Plan Review Details - Permit 11050812
Plan Review Stops For Permit 11050812
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-06-17 Cont ID  
Sent By jwitmer Date 2011-06-17 Time 07:40 Rev Time 1.30
Received By jwitmer Date 2011-06-17 Time 07:40 Sent To  
Notes
2011-06-17 07:57:39BUILDING PLAN REVIEW
 PERMIT: 11050812
 ADD: 815 33RD ST
 CONT: TO BE DETERMINED
 TEL: (561)839-0700
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
  
 2007/09 FBC-B 313.2.2 GROUP DAY CARE HOME. A GROUP DAY
 CARE HOME IS A DAY-CARE HOME IN WHICH AT LEAST SEVEN
 BUT NOT MORE THAN 12 CLIENTS RECEIVE CARE, MAINTENANCE,
 AND SUPERVISION BY OTHER THAN THEIR RELATIVE(S) OR
 LEGAL GUARDIAN(S) FOR LESS THAN 24 HOURS PER DAY WITH
 NO MORE THAN THREE CLIENTS INCAPABLE OF
 SELF-PRESERVATION.
  
 1ST REVIEW
 ACTION: DENIED
  
 PLEASE PROVIDE THE FOLLOWING INFORMATION FOR CODE
 COMPLIANCE:
  
 1) 436.2 CLOSET DOORS. EVERY CLOSET DOOR LATCH SHALL BE
 SUCH THAT CLIENTS CAN OPEN THE DOOR FROM INSIDE THE
 CLOSET.
  
 2) 436.3 BATHROOM DOORS. EVERY BATHROOM DOOR LOCK SHALL
 BE DESIGNED TO PERMIT OPENING OF THE LOCKED DOOR FROM
 THE OUTSIDE IN AN EMERGENCY. THE OPENING DEVICE SHALL
 BE READILY ACCESSIBLE TO THE STAFF.
  
 3) 436.4 DOOR CLOSURE. ANY EXIT DOOR DESIGNED TO BE
 NORMALLY CLOSED SHALL BE KEPT CLOSED AND SHALL COMPLY
 WITH SECTION 715.3.
  
 4) PLANS DO NOT MAKE IT CLEAR IF THE THREE BEDROOMS ARE
 TO BE PART OF THE DAY CARE HOME, IF SO PLEASE COMPLY
 WITH :
  
 436.10.5 SMOKE DETECTION SYSTEMS.
  
 436.10.5.1 SINGLE-STATION SMOKE ALARMS INSTALLED IN
 ACCORDANCE WITH THE HOUSEHOLD FIRE WARNING EQUIPMENT
 REQUIREMENTS OF CHAPTER 2 OF NFPA 72 SHALL BE INSTALLED
 WITHIN DAY CARE HOMES.
  
 EXCEPTION: SYSTEM SMOKE DETECTORS INSTALLED IN
 ACCORDANCE WITH NFPA 72 AND ARRANGED TO FUNCTION IN THE
 SAME MANNER SHALL BE PERMITTED.
  
 436.10.5.2 WHERE THE DAY CARE HOME IS LOCATED WITHIN A
 BUILDING OF ANOTHER OCCUPANCY, ANY CORRIDORS SERVING
 THE DAY CARE HOME SHALL BE PROVIDED WITH A COMPLETE
 SMOKE DETECTION SYSTEM INSTALLED IN ACCORDANCE WITH
 NFPA 72.
  
 436.10.5.3 SINGLE-STATION SMOKE ALARMS SHALL BE POWERED
 BY THE BUILDING ELECTRICAL SYSTEM.
  
 436.10.5.4 SINGLE-STATION SMOKE ALARMS SHALL BE
 PROVIDED IN ALL ROOMS USED FOR SLEEPING.
  
 436.10.5.5 WHERE TWO OR MORE SMOKE ALARMS ARE REQUIRED
 WITHIN A LIVING UNIT, SUITE OF ROOMS, OR SIMILAR AREA,
 THEY SHALL BE ARRANGED SO THAT OPERATION OF ANY SMOKE
 ALARM SHALL CAUSE ALL SMOKE ALARMS WITHIN THE LIVING
 UNIT, SUITE OF ROOMS OR SIMILAR AREA TO SOUND.
  
 436.10.5.5.1 THE ALARMS SHALL SOUND ONLY WITHIN AN
 INDIVIDUAL LIVING UNIT, SUITE OF ROOMS OR SIMILAR AREA
 AND SHALL NOT ACTUATE THE BUILDING FIRE ALARM SYSTEM.
 REMOTE ANNUNCIATION SHALL BE PERMITTED.
  
 JAMES A. WITMER C.B.O.
 COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: (561)805-6715
 FAX:(561)805-6731
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2011-06-20 Cont ID  
Sent By rlecky Date 2011-06-20 Time 11:51 Rev Time 0.00
Received By rlecky Date 2011-06-20 Time 11:44 Sent To  
Notes
2011-06-20 11:52:49 
 ALL RECEPTACLES SHALL BE TAMPER RESISTANT.
 RECEPTACLES IN BATHROOMS AND KITCHEN AREAS SHALL BE
 GFCI PROTECTED
 INTERCONNECTED SMOKE ALARMS WITH BATTERY BACK UP ARE
 REQUIRED IN EACH SLEEPING AREA AND OUTSIDE SLEEPING
 AREAS
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 561-805-6718
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2011-06-09 Cont ID  
Sent By wjolin Date 2011-06-09 Time 16:51 Rev Time 0.00
Received By wjolin Date 2011-06-09 Time 15:19 Sent To  
Notes
2011-06-09 16:51:09815 33RD STREET
 PERMIT #11050812
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 PROVIDE SMOKE ALARMS IN ALL SLEEPING AREAS. SMOKE
 ALARMS SHALL BE POWERED BY THE BUILDING ELECTRICAL
 SYSTEM.
  
 ALL ESCAPE WINDOWS SHALL NOT BE MORE THAN 44 INCHES
 ABOVE THE FLOOR.
  
 PLEASE INDICATE THE AGES OF THE PEOPLE ATTENDING THE
 DAY CARE.
  
 DAY CARE HOMES SHALL BE OPERATED FOR LESS THAN 24-HOURS
 A DAY.
  
 EMERGENCY PLANS SHALL PROVIDED AT THE DAY CARE.
  
 EMERGENCY EGRESS/RELOCATION DRILLS SHALL BE CONDUCTED
 MONTHLY.
  
 FIRE PREVENTION INSPECTIONS SHALL BE CONDUCTED MONTHLY
 BY SENIOR MEMBERS OF THE STAFF. A COPY OF THE LATEST
 INSPECTION REPORT SHALL BE POSTED IN A CONSPICUOUS
 LOCATION PLACE IN THE DAY CARE FACILITY.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  
  
  
  

Review Stop HIST HISTORICAL
Rev No 1 Status N Date 2011-06-06 Cont ID  
Sent By jpapa Date 2011-06-06 Time 14:11 Rev Time 0.00
Received By jpapa Date 2011-06-06 Time 14:11 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-11-17 Cont ID  
Sent By shill Date 2011-06-21 Time   Rev Time 0.00
Received By shill Date 2011-06-01 Time 08:32 Sent To  
Notes
2011-06-01 08:32:41B18

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2011-06-21 Cont ID  
Sent By rregueir Date 2011-06-21 Time 10:43 Rev Time 0.00
Received By rregueir Date 2011-06-21 Time 09:16 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2011-06-21 Cont ID  
Sent By lwagner Date 2011-06-21 Time 09:30 Rev Time 0.00
Received By lwagner Date 2011-06-17 Time 14:42 Sent To  
Notes
2011-06-17 14:48:28FBC PLUMBING 2007 REVIEW #1
 DENIED:
  
 1. PLUMBING 403.1 MINIMUN PLUMBING FACILITIES -
 EDUCATIONAL/DAY CARE REQUIRE 1 DRINKING FOUNTAIN AND 1
 SERVICE SINK. A LAUNDRY SINK WOULD BE EQUAL TO A
 SERVICE SINK.
  
 ****NOTE****
 HTTP://WWW.PBCHD.COM/ENV/CHILD_CARE/CHILD_CARE_FACILITI
 ES.HTML
 THE HEALTH DEPARTMENT MAY HAVE MORE REQUIREMENTS FOR
 PLUMBING FACILITIES.
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  

Review Stop Z ZONING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By ajones Date 2011-06-08 Time 13:53 Sent To  
Notes
2011-06-08 13:54:4412 CHILDREN ALLOWED PER SPECIAL ACT BY FLORIDA
 LEGISLATIVE #2010-249