Plan Review Details - Permit 11050805
Plan Review Stops For Permit 11050805
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2011-07-15 Cont ID  
Sent By jwitmer Date 2011-07-15 Time 09:28 Rev Time 0.77
Received By jwitmer Date 2011-07-15 Time 09:28 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-06-08 Cont ID  
Sent By jwitmer Date 2011-06-08 Time 15:36 Rev Time 0.77
Received By jwitmer Date 2011-06-08 Time 15:20 Sent To  
Notes
2011-06-08 15:49:33BUILDING PLAN REVIEW
 PERMIT: 11050805
 ADD: 314 3RD ST
 CONT: CATALFUMO
 TEL: (561)283-5121
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODEW/ 2009 FBC
 SUPPLEMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) BOTH THE PLANS (SB001) AND STRUCTURAL CALCULATIONS
 INDICATE THIS STRUCTURE IS DESIGNED TO BE INSTALLED IN
 A "B" EXPOSURE, PLEASE REVIEW:
 1609.4.2 SURFACE ROUGHNESS CATEGORIES. A GROUND SURFACE
 ROUGHNESS WITHIN EACH 45-DEGREE (0.79 RAD) SECTOR SHALL
 BE DETERMINED FOR A DISTANCE UPWIND OF THE SITE AS
 DEFINED IN SECTION 1609.4.3 FROM THE CATEGORIES DEFINED
 BELOW, FOR THE PURPOSE OF ASSIGNING AN EXPOSURE
 CATEGORY AS DEFINED IN SECTION 1609.4.3.
 EXPOSURE C. OPEN TERRAIN WITH SCATTERED OBSTRUCTIONS,
 INCLUDING SURFACE UNDULATIONS OR OTHER IRREGULARITIES,
 HAVING HEIGHTS GENERALLY LESS THAN 30 FEET (9144 MM)
 EXTENDING MORE THAN 1,500 FEET (457.2 M) FROM THE
 BUILDING SITE IN ANY QUADRANT. THIS EXPOSURE SHALL ALSO
 APPLY TO ANY BUILDING LOCATED WITHIN EXPOSURE B-TYPE
 TERRAIN WHERE THE BUILDING IS WITHIN 100 FEET
 HORIZONTALLY IN ANY DIRECTION OF OPEN AREAS OF EXPOSURE
 C-TYPE TERRAIN THAT EXTENDS MORE THAN 600 FEET (182.9
 M) AND WIDTH GREATER THAN 150 FT. IN THE UPWIND
 DIRECTION. SHORT-TERM (LESS THAN TWO YEAR) CHANGES IN
 THE PRE-EXISTING TERRAIN EXPOSURE, FOR THE PURPOSES OF
 DEVELOPMENT, SHALL NOT BE CONSIDERED OPEN FIELDS. WHERE
 DEVELOPMENT BUILDOUT WILL OCCUR WITHIN THREE YEARS AND
 THE RESULTANT CONDITION WILL MEET THE DEFINITION OF
 EXPOSURE B, EXPOSURE B SHALL BE REGULATING FOR THE
 PURPOSE OF PERMITTING. THIS CATEGORY INCLUDES FLAT OPEN
 COUNTRY, GRASSLANDS AND OCEAN OR GULF SHORELINES AND
 SHALL EXTEND DOWNWIND FOR A DISTANCE OF 1500 FEET. FOR
 BUILDINGS LOCATED WITHIN A DISTANCE OF 600 FEET OF
 INLAND BODIES OF WATER THAT PRESENT A FETCH OF 1 MILE
 (1.61 KM) OR MORE OR INLAND WATERWAYS OR RIVERS WITH A
 WIDTH OF 1 MILE (1.61 KM) OR MORE ROOF SHEATHING UPLIFT
 AND ROOF-TO-WALL UPLIFT LOADS SHALL BE INCREASED BY 20
 PERCENT.
  
 2) SHEET SB102 KEY NOT# 6 INDICATES THERE IS A SOILS
 REPORT TO INDICATE THE MINIMUM SAFE BEARING VALUE OF
 THE SOIL SHALL BE AND HOW TO ACHIEVE IT,
 2007/09 FBC-B 1802.2.1.
  
 3) SHEET SB001 NOTES UNDER THE HEADING FOR V STRUCTURAL
 ALUMINUM NOTE # 6 STANDING SEAM 0.050" THICK ROOF
 DECKING, PLEASE PROVIDE PRODUCT APPROVAL FOR STRUCTURAL
 STANDING SEAM ROOF DECKING RULE 9N-3, AND COMPONENTS
 AND CLADDING 1609 FBC-B.
  
 JAMES A. WITMER C.B.O.
 COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: (561)805-6715
 FAX:(561)805-6731
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2011-07-28 Cont ID  
Sent By rlecky Date 2011-07-28 Time 14:07 Rev Time 0.00
Received By rlecky Date 2011-07-28 Time 13:59 Sent To  
Notes
2011-07-28 14:07:36 
 NOTED ON PLAN IN RED THAT TWO GROUND RODS ARE REQUIRED.
 NEC 250.53
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 561-805-6718
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2011-06-20 Cont ID  
Sent By rlecky Date 2011-06-20 Time 08:55 Rev Time 0.00
Received By rlecky Date 2011-06-20 Time 08:38 Sent To  
Notes
2011-06-20 08:54:11PROVIDE A CONSTRUCTION DETAIL FOR OF THE NEW LOAD
 CENTER. SUPPORTS, WEATHER RESISTANCE RATING, GROUNDING
 ETC. NEC 215.5, 215.6, 250.32
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 561-805-6718
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2011-07-12 Cont ID  
Sent By mgonzale Date 2011-07-12 Time   Rev Time 1.00
Received By mgonzale Date 2011-07-12 Time   Sent To  
Notes
2011-07-12 12:38:49PLAN IS ACCEPTABLE.
  
 PROVIDE PERVIOUS AND IMPERVIOUS SO THAT STORM WATER
 ACCOUNT IS UPDATED.
  
 THANK YOU!
  
 MANUEL JULIAN GONZALEZ
 CSD ENGINEERING REVIEW
 401 CLEMATIS STREET,
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2011-06-10 Cont ID  
Sent By wjolin Date 2011-06-10 Time 15:18 Rev Time 0.00
Received By wjolin Date 2011-06-10 Time 14:37 Sent To  
Notes
2011-06-10 15:18:06314 3RD STREET
 PERMIT #11050805
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SHEET LP-3: FIRE HYDRANTS SHALL BE PROVIDED WITH
 CLEARANCES OF 7?-6? TO THE FRONT/SIDES AND 4? TO THE
 BACKSIDE PER SECTION 18.3.4.1 OF NFPA 1 FLORIDA
 EDITION.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2011-07-28 Cont ID  
Sent By rlecky Date 2011-07-28 Time 14:40 Rev Time 0.00
Received By rlecky Date 2011-07-27 Time 09:47 Sent To  
Notes
2011-07-27 09:47:55INCOMING TO ADDRESS ELECTRICAL COMMENTS: SENT TO R
 LECKYS DESK. JW

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-07-28 Cont ID  
Sent By rlecky Date 2011-07-28 Time 14:40 Rev Time 0.00
Received By rlecky Date 2011-07-14 Time 13:55 Sent To  
Notes
2011-07-14 14:02:55RE-SUBMITTAL PACKAGE SUBMITTED TO ADDRESS BUILDING
 COMMENTS ONLY. PACKAGE SENT TO SHELF C3 FOR REVIEW.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-07-15 Cont ID  
Sent By jwitmer Date 2011-06-20 Time 09:29 Rev Time 0.00
Received By jwitmer Date 2011-06-01 Time 09:43 Sent To  
Notes
2011-06-01 09:44:04SENT TO C8.

Review Stop L LANDSCAPING
Rev No 1 Status N Date 2011-06-09 Cont ID  
Sent By rkussner Date 2011-06-09 Time 14:13 Rev Time 0.00
Received By rkussner Date 2011-06-09 Time 14:13 Sent To  
Notes
2011-06-09 14:15:47***LANDSCAPE REVIEW NOT REQUIRED***
  
 PLEASE REFER TO PERMIT # 11060098 FOR LANDSCAPE PERMIT
 AND PLANS---RAK

Review Stop P PLUMBING
Rev No 1 Status P Date 2011-06-08 Cont ID  
Sent By lwagner Date 2011-06-08 Time 09:17 Rev Time 0.00
Received By lwagner Date 2011-06-07 Time 14:01 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2011-06-10 Cont ID  
Sent By aaponte Date 2011-06-10 Time 15:53 Rev Time 0.50
Received By aaponte Date 2011-06-10 Time 15:53 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved