| 2011-06-23 09:51:03 | BUILDING PLAN REVIEW |
| | PERMIT: 11060245 |
| | ADD: 2101 45TH ST |
| | CONT: HODGEN CONSTRUCTION & DEVELOPMENT |
| | TEL: (954) 895-1893 |
| | |
| | 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 2007 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | 1) SHEET A100 THE BUILDING DESIGN CRITERIA IS BLANK. |
| | PLEASE PROVIDE THE MINIMUM BUILDING TYPE THIS BUILDING |
| | CAN BE DESIGNED TO SINCE IT MAY EFFECT THE DESIGN |
| | COMPONENTS AND OR MATERIALS TO BE INSTALLED WITHIN OR |
| | ATTACHED TO THE STRUCTURE, TABLE 503 & CHAPTER 6. |
| | |
| | 2) SHEET A302 & A700 BOTH INDICATE THE USE OF NEW |
| | EXTERIOR AUTOMATIC DOORS AS WELL AS STOREFRONT SYSTEMS. |
| | FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING, PROVIDE 2 |
| | COPIES OF PRODUCT TESTING REPORTS, MISSING REPORTS ARE |
| | AS FOLLOWS: |
| | |
| | 2A) AUTOMATIC SLIDING DOORS |
| | |
| | 2B) STOREFRONT SYSTEMS |
| | |
| | 2C) MULLIONS- IF NOT PART OF THE PRODUCT APPROVAL |
| | PACKAGE |
| | |
| | 2D) STORM SHUTTERS IF THE GLAZED AREAS BEING REPLACED |
| | DO NOT HAVE LARGE MISSILE IMPACT RESISTANCE TESTING |
| | |
| | 2E) MCM PANELS |
| | |
| | 3) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE |
| | REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| | SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 4) AUTOMATIC HORIZONTAL SLIDING DOORS SHALL ALSO COMPLY |
| | WITH 1008.1.3.3 PLEASE PROVIDE PRODUCT SPECIFICATIONS. |
| | 1008.1.3.3 HORIZONTAL SLIDING DOORS. IN OTHER THAN |
| | GROUP H OCCUPANCIES, HORIZONTAL SLIDING DOORS PERMITTED |
| | TO BE A COMPONENT OF A MEANS OF EGRESS IN ACCORDANCE |
| | WITH EXCEPTION 6 TO SECTION 1008.1.2 SHALL COMPLY WITH |
| | ALL OF THE FOLLOWING CRITERIA: |
| | |
| | 1. THE DOORS SHALL BE POWER OPERATED AND SHALL BE |
| | CAPABLE OF BEING OPERATED MANUALLY IN THE EVENT OF |
| | POWER FAILURE. |
| | |
| | 2. THE DOORS SHALL BE OPENABLE BY A SIMPLE METHOD FROM |
| | BOTH SIDES WITHOUT SPECIAL KNOWLEDGE OR EFFORT. |
| | |
| | 3. THE FORCE REQUIRED TO OPERATE THE DOOR SHALL NOT |
| | EXCEED 30 POUNDS (133 N) TO SET THE DOOR IN MOTION AND |
| | 15 POUNDS (67 N) TO CLOSE THE DOOR OR OPEN IT TO THE |
| | MINIMUM REQUIRED WIDTH. |
| | |
| | 4. THE DOOR SHALL BE OPENABLE WITH A FORCE NOT TO |
| | EXCEED 15 POUNDS (67 N) WHEN A FORCE OF 250 POUNDS |
| | (1100 N) IS APPLIED PERPENDICULAR TO THE DOOR ADJACENT |
| | TO THE OPERATING DEVICE. |
| | |
| | 5. THE DOOR ASSEMBLY SHALL COMPLY WITH THE APPLICABLE |
| | FIRE PROTECTION RATING AND, WHERE RATED, SHALL BE |
| | SELF-CLOSING OR AUTOMATIC-CLOSING BY SMOKE DETECTION, |
| | SHALL BE INSTALLED IN ACCORDANCE WITH NFPA 80 AND SHALL |
| | COMPLY WITH SECTION 715. |
| | |
| | 6. THE DOOR ASSEMBLY SHALL HAVE AN INTEGRATED STANDBY |
| | POWER SUPPLY. |
| | |
| | 7. THE DOOR ASSEMBLY POWER SUPPLY SHALL BE ELECTRICALLY |
| | SUPERVISED. |
| | |
| | 8. THE DOOR SHALL OPEN TO THE MINIMUM REQUIRED WIDTH |
| | WITHIN 10 SECONDS AFTER ACTIVATION OF THE OPERATING |
| | DEVICE. |
| | |
| | 9. IN APARTMENT BUILDINGS, HOTELS AND DORMITORIES, |
| | HORIZONTAL SLIDING DOORS SHALL NOT BE USED ACROSS |
| | CORRIDORS |
| | |
| | |
| | 5). PLEASE PROVIDE DOCUMENTATION FOR MCM PANELS FOR THE |
| | FOLLOWING:1407.2 EXTERIOR WALL FINISH. MCM USED AS |
| | EXTERIOR WALL FINISH OR AS ELEMENTS OF BALCONIES AND |
| | SIMILAR PROJECTIONS AND BAY AND ORIEL WINDOWS TO |
| | PROVIDE CLADDING OR WEATHER RESISTANCE SHALL COMPLY |
| | WITH SECTIONS 1407.4 THROUGH 1407.13. |
| | |
| | 5A)1407.4 STRUCTURAL DESIGN. MCM SYSTEMS SHALL BE |
| | DESIGNED AND CONSTRUCTED TO RESIST WIND LOADS AS |
| | REQUIRED BY CHAPTER 16 FOR COMPONENTS AND CLADDING. |
| | |
| | 5B) 1407.5 APPROVAL. RESULTS OF APPROVED TESTS OR AN |
| | ENGINEERING ANALYSIS SHALL BE SUBMITTED TO THE BUILDING |
| | OFFICIAL TO VERIFY COMPLIANCE WITH THE REQUIREMENTS OF |
| | CHAPTER 16 FOR WIND LOADS. |
| | |
| | 5C) 1407.6 WEATHER RESISTANCE. MCM SYSTEMS SHALL COMPLY |
| | WITH SECTION 1403 AND SHALL BE DESIGNED AND CONSTRUCTED |
| | TO RESIST WIND AND RAIN IN ACCORDANCE WITH THIS SECTION |
| | AND THE MANUFACTURER'S INSTALLATION INSTRUCTIONS. |
| | |
| | 5D) 1407.7 DURABILITY. MCM SYSTEMS SHALL BE CONSTRUCTED |
| | OF APPROVED MATERIALS THAT MAINTAIN THE PERFORMANCE |
| | CHARACTERISTICS REQUIRED IN SECTION 1407 FOR THE |
| | DURATION OF USE. |
| | |
| | 5E) 1407.8 FIRE-RESISTANCE RATING. WHERE MCM SYSTEMS |
| | ARE USED ON EXTERIOR WALLS REQUIRED TO HAVE A |
| | FIRE-RESISTANCE RATING IN ACCORDANCE WITH SECTION 704, |
| | EVIDENCE SHALL BE SUBMITTED TO THE BUILDING OFFICIAL |
| | THAT THE REQUIRED FIRE-RESISTANCE RATING IS MAINTAINED. |
| | |
| | 5F) 1407.9 SURFACE-BURNING CHARACTERISTICS. UNLESS |
| | OTHERWISE SPECIFIED, MCM SHALL HAVE A FLAME SPREAD |
| | INDEX OF 75 OR LESS AND A SMOKE-DEVELOPED INDEX OF 450 |
| | OR LESS WHEN TESTED AS AN ASSEMBLY IN THE MAXIMUM |
| | THICKNESS INTENDED FOR USE IN ACCORDANCE WITH ASTM E |
| | 84. |
| | |
| | 5F) 1407.10 TYPE I, II, III AND IV CONSTRUCTION. WHERE |
| | INSTALLED ON BUILDINGS OF TYPE I, II, III AND IV |
| | CONSTRUCTION, MCM SYSTEMS SHALL COMPLY WITH SECTIONS |
| | 1407.10.1 THROUGH 1407.10.4, OR 1407.11. |
| | |
| | 5G) 1407.12 TYPE V CONSTRUCTION. MCM SHALL BE PERMITTED |
| | TO BE INSTALLED ON BUILDINGS OF TYPE V CONSTRUCTION. |
| | |
| | 5H) 1407.13 LABELING. MCM SHALL BE LABELED IN |
| | ACCORDANCE WITH SECTION 1703.5. |
| | |
| | INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER C.B.O. |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: (561)805-6715 |
| | FAX:(561)805-6731 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |