| 2011-06-10 13:46:50 | 225 CLEMATIS STREET, SUITE #200 |
| | PERMIT #11050822 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | DESIGN SHALL CONFORM TO THE FLORIDA FIRE PREVENTION |
| | CODE 2007 EDITION: NFPA 1 AND NFPA 101 - 2006 EDITION |
| | WITH FLORIDA AMENDMENTS. |
| | |
| | PROVIDE ADDRESS SUITE NUMBER ON PLANS. |
| | |
| | INDICATE THE PREVIOUS OCCUPANCY/USE OF THIS SPACE. |
| | INDICATE IF ANY DEMOLITION WORK WILL BE PERFORMED. |
| | |
| | ALL DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS |
| | OF NFPA 241. |
| | |
| | FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING |
| | DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A |
| | FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN |
| | 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE |
| | PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST |
| | BE APPROVED AND SUBMITTED IN WRITING TO THE OFFICE OF |
| | THE FIRE MARSHAL. |
| | |
| | THIS SPACE IS FUNCTIONING AS AN ASSEMBLY OCCUPANCY NOT |
| | A BUSINESS OCCUPANCY. OCCUPANT LOAD SHOULD BE BASED |
| | UPON 15 SQ.FT. PER PERSON PER NFPA 101 TABLE 7.3.1.2. |
| | |
| | EACH NEW SMOKE OR FIRE-RATED WALL/PARTITION SHALL BE |
| | PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING READING |
| | FIRE/SMOKE BARRIER?PROTECT ALL OPENINGS. CHARACTERS |
| | SHALL BE AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN |
| | WIDTH. IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15 |
| | FEET ON CENTER. REFERENCE SECTION 8.3.2.4 OF FLORIDA |
| | FIRE PREVENTION CODE ? NFPA 101 |
| | |
| | THE RELEASING MECHANISM ON ALL DOORS SHALL OPEN THE |
| | DOOR WITH NOT MORE THAN ONE RELEASING OPERATION. THE |
| | RELEASING MECHANISM SHALL HAVE AN OBVIOUS METHOD OF |
| | OPERATION THAT IS READILY OPERATED UNDER ALL LIGHTING |
| | CONDITIONS. THE RELEASING DEVICE SHOULD BE CAPABLE OF |
| | BEING OPERATED WITH ONE HAND AND SHOULD NOT REQUIRE |
| | TIGHT GRASPING, TIGHT PINCHING OR TWISTING OF THE WRIST |
| | TO OPERATE PER SECTION 7.2.1.5.9 OF NFPA 101 FLORIDA |
| | EDITION 2007. PANIC OR FIRE EXIT HARDWARE REQUIRED FOR |
| | ASSEMBLY OCCUPANCIES WITH AN OCCUPANT LOAD EXCEEDING |
| | 100 PERSONS. |
| | |
| | PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH |
| | EXIT SIGNS. |
| | |
| | PORTABLE FIRE EXTINGUISHERS SHALL HAVE A MINIMUM RATING |
| | OF 2A:10BC AND SHALL BE TAGGED BY A LICENSED FIRE |
| | EXTINGUISHER COMPANY. |
| | |
| | SHEET FA1.01: NOTIFICATION SIGNALS FOR OCCUPANTS TO |
| | EVACUATE SHALL BE AUDIBLE AND VISIBLE SIGNALS IN |
| | ACCORDANCE WITH NFPA 72. CURRENTLY ONLY STROBE DEVICES |
| | HAVE BEEN PROVIDED FOR THE STUDIO AND OFFICE SPACES. |
| | |
| | SHEET FA1.01: PER LOCAL CODE AMENDMENTS, DUCT SMOKE |
| | DETECTORS SHALL INITIATE A GENERAL FIRE ALARM |
| | CONDITION. |
| | |
| | VERIFY TOTAL SPRINKLER SCOPE DOES NOT AFFECT 50 OR MORE |
| | SPRINKLERS, AS SECTION 105.3.1.2(2) OF THE FLORIDA |
| | BUILDING CODE REQUIRES SEALED FIRE PROTECTION |
| | CONSTRUCTION DOCUMENTS FOR THE RELOCATION, ADDITION, OR |
| | DELETION OF 50 OR MORE AUTOMATIC FIRE SPRINKLERS. |
| | |
| | PER FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004, |
| | PLANS SHALL INDICATE THE HAZARD CLASSIFICATIONS, DESIGN |
| | DENSITIES, AND WATER SUPPLY DATA. |
| | |
| | USE OF FLEXIBLE DROPS IN LIEU OF STEEL PIPING WILL |
| | REQUIRE HYDRAULIC CALCULATIONS ACCOUNTING FOR THE |
| | ADDITIONAL FRICTION LOSS IN THIS MATERIAL. INDICATE |
| | MAXIMUM LENGTH OF FLEXIBLE DROPS TO BE USED. |
| | |
| | WESLEY JOLIN |
| | WEST PALM BEACH FIRE RESCUE |
| | FIRE & LIFE SAFETY PLAN REVIEW |
| | |