Plan Review Details - Permit 11060236
Plan Review Stops For Permit 11060236
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2011-06-28 Cont ID  
Sent By shill Date 2011-06-28 Time 15:39 Rev Time 0.00
Received By shill Date 2011-06-28 Time 15:39 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2011-06-27 Cont ID  
Sent By shill Date 2011-06-27 Time 14:49 Rev Time 0.00
Received By shill Date 2011-06-27 Time 14:49 Sent To  
Notes
2011-06-27 14:50:33****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. SCOPE NOT CLEAR. A BAHAMA SHUTTER IS SHOWN OVER THE
 DOOR. BASED ON TRAVEL DISTANCE AND DEAD END CREATED,
 THE EXIT DOOR CANNOT BE COVERED WITH A BAHAMA SHUTTER
 AS DEPICTED.
  
 FBC 1003.6, MEANS OF EGRESS CONTINUITY. THE PATH OF
 EGRESS TRAVEL ALONG A MEANS OF EGRESS SHALL NOT BE
 INTERRUPTED BY ANY BUILDING ELEMENT OTHER THAN A MEANS
 OF EGRESS COMPONENT AS SPECIFIED IN THIS CHAPTER.
 OBSTRUCTIONS SHALL NOT BE PLACED IN THE REQUIRED WIDTH
 OF A MEANS OF EGRESS EXCEPT PROJECTIONS PERMITTED BY
 THIS CHAPTER.
  
 1008.1.3.5 SECURITY GRILLS. IN GROUPS B, F, M, R AND S,
 HORIZONTAL SLIDING OR VERTICAL SECURITY GRILLES ARE
 PERMITTED AT THE MAIN EXIT AND SHALL BE OPENABLE FROM
 THE INSIDE WITHOUT THE USE OF A KEY OR SPECIAL
 KNOWLEDGE OR EFFORT DURING PERIODS THAT THE SPACE IS
 OCCUPIED. THE GRILLES SHALL REMAIN SECURED IN THE
 FULL-OPEN POSITION DURING THE PERIOD OF OCCUPANCY BY
 THE GENERAL PUBLIC. WHERE TWO OR MORE MEANS OF EGRESS
 ARE REQUIRED, NOT MORE THAN ONE-HALF OF THE EXITS OR
 EXIT ACCESS DOORWAYS SHALL BE EQUIPPED WITH HORIZONTAL
 SLIDING OR VERTICAL SECURITY GRILLES.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-06-10 Cont ID  
Sent By shill Date 2011-06-10 Time 11:43 Rev Time 0.00
Received By shill Date 2011-06-10 Time 11:43 Sent To Z
Notes
2011-06-10 11:50:33****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. COMPLETE THE SAMPLE INSTALLATION SCHEDULE OR PROVIDE
 ALL INFORMATION TO SHOW CODE COMPLIANCE IN ANOTHER
 FORMAT, FBC*106, FBC R301, FBC1609. TWO SETS REQUIRED.
 THIS FORM IS AVAILABLE IN THE LOBBY OR ON THE INTERNET
 AT
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/PDF/SCHEDULE_FOR_
 INSTALLATION.PDF
  
 2. SEE FBC1003.6, 1008.1. PROVIDE MORE INFORMATION
 REGARDING THIS COMMERCIAL BUILDING.
  
 PLEASE DESIGNATE WHICH OPENINGS ARE DOORS (EXITS).
 PROVIDE INFORMATION REGARDING THE OCCUPANCY
 CLASSIFICATION (USE) OF THE BUILDING, FBC CHAPTER 3.
 MORE INFORMATION MAY BE REQUIRED.
  
 FBC 1003.6, MEANS OF EGRESS CONTINUITY. THE PATH OF
 EGRESS TRAVEL ALONG A MEANS OF EGRESS SHALL NOT BE
 INTERRUPTED BY ANY BUILDING ELEMENT OTHER THAN A MEANS
 OF EGRESS COMPONENT AS SPECIFIED IN THIS CHAPTER.
 OBSTRUCTIONS SHALL NOT BE PLACED IN THE REQUIRED WIDTH
 OF A MEANS OF EGRESS EXCEPT PROJECTIONS PERMITTED BY
 THIS CHAPTER.
  
 1008.1.3.5 SECURITY GRILLS. IN GROUPS B, F, M, R AND S,
 HORIZONTAL SLIDING OR VERTICAL SECURITY GRILLES ARE
 PERMITTED AT THE MAIN EXIT AND SHALL BE OPENABLE FROM
 THE INSIDE WITHOUT THE USE OF A KEY OR SPECIAL
 KNOWLEDGE OR EFFORT DURING PERIODS THAT THE SPACE IS
 OCCUPIED. THE GRILLES SHALL REMAIN SECURED IN THE
 FULL-OPEN POSITION DURING THE PERIOD OF OCCUPANCY BY
 THE GENERAL PUBLIC. WHERE TWO OR MORE MEANS OF EGRESS
 ARE REQUIRED, NOT MORE THAN ONE-HALF OF THE EXITS OR
 EXIT ACCESS DOORWAYS SHALL BE EQUIPPED WITH HORIZONTAL
 SLIDING OR VERTICAL SECURITY GRILLES.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2011-08-09 Cont ID  
Sent By rlecky Date 2011-08-09 Time 10:59 Rev Time 0.00
Received By rlecky Date 2011-08-09 Time 10:54 Sent To  
Notes
2011-08-09 10:54:41TO SH

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-06-27 Cont ID  
Sent By shill Date 2011-06-27 Time 14:50 Rev Time 0.00
Received By shill Date 2011-06-24 Time 15:46 Sent To  
Notes
2011-06-24 15:47:35GAVE TO SAMANTHA

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-06-10 Cont ID  
Sent By shill Date 2011-06-10 Time 11:50 Rev Time 0.00
Received By shill Date 2011-06-09 Time 16:22 Sent To  
Notes
2011-06-09 16:22:53INCOMING SENT TO MISC BOX# 1. JW

Review Stop Z ZONING
Rev No 1 Status P Date 2011-06-16 Cont ID  
Sent By eschneid Date 2011-06-16 Time 10:25 Rev Time 0.75
Received By eschneid Date 2011-06-14 Time 15:45 Sent To  
Notes
***NONE***