Plan Review Details - Permit 11060346
Plan Review Stops For Permit 11060346
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2011-06-22 Cont ID  
Sent By jwitmer Date 2011-06-21 Time 15:51 Rev Time 1.20
Received By jwitmer Date 2011-06-21 Time 15:51 Sent To  
Notes
2011-06-21 15:57:00BUILDING PLAN REVIEW
 PERMIT: 11060346
 ADD:S OLIVE # 100
 CONT: OWNER/ BUILDER
 TEL: (561)889-6378
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: PASSED
  
  
 1) THE EDUCATIONAL OCCUPANCY DOES NOT REQUIRE WINDOWS
 FOR AN EMERGENCY EXITING WHEN THE ROOM HAS AN DOOR TO
 THE EXTERIOR, THE ROOM LABELEC VAULT, WHAT WILL THIS
 ROOM BE USED FOR? HOW WILL THE VAULT DOOR BE ENSURED
 THAT NO ONE WILL BE ABLE TO PULL IT SHUT AND LOCK IT?
  
  
 THE TENANT MS. MITCHELL DID CALL EXPLAING THE VAULT
 DOOR LOCK HAS BEEN DISABLED, AND THE USAGE OF THE VAULT
 AREA WILL BE STORAGE, NO KIDS ALLOWED IN VAULT.
 JAMES A. WITMER C.B.O.
 COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: (561)805-6715
 FAX:(561)805-6731
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2011-06-22 Cont ID  
Sent By rlecky Date 2011-06-22 Time 12:29 Rev Time 0.00
Received By rlecky Date 2011-06-22 Time 12:29 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2011-07-05 Cont ID  
Sent By wjolin Date 2011-07-05 Time 13:40 Rev Time 0.00
Received By wjolin Date 2011-07-05 Time 13:35 Sent To  
Notes
2011-07-05 13:40:36215 SOUTH OLIVE AVENUE, SUITE #100
 PERMIT #11060346
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 AS DISCUSSED WITH MS. MITCHELL ON JUNE 30, 2011, THE
 VAULT STORAGE ROOM SHALL NOT BE USED OR ACCESSIBLE
 UNTIL THIS ROOM IS PROTECTED BY THE AUTOMATIC SPRINKLER
 SYSTEM.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2011-06-24 Cont ID  
Sent By wjolin Date 2011-06-24 Time 12:47 Rev Time 0.00
Received By wjolin Date 2011-06-24 Time 12:24 Sent To  
Notes
2011-06-24 12:46:52215 SOUTH OLIVE AVENUE, SUITE #100
 PERMIT #11060346
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 DESIGN SHALL CONFORM TO THE FLORIDA FIRE PREVENTION
 CODE 2007 EDITION: NFPA 1 AND NFPA 101 - 2006 EDITION
 WITH FLORIDA AMENDMENTS.
  
 PROVIDE EMERGENCY LIGHTING AND EXIT SIGNS. NOTE: TWO
 PATHS OF EXIT ARE REQUIRED FOR EDUCATIONAL OCCUPANCIES.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND FIRE ALARM SYSTEM. NOTE: SPRINKLERS ARE
 NEEDED IN THE VAULT/STORAGE ROOM IF THEY DO NOT ALREADY
 EXIST.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-07-06 Cont ID  
Sent By shill Date 2011-07-06 Time 09:15 Rev Time 0.00
Received By shill Date 2011-06-30 Time 15:03 Sent To  
Notes
2011-06-30 15:04:27INCOMING SENT TO FIRE BOX. JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-07-05 Cont ID  
Sent By wjolin Date 2011-07-05 Time 13:45 Rev Time 0.00
Received By wjolin Date 2011-06-17 Time 09:48 Sent To  
Notes
2011-07-05 13:46:12INCOMING SENT TO B-14.
2011-06-17 09:49:30INCOMING SENT TO B-15 BOX. JW

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2011-07-07 Cont ID  
Sent By shill Date 2011-07-07 Time 14:42 Rev Time 0.00
Received By hmoser Date 2011-07-07 Time 07:11 Sent To  
Notes
2011-07-07 14:25:08****PROVISO****
  
 TCO ISSUED SUBJECT TO THE FOLLOWING:
  
 1. FBC EXISTING BUILDING 1103 AND APPENDIX B, PROPERTY
 OWNER IS TO APPLY FOR HISTORIC BUILDING DESIGNATION
 WITHIN 30 DAYS. EVIDENCE THAT HISTORIC BUILDING
 DESIGNATION HAS BEEN GRANTED IS TO BE SUBMITTED WITHIN
 90 DAYS.
  
 2. ALTERNATIVELY, OR IF HISTORIC BUILDING DESIGNATION
 HAS NOT BEEN GRANTED, PER FBC MECHANICAL 403 AND FBC
 EXISTING BUILDING 909, COMPLY WITH VENTILATION
 REQUIREMENTS WITHIN 90 DAYS.
  
 HAROLD MOSER, MECHANICAL PLANS EXAMINER
 561-805-6732
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2011-07-06 Cont ID  
Sent By shill Date 2011-07-06 Time 09:13 Rev Time 0.00
Received By hmoser Date 2011-07-06 Time 09:13 Sent To  
Notes
2011-07-06 09:15:21****CORRECTIONS****
  
 1. PROVIDE THE TOTAL SQUARE FOOT AREA OF PROPOSED
 EDUCATIONAL AREA.
  
 2. FBC EXISTING BUILDING 909, SHOW COMPLIANCE WITH FBC
 MECHANICAL 403 (VENTILATION/OUTSIDE AIR REQUIREMENTS).
  
 HAROLD MOSER, MECHANICAL PLANS EXAMINER
 561-805-6724
  
  

Review Stop Z ZONING
Rev No 1 Status P Date 2011-07-05 Cont ID  
Sent By aaponte Date 2011-07-05 Time 15:54 Rev Time 0.15
Received By aaponte Date 2011-07-05 Time 15:54 Sent To  
Notes
2011-07-05 15:59:03CHANGE OF OCCUPANCY ONLY. NO INTERIOR OR EXTERIOR
 CHANGES. EDUCATIONAL USE PERMITTED ON SITE. NO HEAVY
 EQUIPMENT.