Plan Review Details - Permit 11060158
Plan Review Stops For Permit 11060158
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2011-06-08 Cont ID  
Sent By jgomez Date 2011-06-08 Time 15:08 Rev Time 0.00
Received By jgomez Date 2011-06-08 Time 15:07 Sent To PC
Notes
2011-06-08 15:33:18RESIDENTIAL (R3) STAIR REVISION, BUILDING REVIEW
 CHECKLIST.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- PER CONVERSATION WITH DOUG WISE (BUILDING OFFICIAL)
 AND ROBERT BROWN (ASSISTANT BUILDING OFFICIAL) THE
 CONTRACTOR CAN REPLACE THE SLIDING DOOR WITH AN
 IN-SWING DOOR TO COMPLY WITH EXCEPTION ON SECTION
 R311.5.4 OR CONTRACTOR CAN SUBMIT THE REVISION FOR THE
 BUILDING OFFICIAL APPROVAL UNDER THE ALTERNATIVE DESIGN
 AND METHODS OF SEC. 104.11 OF CITY AMENDMENTS TO FBC.
 PROVIDE COMPLETE INFORMATION FOR BUILDING OFFICIAL
 REVIEW AND APPROVAL. CONTACT DOUG WISE AT (561)805-6650
 OR ROBERT BROWN AT (561)805-6652.
  
 2- IF REPLACING DOOR WITH IN-SWING DOOR, THEN, PROPER
 PRODUCT APPROVAL (2 COPIES) IS REQUIRED BY DCA RULE
 9N-3. AND, DESIGNER OF RECORD TO REVIEW AND APPROVE IN
 WRITING. SEC. 106.3.3 CITY AMENDMENTS TO FBC.
  
 3- THIS STAIRS ARE A REVISION TO THE ORIGINAL DESIGN
 INTENT. ARCHITECT NEEDS TO REVISE HIS PLANS TO REFLECT
 THIS CHANGE AND SUBMIT TO THIS OFFICE. SEC. 106.1 CITY
 AMENDMENTS.
  
  
  
 ***NOTE: THE FOLLOWING ITEMS FROM FIRST REVIEW NEED TO
 BE ADDRESSED ALSO:
  
 1- HANDRAIL REQUIRED. SEE SEC. R311.5.6.
  
 2- SPECIFY RISER AND TREADS DIMENSIONS TO VERIFY
 COMPLIANCE WITH SEC. R311.5.3.
  
 3- GUARDRAIL MAY BE REQUIRED. SPECIFY LANDING HEIGHT TO
 VERIFY COMPLIANCE WITH SEC. R312.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-06-07 Cont ID  
Sent By jgomez Date 2011-06-07 Time 14:59 Rev Time 0.00
Received By jgomez Date 2011-06-07 Time 14:58 Sent To PC
Notes
2011-06-07 15:38:28RESIDENTIAL (R3) STAIR REVISION, BUILDING REVIEW
 CHECKLIST.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- PROPOSED STAIR REVISION DOESN'T COMPLY WITH THE
 LANDING AT DOORS AS REQUIRED BY SEC. R311.4.3. "THERE
 SHALL BE A FLOOR OR LANDING ON EACH SIDE OF EACH
 EXTERIOR DOOR". PROVIDE LANDING AS REQUIRED.
  
 2- HANDRAIL REQUIRED. SEE SEC. R311.5.6.
  
 3- SPECIFY RISER AND TREADS DIMENSIONS TO VERIFY
 COMPLIANCE WITH SEC. R311.5.3.
  
 4- GUARDRAIL MAY BE REQUIRED. SPECIFY LANDING HEIGHT TO
 VERIFY COMPLIANCE WITH SEC. R312.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-06-08 Cont ID  
Sent By jgomez Date 2011-06-08 Time 15:07 Rev Time 0.00
Received By jgomez Date 2011-06-08 Time 15:07 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-06-07 Cont ID  
Sent By jgomez Date 2011-06-07 Time 15:40 Rev Time 0.00
Received By jgomez Date 2011-06-07 Time 10:36 Sent To  
Notes
2011-06-07 10:36:39TO JG DESK

Review Stop P PLUMBING
Rev No 1 Status P Date 2011-06-07 Cont ID  
Sent By jgomez Date 2011-06-07 Time 15:39 Rev Time 0.00
Received By jgomez Date 2011-06-07 Time 15:39 Sent To  
Notes
2011-06-07 15:40:28REVISED GAS RISER DIAGRAM.