| 2011-06-20 09:04:42 | 2007 FBC W/2009 REVISIONS | | | DENIED BY MECHANICAL | | | | | | 1) THE RETURN AIR TRANSFER DUCT FROM THE MASTER SUITE | | | IS REQUIRED TO BE ONE AND ONE HALF TIMES THE CROSS | | | SECTIONAL AREA OF THE SUPPLY DUCT ENTERING THE ROOM. | | | THE PLANS SPECIFY A 10" SUPPLY FOR THE MASTER SUITE | | | WHICH WILL REQUIRE 14" DIAMETER TRANSFER DUCT. | | | | | | 2) THE EQUIPMENT SIZING CALCULATIONS SPECIFIES A LATENT | | | COOLING EQUIPMENT TOTAL LOAD OF 29272 BTUH ( 2.5 TON) | | | AND A TOTAL CAPACITY OF 3.0 TON. THE EXISTING UNIT IS | | | 2.5 TON. PLEASE CORRECT THE FORM. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2011-06-17 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2011-06-17 |
Time |
13:25 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2011-06-17 |
Time |
13:25 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2011-07-08 |
|
|
Cont ID |
|
| Sent By |
jpapa |
Date |
2011-07-08 |
Time |
13:56 |
Rev Time |
0.00 |
| Received By |
jpapa |
Date |
2011-07-08 |
Time |
13:57 |
Sent To |
|
|
| Notes |
| 2011-07-08 14:10:11 | PROVISO: | | | | | | ZONING APPROVAL SHALL BE CONTINGENT UPON DEMOSTRATED | | | COMPLIANCE WITH SECTION 94-442 (B)(2)A OF THE ZONING | | | AND LAND DEVELOPMENT REGULATIONS THROUGH LANDSCAPING | | | PERMIT NO. 11060790. FOR MORE INFORMATION, PLEASE | | | CONTACT JILLIAN PAPA, HISTORIC PRESERVATION PLANNET AT | | | 561-822-1454. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2011-06-15 |
|
|
Cont ID |
|
| Sent By |
jpapa |
Date |
2011-06-15 |
Time |
14:51 |
Rev Time |
0.00 |
| Received By |
jpapa |
Date |
2011-06-15 |
Time |
15:03 |
Sent To |
|
|
| Notes |
| 2011-06-15 15:03:30 | FAILED. LANDSCAPE COMPLIANCE MUST BE DEMOSTRATED. | | | | | | THE VALUE OF THE CONSTRUCTION ($144,900) EXCEEDS 50% OF | | | THE STRUCTURE'S VALUE ($81,057) ACCORDING TO THE P.B.C. | | | PROPERTY APPRAISER'S OFFICE; THEREFORE, PURSUANT TO | | | SECTION 94-441(C)(2) OF THE ZONING AND LAND DEVELOPMENT | | | REGULATIONS (ZLDR), THE LANDSCAPE ON THE SITE SHALL BE | | | IN COMPLIANCE WITH ALL APPLICABLE REGULATIONS FOUND IN | | | ARTICLE XIV OF THE ZLDR. IF THE SITE CONFORMS TO | | | ARTICLE XIV, THEN TWO (2) COPIES OF A LANDSCAPE PLAN | | | DEMONSTRATING COMPLIANCE SHALL BE INCLUDED WITH THE | | | PERMIT RE-SUBMITTAL. IF THE SITE DOES NOT CONFORM TO | | | ARTICLE XIV, THEN PRIOR TO THE ZONING APPROVAL OF THIS | | | PERMIT A SEPARATE LANDSCAPE PERMIT AND IRRIGATION | | | PERMIT SHALL BE SUBMITTED SHOWING MATERIAL TO BRING THE | | | SITE INTO CONFORMITY. | | | | | | PLEASE CONTACT JILLIAN PAPA, HISTORIC PRESERVATION | | | PLANNER AT 561 822-1454 FOR MORE INFORMATION. |
|
|