Plan Review Details - Permit 11060245
Plan Review Stops For Permit 11060245
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2011-07-29 Cont ID  
Sent By jwitmer Date 2011-07-29 Time 15:02 Rev Time 0.77
Received By jwitmer Date 2011-07-29 Time 14:26 Sent To  
Notes
2011-07-29 15:14:39BUILDING PLAN REVIEW
 PERMIT: 11060245
 ADD: 2101 45TH ST
 CONT: HODGEN CONSTRUCTION & DEVELOPMENT
 TEL: (954) 895-1893
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING, PROVIDE 2
 COPIES OF PRODUCT TESTING REPORTS, MISSING REPORTS ARE
 AS FOLLOWS:
 AUTOMATIC SLIDING DOORS
  
  
  
 JAMES A. WITMER C.B.O.
 COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: (561)805-6715
 FAX:(561)805-6731
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-06-23 Cont ID  
Sent By jwitmer Date 2011-06-23 Time 09:52 Rev Time 0.90
Received By jwitmer Date 2011-06-23 Time 09:00 Sent To  
Notes
2011-06-23 09:51:03BUILDING PLAN REVIEW
 PERMIT: 11060245
 ADD: 2101 45TH ST
 CONT: HODGEN CONSTRUCTION & DEVELOPMENT
 TEL: (954) 895-1893
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
 1) SHEET A100 THE BUILDING DESIGN CRITERIA IS BLANK.
 PLEASE PROVIDE THE MINIMUM BUILDING TYPE THIS BUILDING
 CAN BE DESIGNED TO SINCE IT MAY EFFECT THE DESIGN
 COMPONENTS AND OR MATERIALS TO BE INSTALLED WITHIN OR
 ATTACHED TO THE STRUCTURE, TABLE 503 & CHAPTER 6.
  
 2) SHEET A302 & A700 BOTH INDICATE THE USE OF NEW
 EXTERIOR AUTOMATIC DOORS AS WELL AS STOREFRONT SYSTEMS.
 FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING, PROVIDE 2
 COPIES OF PRODUCT TESTING REPORTS, MISSING REPORTS ARE
 AS FOLLOWS:
  
 2A) AUTOMATIC SLIDING DOORS
  
 2B) STOREFRONT SYSTEMS
  
 2C) MULLIONS- IF NOT PART OF THE PRODUCT APPROVAL
 PACKAGE
  
 2D) STORM SHUTTERS IF THE GLAZED AREAS BEING REPLACED
 DO NOT HAVE LARGE MISSILE IMPACT RESISTANCE TESTING
  
 2E) MCM PANELS
  
 3) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 4) AUTOMATIC HORIZONTAL SLIDING DOORS SHALL ALSO COMPLY
 WITH 1008.1.3.3 PLEASE PROVIDE PRODUCT SPECIFICATIONS.
 1008.1.3.3 HORIZONTAL SLIDING DOORS. IN OTHER THAN
 GROUP H OCCUPANCIES, HORIZONTAL SLIDING DOORS PERMITTED
 TO BE A COMPONENT OF A MEANS OF EGRESS IN ACCORDANCE
 WITH EXCEPTION 6 TO SECTION 1008.1.2 SHALL COMPLY WITH
 ALL OF THE FOLLOWING CRITERIA:
  
 1. THE DOORS SHALL BE POWER OPERATED AND SHALL BE
 CAPABLE OF BEING OPERATED MANUALLY IN THE EVENT OF
 POWER FAILURE.
  
 2. THE DOORS SHALL BE OPENABLE BY A SIMPLE METHOD FROM
 BOTH SIDES WITHOUT SPECIAL KNOWLEDGE OR EFFORT.
  
 3. THE FORCE REQUIRED TO OPERATE THE DOOR SHALL NOT
 EXCEED 30 POUNDS (133 N) TO SET THE DOOR IN MOTION AND
 15 POUNDS (67 N) TO CLOSE THE DOOR OR OPEN IT TO THE
 MINIMUM REQUIRED WIDTH.
  
 4. THE DOOR SHALL BE OPENABLE WITH A FORCE NOT TO
 EXCEED 15 POUNDS (67 N) WHEN A FORCE OF 250 POUNDS
 (1100 N) IS APPLIED PERPENDICULAR TO THE DOOR ADJACENT
 TO THE OPERATING DEVICE.
  
 5. THE DOOR ASSEMBLY SHALL COMPLY WITH THE APPLICABLE
 FIRE PROTECTION RATING AND, WHERE RATED, SHALL BE
 SELF-CLOSING OR AUTOMATIC-CLOSING BY SMOKE DETECTION,
 SHALL BE INSTALLED IN ACCORDANCE WITH NFPA 80 AND SHALL
 COMPLY WITH SECTION 715.
  
 6. THE DOOR ASSEMBLY SHALL HAVE AN INTEGRATED STANDBY
 POWER SUPPLY.
  
 7. THE DOOR ASSEMBLY POWER SUPPLY SHALL BE ELECTRICALLY
 SUPERVISED.
  
 8. THE DOOR SHALL OPEN TO THE MINIMUM REQUIRED WIDTH
 WITHIN 10 SECONDS AFTER ACTIVATION OF THE OPERATING
 DEVICE.
  
 9. IN APARTMENT BUILDINGS, HOTELS AND DORMITORIES,
 HORIZONTAL SLIDING DOORS SHALL NOT BE USED ACROSS
 CORRIDORS
  
  
 5). PLEASE PROVIDE DOCUMENTATION FOR MCM PANELS FOR THE
 FOLLOWING:1407.2 EXTERIOR WALL FINISH. MCM USED AS
 EXTERIOR WALL FINISH OR AS ELEMENTS OF BALCONIES AND
 SIMILAR PROJECTIONS AND BAY AND ORIEL WINDOWS TO
 PROVIDE CLADDING OR WEATHER RESISTANCE SHALL COMPLY
 WITH SECTIONS 1407.4 THROUGH 1407.13.
  
 5A)1407.4 STRUCTURAL DESIGN. MCM SYSTEMS SHALL BE
 DESIGNED AND CONSTRUCTED TO RESIST WIND LOADS AS
 REQUIRED BY CHAPTER 16 FOR COMPONENTS AND CLADDING.
  
 5B) 1407.5 APPROVAL. RESULTS OF APPROVED TESTS OR AN
 ENGINEERING ANALYSIS SHALL BE SUBMITTED TO THE BUILDING
 OFFICIAL TO VERIFY COMPLIANCE WITH THE REQUIREMENTS OF
 CHAPTER 16 FOR WIND LOADS.
  
 5C) 1407.6 WEATHER RESISTANCE. MCM SYSTEMS SHALL COMPLY
 WITH SECTION 1403 AND SHALL BE DESIGNED AND CONSTRUCTED
 TO RESIST WIND AND RAIN IN ACCORDANCE WITH THIS SECTION
 AND THE MANUFACTURER'S INSTALLATION INSTRUCTIONS.
  
 5D) 1407.7 DURABILITY. MCM SYSTEMS SHALL BE CONSTRUCTED
 OF APPROVED MATERIALS THAT MAINTAIN THE PERFORMANCE
 CHARACTERISTICS REQUIRED IN SECTION 1407 FOR THE
 DURATION OF USE.
  
 5E) 1407.8 FIRE-RESISTANCE RATING. WHERE MCM SYSTEMS
 ARE USED ON EXTERIOR WALLS REQUIRED TO HAVE A
 FIRE-RESISTANCE RATING IN ACCORDANCE WITH SECTION 704,
 EVIDENCE SHALL BE SUBMITTED TO THE BUILDING OFFICIAL
 THAT THE REQUIRED FIRE-RESISTANCE RATING IS MAINTAINED.
  
 5F) 1407.9 SURFACE-BURNING CHARACTERISTICS. UNLESS
 OTHERWISE SPECIFIED, MCM SHALL HAVE A FLAME SPREAD
 INDEX OF 75 OR LESS AND A SMOKE-DEVELOPED INDEX OF 450
 OR LESS WHEN TESTED AS AN ASSEMBLY IN THE MAXIMUM
 THICKNESS INTENDED FOR USE IN ACCORDANCE WITH ASTM E
 84.
  
 5F) 1407.10 TYPE I, II, III AND IV CONSTRUCTION. WHERE
 INSTALLED ON BUILDINGS OF TYPE I, II, III AND IV
 CONSTRUCTION, MCM SYSTEMS SHALL COMPLY WITH SECTIONS
 1407.10.1 THROUGH 1407.10.4, OR 1407.11.
  
 5G) 1407.12 TYPE V CONSTRUCTION. MCM SHALL BE PERMITTED
 TO BE INSTALLED ON BUILDINGS OF TYPE V CONSTRUCTION.
  
 5H) 1407.13 LABELING. MCM SHALL BE LABELED IN
 ACCORDANCE WITH SECTION 1703.5.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER C.B.O.
 COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: (561)805-6715
 FAX:(561)805-6731
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2011-06-22 Cont ID  
Sent By rlecky Date 2011-06-22 Time 15:02 Rev Time 0.00
Received By rlecky Date 2011-06-22 Time 14:35 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2011-06-27 Cont ID  
Sent By wjolin Date 2011-06-27 Time 10:37 Rev Time 0.00
Received By wjolin Date 2011-06-27 Time 10:00 Sent To  
Notes
2011-06-27 10:37:262101 45TH STREET
 PERMIT #11060245
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 ALL DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS
 OF NFPA 241.
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE APPROVED AND SUBMITTED IN WRITING TO THE OFFICE OF
 THE FIRE MARSHAL.
  
 PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY
 RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING
 NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM
 WWW.KNOXBOX.COM.
  
 SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND FIRE ALARM SYSTEM.
  
 POWERED DOORS: SEE BUILDING REVIEW COMMENTS.
  
 DRAWINGS WILL BE STAMPED, INITIALED, AND DATED BY THE
 FIRE DEPARTMENT AFTER ALL PLAN REVIEWER COMMENTS HAVE
 BEEN SATISFIED.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-08-19 Cont ID  
Sent By shill Date 2011-08-19 Time 15:49 Rev Time 0.00
Received By shill Date 2011-07-28 Time 09:52 Sent To  
Notes
2011-08-19 15:50:11ON SH DESK FOR PROCESSING
  
2011-07-28 09:52:52SENT TO C2 SHELF FOR BUILDING AND ZONING REVIEW.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-06-29 Cont ID  
Sent By hmoser Date 2011-06-29 Time 13:51 Rev Time 0.00
Received By hmoser Date 2011-06-10 Time 17:17 Sent To  
Notes
2011-06-10 17:18:44********************EXPEDITED**********************
 C--3
  

Review Stop L LANDSCAPING
Rev No 1 Status N Date 2011-06-15 Cont ID  
Sent By rkussner Date 2011-06-15 Time 16:13 Rev Time 0.00
Received By rkussner Date 2011-06-15 Time 16:13 Sent To  
Notes
2011-06-15 16:14:05***LANDSCAPE REVIEW NOT REQUIRED***
 THE COST OF THE ALTERATIONS DOES NOT EXCEED 50% OF THE
 IMPROVEMENT VALUE.--RAK

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2011-06-29 Cont ID  
Sent By hmoser Date 2011-06-29 Time 13:51 Rev Time 0.00
Received By hmoser Date 2011-06-29 Time 13:09 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2011-06-22 Cont ID  
Sent By lwagner Date 2011-06-22 Time 09:26 Rev Time 0.00
Received By lwagner Date 2011-06-22 Time 07:03 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2011-08-17 Cont ID  
Sent By lfranco Date 2011-08-17 Time 18:03 Rev Time 0.50
Received By lfranco Date 2011-08-17 Time 18:02 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2011-06-21 Cont ID  
Sent By lfranco Date 2011-06-21 Time 11:38 Rev Time 1.00
Received By lfranco Date 2011-06-21 Time 10:17 Sent To  
Notes
2011-06-21 11:30:49PLANNING AND ZONING: *** FAILED ***
  
 1. RESPOND TO COMMENTS IN WRITING.
  
 2. SHEET A100 SHOWS NEW DISPLAY AREA/STORAGE AREA FOR
 VEHICLES. PROVIDE INFORMATION ON SITE DATA REGARDING
 HOW MANY SPACES WILL BE USED FOR VEHICLE DISPLAY. THE
 PARKING REQUIREMENTS ARE AS FOLLOWS:
  
 THREE (3) PARKING SPACES REQUIRED PER SERVICE BAY;
 ONE (1) PARKING SPACE PER 500 SQUARE FEET OF ENCLOSED
 AREA (PROVIDE ALL BUILDINGS SQUARE FOOTAGE);
 ONE (1) PARKING SPACE PER 1,500 SQUARE FEET OF OUTDOOR
 STORAGE (THIS INCLUDES INVENTORY PARKING AND DISPLAY
 AREA)
  
 PROVIDE PARKING REQUIREMENTS ABOVE AND SHOW TOTAL
 PARKING REQUIRED AND PROVIDED ON SITE DATA.
  
 3. ANY NEW SIGNAGE ON BUILDING OR FREE STANDING
 REQUIRES A SEPARATE SIGNAGE BUILDING PERMIT. SHOW
 EXISTING SIGNAGE WITH SQUARE FOOTAGE AND PROPOSED,
 INCLUDING FACADE DIMENSIONS FOR EACH SIDE OF THE
 BUILDING(S).
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME.
  