Plan Review Details - Permit 11060099
Plan Review Stops For Permit 11060099
Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2011-08-17 Cont ID  
Sent By wjolin Date 2011-08-17 Time 10:07 Rev Time 0.00
Received By wjolin Date 2011-08-17 Time 10:03 Sent To M
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2011-08-03 Cont ID  
Sent By wjolin Date 2011-08-03 Time 13:15 Rev Time 0.00
Received By wjolin Date 2011-08-03 Time 11:52 Sent To  
Notes
2011-08-03 12:29:13201 CLEMATIS STREET
 PERMIT #11060099
 MASTER #11030136
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE COMMUNICATING SPACE OF LOBBY #200 SHOWS CLOSELY
 SPACED SPRINKLERS PROTECTING THE GLASS CURTAIN WALL;
 THIS DESIGN ALTERNATIVE IS ONLY PERMITTED FOR ATRIUM
 FIRE SEPARATION.
  
 STORAGE #215 SHOWS A COUPLE SPRINKLERS SPACED 16 FEET
 APART.
  
 STORAGE LEDGER #301 SHOWS SPRINKLERS PROTECTING MORE
 THAN 130 SQUARE FEET.
  
 REPEAT COMMENT: PROVIDE LOCKABLE KNOX CAPS ON EXISTING
 FIRE DEPARTMENT CONNECTION. CAPS CAN BE ORDERED FROM
 WWW.KNOXBOX.COM.
  
 REPEAT COMMENT: PROVIDE RECENT FIRE HYDRANT FLOW TEST
 DATA ON PLANS.
  
 NOTE: FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE
 DURING DEMOLITION AND RENOVATION ACTIVITIES. IN THE
 EVENT A FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR
 MORE THAN 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING
 SHALL BE PLACED UNDER A FIRE WATCH. ALL FIRE WATCH
 REQUESTS MUST BE APPROVED AND SUBMITTED IN WRITING TO
 THE OFFICE OF THE FIRE MARSHAL.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2011-06-07 Cont ID  
Sent By wjolin Date 2011-06-07 Time 17:15 Rev Time 0.00
Received By wjolin Date 2011-06-07 Time 16:39 Sent To M
Notes
2011-06-07 17:14:48201 CLEMATIS STREET
 PERMIT #11060099
 MASTER #11030136
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE JOB VALUE AND SCOPE OF SPRINKLER WORK DOES NOT
 CORRESPOND WITH THE AMOUNT OF RENOVATIONS OCCURING AT
 THE FACILITY. FOR EXAMPLE THE ARCHITECTURAL SHEETS SHOW
 SEVERAL CEILINGS THAT ARE BEING ALTERED OR REPLACED;
 HOWEVER, THE SPRINKLER SCOPE DOES NOT SEEM TO ACCOUNT
 FOR THESE SPACES. ENGINEERING SHEET FP1.01 INDICATES
 THE 1-1/2" SPRINKLER LOOP TO BE RAISED TIGHT TO
 STRUCTURE AND NEW SPRINKLERS TO BE LOCATED UNDER THE
 NEW CANOPY ETC. REAR STAIR NUMBER 12 IS A NEW STAIR.
  
 PROVIDE LOCKABLE KNOX CAPS ON EXISTING FIRE DEPARTMENT
 CONNECTION. CAPS CAN BE ORDERED FROM WWW.KNOXBOX.COM.
  
 PROVIDE RECENT FIRE HYDRANT FLOW TEST DATA ON PLANS.
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE APPROVED AND SUBMITTED IN WRITING TO THE OFFICE OF
 THE FIRE MARSHAL.
  
 CLOSELY SPACED SPRINKLERS AND 18-INCH DEEP DRAFTSTOPS
 ARE REQUIRED AROUND THE ENTRANCE LOBBY FLOOR OPENING.
  
 IDENTIFY SIZE OF STAGE AS STAGES GREATER THAN 1,000
 SQUARE FEET REQUIRE FIRE DEPARTMENT HOSE VALVES.
  
 COSTUME AND STORAGE SPACES SHALL BE DESIGNED AS
 ORDINARY HAZARD DUE TO THE INCREASED FIRE LOAD.
  
 SPRINKLER IN CONFERENCE ROOM 118 IS MORE THAN 9' FROM
 WALL.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2011-08-22 Cont ID  
Sent By hmoser Date 2011-08-22 Time 16:25 Rev Time 0.00
Received By hmoser Date 2011-08-15 Time 07:19 Sent To  
Notes
2011-08-15 07:20:05SENT TO FIRE BOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-08-03 Cont ID  
Sent By wjolin Date 2011-08-03 Time 13:15 Rev Time 0.00
Received By wjolin Date 2011-07-29 Time 15:41 Sent To  
Notes
2011-07-29 15:41:58IN MECH. BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-06-16 Cont ID  
Sent By hmoser Date 2011-06-16 Time 09:49 Rev Time 0.00
Received By hmoser Date 2011-06-03 Time 13:41 Sent To  
Notes
2011-06-03 13:42:09SENT TO FIRE BOX.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2011-08-22 Cont ID  
Sent By hmoser Date 2011-08-22 Time 16:25 Rev Time 0.00
Received By hmoser Date 2011-08-22 Time 16:13 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2011-08-01 Cont ID  
Sent By hmoser Date 2011-08-01 Time 13:31 Rev Time 0.00
Received By hmoser Date 2011-08-01 Time 13:25 Sent To FIRE
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2011-06-16 Cont ID  
Sent By hmoser Date 2011-06-16 Time 08:52 Rev Time 0.00
Received By hmoser Date 2011-06-16 Time 08:52 Sent To  
Notes
2011-06-16 09:48:55PLANS DENIED
 1) ADDRESS ON THE FIRE SPRINKLER APPLICATION 11060099
 DOES NOT MATCH THE MASTER 11030136.
 2) PLEASE PROVIDE A SIGNED CONTRACT TO VERIFY THE VALUE
 OF THE JOB.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732
 [email protected]