Plan Review Details - Permit 11060317
Plan Review Stops For Permit 11060317
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-02-13 Cont ID  
Sent By jwitmer Date 2012-02-13 Time 15:55 Rev Time 0.00
Received By jwitmer Date 2012-02-13 Time 15:55 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-07-12 Cont ID  
Sent By jwitmer Date 2011-07-12 Time 08:42 Rev Time 0.77
Received By jwitmer Date 2011-07-08 Time 08:42 Sent To  
Notes
2011-07-12 08:53:03SHEET E-5 PLEASE REVIEW FREIGHT ELEVATOR EAST TOWER TOP
 OF POINT CLUB LEVEL, MISSING AUTOMATIC FIRE ALARM
 INITIATING DEVICES SHALL BE LOCATED AND INSTALLED IN
 ACCORDANCE WITH ASME A17.1 & NFPA 72.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2012-02-08 Cont ID  
Sent By rlecky Date 2012-02-08 Time 09:21 Rev Time 0.00
Received By rlecky Date 2012-02-08 Time 08:12 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2011-07-11 Cont ID  
Sent By rlecky Date 2011-07-11 Time 14:09 Rev Time 0.00
Received By rlecky Date 2011-07-11 Time 08:57 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2012-02-09 Cont ID  
Sent By wjolin Date 2012-02-09 Time 14:58 Rev Time 0.00
Received By wjolin Date 2012-02-08 Time 15:55 Sent To  
Notes
2012-02-09 14:58:27777 SOUTH FLAGLER DRIVE
 PERMIT #11060317
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SHEET M2.1 - ONLY PENETRATIONS, DUCTS, ETC. SERVING AS
 AN ESSENTIAL FUNCTION OF THE STAIR ARE PERMITTED IN THE
 FIRE-RATED STAIR ENCLOSURE.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2011-07-07 Cont ID  
Sent By wjolin Date 2011-07-07 Time 13:46 Rev Time 0.00
Received By wjolin Date 2011-07-07 Time 11:16 Sent To  
Notes
2011-07-07 13:46:04777 SOUTH FLAGLER DRIVE
 PERMIT #11060317
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SHEET E-5
 1) A NEW SMOKE DETECTOR IS PROVIDED IN THE ELEVATOR
 LOBBY (SERVICE ELEVATOR) OF THE WEST TOWER; HOWEVER, NO
 SMOKE DETECTOR WAS PROVIDED IN THE ELEVATOR LOBBY OF
 THE EAST TOWER.
  
 2) CLARIFY THE INTENT OF THE MAGNETIC DOOR HOLDERS TO
 BE RELEASED VIA "OVERHEAD DOOR CLOSURE."
  
 3) CLARIFY THE MEANING OF "CLASS A" FIRE ALARM.
  
 SHEET E-6
 1) SECTION CALLED "NOTES" STATES IN THE EVENT OF A FIRE
 ALARM, "THE PASSENGER ELEVATORS WILL RECALL AND
 SHUTDOWN." ELEVATORS SHOULD ONLY BE AUTOMATICALLY
 RECALLED IF A SMOKE DETECTOR HAS OPERATED IN THE
 ELEVATOR LOBBY, ELEVATOR MACHINE ROOM, OR ELEVATOR
 SHAFT. ELEVATOR POWER SHOULD ONLY BE SHUNTED BY A HEAT
 DETECTOR LOCATED IN THE ELEVATOR SHAFT, OR A HEAT
 DETECTOR/FLOW SWITCH LOCATED IN THE ELEVATOR MACHINE
 ROOM.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2012-02-15 Time   Rev Time 0.00
Received By rregueir Date 2012-02-06 Time 14:02 Sent To  
Notes
2012-02-07 14:03:24**DIGITAL PLANS** SEE PROJECTDOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2011-10-11 Time   Rev Time 0.00
Received By rregueir Date 2011-07-06 Time 15:36 Sent To  
Notes
2011-07-06 15:36:50****PROJECTDOX***** IMPORTANT NOTE: REVIEWS FOR THIS
 PERMIT AND 11060318 ARE BEING PERFORMED IN PROJECTDOX
 UNDER PERMIT #11060317. PLEASE ENTER PLAN REVIEW
 COMMENTS, RESULTS AND FRONT SCREEN NOTES ON BOTH
 PERMITS. RJR

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2012-02-15 Cont ID  
Sent By rregueir Date 2012-02-15 Time 15:05 Rev Time 0.00
Received By rregueir Date 2012-02-15 Time 15:05 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2011-10-11 Cont ID  
Sent By rregueir Date 2011-10-11 Time 14:05 Rev Time 0.00
Received By rregueir Date 2011-10-11 Time 14:05 Sent To  
Notes
2011-10-11 15:23:22REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. ELEVATOR VENTILATION DUCTS SHALL BE ENCLOSED BY
 CONSTRUCTION HAVING NOT LESS THAN THE FIRE PROTECTION
 RATING REQUIRED FOR THE HOISTWAY (2 HOURS, IN THIS
 CASE) PER FBC-B 3004.2.
  
 2. NO DETAIL PROVIDED FOR ATTACHMENT OF NEW CONDENSING
 UNITS TO EXISTING ROOF CURB ON PAGE M5.1. SHOW HOW
 ATTACHMENT FOR WIND RESISTANCE IS TO BE ACHIEVED PER
 FBC-M 301.12.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2012-04-24 Cont ID  
Sent By rregueir Date 2012-02-15 Time 16:09 Rev Time 0.00
Received By rregueir Date 2012-02-15 Time 16:09 Sent To  
Notes
2012-04-24 16:11:04ONE SET OF SIGNED AND SEALED PLANS WITH CITY STAMPS
 ALREADY APPLIED.