| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | THE JOB VALUE AND SCOPE OF SPRINKLER WORK DOES NOT |
| | CORRESPOND WITH THE AMOUNT OF RENOVATIONS OCCURING AT |
| | THE FACILITY. FOR EXAMPLE THE ARCHITECTURAL SHEETS SHOW |
| | SEVERAL CEILINGS THAT ARE BEING ALTERED OR REPLACED; |
| | HOWEVER, THE SPRINKLER SCOPE DOES NOT SEEM TO ACCOUNT |
| | FOR THESE SPACES. ENGINEERING SHEET FP1.01 INDICATES |
| | THE 1-1/2" SPRINKLER LOOP TO BE RAISED TIGHT TO |
| | STRUCTURE AND NEW SPRINKLERS TO BE LOCATED UNDER THE |
| | NEW CANOPY ETC. REAR STAIR NUMBER 12 IS A NEW STAIR. |
| | |
| | PROVIDE LOCKABLE KNOX CAPS ON EXISTING FIRE DEPARTMENT |
| | CONNECTION. CAPS CAN BE ORDERED FROM WWW.KNOXBOX.COM. |
| | |
| | PROVIDE RECENT FIRE HYDRANT FLOW TEST DATA ON PLANS. |
| | |
| | FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING |
| | DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A |
| | FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN |
| | 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE |
| | PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST |
| | BE APPROVED AND SUBMITTED IN WRITING TO THE OFFICE OF |
| | THE FIRE MARSHAL. |
| | |
| | CLOSELY SPACED SPRINKLERS AND 18-INCH DEEP DRAFTSTOPS |
| | ARE REQUIRED AROUND THE ENTRANCE LOBBY FLOOR OPENING. |
| | |
| | IDENTIFY SIZE OF STAGE AS STAGES GREATER THAN 1,000 |
| | SQUARE FEET REQUIRE FIRE DEPARTMENT HOSE VALVES. |
| | |
| | COSTUME AND STORAGE SPACES SHALL BE DESIGNED AS |
| | ORDINARY HAZARD DUE TO THE INCREASED FIRE LOAD. |
| | |
| | SPRINKLER IN CONFERENCE ROOM 118 IS MORE THAN 9' FROM |
| | WALL. |
| | |
| | WESLEY JOLIN |
| | WEST PALM BEACH FIRE RESCUE |
| | FIRE & LIFE SAFETY PLAN REVIEW |
| | |