Plan Review Details - Permit 11060345
Plan Review Stops For Permit 11060345
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2011-07-18 Cont ID  
Sent By jgomez Date 2011-07-18 Time 10:28 Rev Time 0.00
Received By jgomez Date 2011-07-18 Time 10:17 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-07-12 Cont ID  
Sent By jgomez Date 2011-07-12 Time 10:30 Rev Time 0.00
Received By jgomez Date 2011-07-12 Time 08:42 Sent To  
Notes
2011-07-12 10:35:48RESIDENTIAL (R3) ALTERATION BUILDING REVIEW CHECKLIST.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- ENGINEER'S DRAWINGS IS MISSING DETAIL 1 FOR THE BEAM
 CONNECTION AT THE EXISTING MASONRY WALL END. PROVIDE
 CONNECTION DETAIL. SEC. 106.1.2 CITY AMENDMENTS TO FBC.
  
 2- COPIES OF THE DRAWINGS FOR THE ALUMINUM MULLIONS AND
 SINGLE HUNG WINDOWS ON THE NOA'S SUBMITTED ARE CUT IN
 HALF. PROVIDE COMPLETE DRAWINGS.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2011-07-07 Cont ID  
Sent By rlecky Date 2011-07-07 Time 14:27 Rev Time 0.00
Received By rlecky Date 2011-07-07 Time 14:07 Sent To  
Notes
2011-07-07 14:27:50PROVISO:
 REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE DETECTORS. IF THE
 RESIDENCE HAS GAS APPLIANCES, AN ATTACHED GARAGE OR A
 FIRE PLACE A CARBON MONOXIDE DETECTOR IS REQUIRED
 WITHIN TEN FEET OF EACH ROOM USED FOR SLEEPING. FBC
 R313
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 561-805-6718
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-07-18 Cont ID  
Sent By jgomez Date 2011-07-18 Time 10:17 Rev Time 0.00
Received By jgomez Date 2011-07-18 Time 10:17 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-07-12 Cont ID  
Sent By jgomez Date 2011-07-12 Time 10:35 Rev Time 0.00
Received By jgomez Date 2011-06-16 Time 07:56 Sent To  
Notes
2011-07-06 15:45:58R7
2011-06-16 07:57:16SENT TO ZONING BOX

Review Stop Z ZONING
Rev No 1 Status P Date 2011-06-25 Cont ID  
Sent By astelly Date 2011-06-25 Time 09:25 Rev Time 0.00
Received By astelly Date 2011-06-25 Time 09:25 Sent To  
Notes
***NONE***