Plan Review Details - Permit 11050759
Plan Review Stops For Permit 11050759
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2011-07-12 Cont ID  
Sent By jwitmer Date 2011-07-12 Time 13:38 Rev Time 0.33
Received By jwitmer Date 2011-07-12 Time 13:37 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2011-06-30 Cont ID  
Sent By jwitmer Date 2011-06-30 Time 13:35 Rev Time 0.77
Received By jwitmer Date 2011-06-30 Time 13:35 Sent To  
Notes
2011-06-30 13:38:38BUILDING PLAN REVIEW
 PERMIT: 11050759
 ADD: 525 S FLAGLER DR SUITE# (MEZZANINE LEVEL)
 CONTRACTOR: CAMBRIDGE
 TEL: (561)248-5266
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) SHEET A-2 INDICATES THE REMOVAL OF A WALL THAT IS
 COMMON TO THE FIRST FLOOR. THE PLANS INDICATE THIS TO
 BE A MEZZANINE LEVEL, IT CAN NOT BE DETERMINED IF THIS
 IS A MEZZANINE OR A INTERMETANT STORY, 2ND FLOOR THAT
 MAY NOT BE COMMON TO THE REST OF THE BUILDING. THE
 SQUARE FOOTAGE OF THE MEZZANINE IS INDICATED AS 2566 SQ
 FT THE CLEAR OPEN AREA BENEATH THE MEZZANINE WITHOUT
 ANY WALLS WILL NEED TO BE 5132 SQ FT TO MEET THE
 DEFINITION OF MEZZANINE.
 PLEASE PROVIDE DOCUMENTATION.505.2 EXCEPTION # 2.
  
 2) THE MEZZANINE IS SUPPOSE TO BE OPEN TO THE ROOM
 BELOW 505.4PLEASE INDICATE IF ANY OF THE EXEMPTIONS
 APPLY.
  
 3) IF THIS AREA IS TO BE CONSIDERED AN INTERMETANT 2ND
 FLOOR THAT WILL BE LOOKING INTO A LOBBY TYPE ATRIUM
 WITH A GLASS WALL, THEN THE REQUIREMNTS OF ATRIUM WILL
 APPLY TO THE GLASS WALL PLEASE SEE 404.5 EXCEPTION # 1.
  
 4) IF THIS IS TRUELY THE 2ND FLOOR IS THERE A THIRD
 FLOOR THAT IS COMMON TO THE ATRIUM THAT WOULD ENACT
 404.4 SMOKE CONTROL.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER C.B.O.
 COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: (561)805-6715
 FAX:(561)805-6731
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-06-09 Cont ID  
Sent By jwitmer Date 2011-06-09 Time 16:33 Rev Time 0.77
Received By jwitmer Date 2011-06-09 Time 16:33 Sent To  
Notes
2011-06-09 16:46:56BUILDING PLAN REVIEW
 PERMIT: 11050759
 ADD: 525 S FLAGLER DR SUITE# ?????
 CONT: CAMBRIDGE
 TEL: (561)248-5266
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) 2007 FBC 106.1.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE &
 EXTENT OF THE WORK PROPOSED & SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, AND RULES AND REGULATIONS AS
 DETERMINED BY THE BUILDING OFFICIAL.
 1A) SHEET A-0 THE PROJECT DATA IS NOT FILLED IN MOST OF
 THE SPACES INDICATE N/A, NOT APPLICABLE.
  
 1B) PLEASE CORRECT THE CODES TO THE CURRENT CODE CYCLE,
 2007 FBC.
  
 2) SHEETS A1-A3 DO NOT PROVIDE DETAIL AS IF THIS AREA
 IS PART OF THE COMMON AREA, PART OF A LOBBY AND OR
 ATRIUM OR A TENANT SPACE. THE PROPOSED BUTT GLASS WALL
 WIT APPEARS THAT IT IS NOT LOCATED WITHIN THE TENANT
 SPACE WHAT DOES IT DIVIDE? ADDITIONAL INFORMATION
 REQUIRED. 106.1.2.
  
 3) THE PLANS ARE SIGNED AND SEALED BY AN ENGINEER BUT
 ON THE PLANS SUBMITTED I DO NOT SEE ANY STRUCTURAL
 PAGES ATTACHED OR ANY STRUCTURAL ELEMENTS WITHIN THE
 SCOPE OF THE PROPOSED PROJECT. FLORIDA STATUTE 481.229
 (4) ENGINEERS CAN ONLY PREFORM ARCHITECTURAL SERVIVES
 WHEN THEY ARE PURELY INCIDENTAL TO HIS OR HER
 ENGINEERING PRECTICE.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER C.B.O.
 COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: (561)805-6715
 FAX:(561)805-6731
 E-MAIL: [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2011-07-06 Cont ID  
Sent By rlecky Date 2011-07-06 Time 10:28 Rev Time 0.00
Received By rlecky Date 2011-07-06 Time 10:28 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2011-06-01 Cont ID  
Sent By rlecky Date 2011-06-01 Time 12:36 Rev Time 0.00
Received By rlecky Date 2011-06-01 Time 12:31 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2011-07-12 Cont ID  
Sent By wjolin Date 2011-07-12 Time 10:15 Rev Time 0.00
Received By wjolin Date 2011-07-12 Time 10:09 Sent To B
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2011-07-08 Cont ID  
Sent By wjolin Date 2011-07-08 Time 13:55 Rev Time 0.00
Received By wjolin Date 2011-07-08 Time 13:15 Sent To B
Notes
2011-07-08 13:55:23525 SOUTH FLAGLER DRIVE - MEZZANINE
 PERMIT #11050759
 ROUND 3 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FOR ASSEMBLY OCCUPANCIES, THE COMMON PATH OF TRAVEL TO
 ONE MEANS OF EGRESS IS LIMITED TO 20 FEET WHEN THE
 OCCUPANT LOAD EXCEEDS 50 PERSONS PER SECTION 13.2.5.1.2
 OF NFPA 101 FLORIDA EDITION.
  
 IF NEW GLASS ENTRY DOORS ARE EQUIPPED WITH A LOCK OR
 LATCH, THESE DOORS ARE REQUIRED TO HAVE LISTED PANIC OR
 FIRE EXIT HARDWARE TO RELEASE THE LOCK/LATCH. POSTING A
 SIGN THAT THE DOORS ARE TO REMAIN UNLOCKED WHEN THE
 SPACE IS OCCUPIED IS ONLY ALLOWED FOR EXTERIOR DOORS
 PER SECTION 7.2.1.5.4 OF NFPA 101 FLORIDA EDITION.
  
 SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND FIRE ALARM SYSTEM.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2011-06-30 Cont ID  
Sent By wjolin Date 2011-06-30 Time 12:39 Rev Time 0.00
Received By wjolin Date 2011-06-30 Time 12:01 Sent To B
Notes
2011-06-30 12:39:31525 SOUTH FLAGLER DRIVE - MEZZANINE
 PERMIT #11050759
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PER SECTION 13.2.4.7 OF NFPA 101 FLORIDA EDITION
 (2006), MEZZANINES WITH AN OCCUPANT LOAD GREATER
 THAN100 PERSONS SHALL HAVE TWO SEPARATE MEANS OF
 EGRESS. A COMMON PATH OF TRAVEL IS LIMITED TO 20 FEET
 WHEN THE OCCUPANT LOAD EXCEEDS 50 PERSONS. NOTE: TWO
 REMOTE MEANS OF EGRESS CAN LEAD TO THE FLOOR BELOW WHEN
 THE OCCUPANT LOAD DOES NOT EXCEED 100 PERSONS.
  
 IF NEW GLASS ENTRY DOORS (DOUBLE DOORS) ARE EQUIPPED
 WITH A LOCK OR LATCH, THESE DOORS ARE REQUIRED TO HAVE
 LISTED PANIC HARDWARE TO RELEASE THE LOCK/LATCH.
  
 PROVIDE EMERGENCY LIGHTING. ARCHITECTURAL AND
 ELECTRICAL SHEETS INDICATE "EMERGENCY LIGHT" WHILE
 POINTING TO AN EXIT SIGN. INDICATE IF THESE FIXTURES
 ARE COMBINATION EXIT SIGNS AND EMERGENCY LIGHTS WITH
 BATTERY BACK-UP.
  
 REPEAT COMMENT: INDICATE ON SHEET E-1 WHAT TYPE OF FIRE
 ALARM DEVICES ARE SHOWN. SHEET ONLY INDICATES THE
 LETTER "F" INSIDE A SQUARE.
  
 SCOPE OF WORK WILL AFFECT FIRE PROTECTION EQUIPMENT
 CONTRARY TO SHEET E-2. SPRINKLERS AND FIRE ALARM
 NOTIFICATION APPLIANCES WILL NEED TO BE ADDED TO
 ACCOMODATE THE ROOMS CREATED BY ADDING WALLS.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2011-06-10 Cont ID  
Sent By wjolin Date 2011-06-10 Time 12:25 Rev Time 0.00
Received By wjolin Date 2011-06-10 Time 12:08 Sent To  
Notes
2011-06-10 12:25:45525 SOUTH FLAGLER DRIVE - MEZZANINE
 PERMIT #11050759
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 OVERALL PLAN INFORMATION IS INCOMPLETE TO PERFORM A
 THOROUGH REVIEW OF THE DRAWINGS.
  
 PROVIDE A LIFE SAFETY PLAN SHOWING TRAVEL DISTANCES TO
 EXITS, EXIT DOORS, EMERGENCY LIGHTS, FIRE ALARM
 DEVICES, FURNITURE LAYOUT, PORTABLE FIRE EXTINGUISHERS,
 OCCUPANT LOAD, FIRE-RATED WALLS ETC.
  
 IDENTIFY ROOM NAMES ON PLANS. INDICATE IF THESE ROOMS
 ARE A CHANGE OF USE.
  
 INDICATE WHICH FLOOR IS ASSOCIATED WITH THE MEZZANINE.
  
 DESIGN SHALL CONFORM TO THE FLORIDA FIRE PREVENTION
 CODE 2007 EDITION: NFPA 1 AND NFPA 101 - 2006 EDITION
 WITH FLORIDA AMENDMENTS.
  
 ALL DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS
 OF NFPA 241.
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE APPROVED AND SUBMITTED IN WRITING TO THE OFFICE OF
 THE FIRE MARSHAL.
  
 IF APPLICABLE, DOOR IS REQUIRED TO SWING IN THE
 DIRECTION OF EGRESS TRAVEL FOR AN OCCUPANT LOAD OF 50
 OR GREATER PERSONS PER SECTION 7.2.1.4.2 OF THE FLORIDA
 FIRE PREVENTION CODE: NFPA 101 - LIFE SAFETY CODE.
  
 INDICATE ON SHEET E-1 WHAT TYPE OF FIRE ALARM DEVICES
 ARE SHOWN.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By lmartine Date 2011-07-11 Time 10:29 Sent To  
Notes
2011-07-11 10:30:27********************EXPEDITED*********************
 PUT ON WESLEY'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By lmartine Date 2011-07-08 Time 10:14 Sent To  
Notes
2011-07-08 10:15:48**********************EXPEDITED***********************
 PUT ON WESLEY JOLIN'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-07-06 Cont ID  
Sent By rlecky Date 2011-07-06 Time 11:07 Rev Time 0.00
Received By rlecky Date 2011-06-22 Time 11:12 Sent To  
Notes
2011-06-24 11:13:41********************EXPEDITED******************
2011-06-24 11:13:05IN FIRE BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-06-24 Cont ID  
Sent By lmartine Date 2011-06-20 Time 11:11 Rev Time 0.00
Received By lmartine Date 2011-05-27 Time 16:32 Sent To  
Notes
2011-05-27 16:33:01B--6

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2011-06-20 Cont ID  
Sent By hmoser Date 2011-06-20 Time 11:13 Rev Time 0.00
Received By hmoser Date 2011-06-20 Time 11:09 Sent To  
Notes
2011-06-20 11:18:20CALLED CHRIS THE CONTRACTOR HE SAID THERE IS NO
 MECHANICAL WORK ON THIS JOB.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status N Date 2011-06-14 Cont ID  
Sent By lwagner Date 2011-06-14 Time 11:18 Rev Time 0.00
Received By lwagner Date 2011-06-13 Time 14:44 Sent To  
Notes
2011-06-14 11:18:54NO PLUMBING ON PLAN

Review Stop Z ZONING
Rev No 1 Status N Date 2011-06-10 Cont ID  
Sent By aaponte Date 2011-06-10 Time 16:07 Rev Time 0.25
Received By aaponte Date 2011-06-10 Time 16:07 Sent To  
Notes
2011-06-10 16:08:14ACCORDING TO CONTRACTOR'S DESCRIPTION THE SPACE IS USED
 FOR AS A "CLUB HOUSE" FOR BOARD MEETING AND SIMILIAR
 FUNCIONS. NO ACCESS BY GENERAL PUBLIC.