Plan Review Details - Permit 11050710
Plan Review Stops For Permit 11050710
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2011-07-21 Cont ID  
Sent By jwitmer Date 2011-07-21 Time 11:22 Rev Time 0.50
Received By jwitmer Date 2011-07-21 Time 11:21 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2011-06-17 Cont ID  
Sent By jwitmer Date 2011-06-17 Time 13:09 Rev Time 1.22
Received By jwitmer Date 2011-06-17 Time 11:51 Sent To  
Notes
2011-06-17 13:31:01BUILDING PROVISO:
 COVERSHEET INDICATES WINDZONE AS 130 MPH.
 THE CORRECT WIND ZONE IS 140 MPH, 3 SECOND GUST
 AND A EXPOSURE C. PLEASE BASE ANY EXTERIOR WIND
 DESIGN CRITERIA ON THIS INFORMATION.
  
 JAMES A. WITMER C.B.O.
 COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: (561)805-6715
 FAX:(561)805-6731
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2011-07-21 Cont ID  
Sent By rlecky Date 2011-07-21 Time 15:35 Rev Time 0.00
Received By rlecky Date 2011-07-21 Time 15:35 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2011-05-31 Cont ID  
Sent By rlecky Date 2011-05-31 Time 15:25 Rev Time 0.00
Received By rlecky Date 2011-05-31 Time 12:26 Sent To  
Notes
2011-05-31 12:55:59PROVIDE SPECIFICATIONS AND LISTING FOR P2 THRU P11
 CUSTOM BOTTLE LIGHTING FIXTURES SUPPLIED BY AMERITIC
 LIGHTING. NEC 110.3
 PROVIDE STRUCTURAL SUPPORT DETAIL FOR P2 THRU P11
 CUSTOM FIXTURES SUPPLIED BY AMERITIC FOR LUMINARIES
 RATED AT MORE THAN 50 POUNDS. NEC 410.36, 314.27
 GENERAL PURPOSE RECEPTACLES LOCATED AT BAR SINKS MUST
 BE GFCI PROTECTED. NEC 210.8 (B)
 A GFCI PROTECTED RECEPTACLE IS REQUIRED TO SERVICE THE
 MECHANICAL EQUIPMENT ON THE ROOF. NEC 210.63
  
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 561-805-6718
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2011-07-20 Cont ID  
Sent By wjolin Date 2011-07-20 Time 16:18 Rev Time 0.00
Received By wjolin Date 2011-07-20 Time 14:24 Sent To  
Notes
2011-07-20 16:17:561 NORTH CLEMATIS STREET #110
 PERMIT #11050710
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FIELD VERIFY DINING ROOM #104 DOOR IS EQUIPPED WITH
 PANIC HARDWARE.
  
 ANY NEW AND EXISTING FIRE DAMPERS FOR THIS SPACE SHALL
 BE DROP TESTED.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2011-05-27 Cont ID  
Sent By wjolin Date 2011-05-27 Time 16:11 Rev Time 0.00
Received By wjolin Date 2011-05-27 Time 13:30 Sent To  
Notes
2011-05-27 16:11:521 NORTH CLEMATIS STREET, SUITE #110
 PERMIT #11050710
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 ALL DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS
 OF NFPA 241.
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE APPROVED AND SUBMITTED IN WRITING TO THE OFFICE OF
 THE FIRE MARSHAL.
  
 PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY
 RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING
 NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM
 WWW.KNOXBOX.COM.
  
 PROVIDE PORTABLE FIRE EXTINGUISHER LOCATIONS ON PLANS.
 EXTINGUISHERS SHALL HAVE A MINIMUM RATING OF 2A:10BC
 AND SHALL BE TAGGED BY A LICENSED FIRE EXTINGUISHER
 COMPANY. TRAVEL DISTANCE TO EXTINGUISHERS SHALL NOT
 EXCEED 75 FEET.
  
 PROVIDE TACTILE SIGNAGE AT EXIT DOORS.
  
 IF ENTRY DOOR 102 IS EQUIPPED WITH A LATCH, PANIC
 HARDWARE IS NEEDED ON THIS EXISTING DOOR.
  
 THE OCCUPANT LOAD TO BE POSTED IN THE BUILDING INTERIOR
 SHOULD NOT INCLUDE THE EXTERIOR SEATING.
  
 INDICATE THE AMOUNT OF COAL THAT CAN BE STORED IN THE
 COAL STORAGE COMPARTMENT OF THE BRICK OVEN. NOTE: PER
 NFPA 96 SECTION 14.9.2.1. FUEL STORAGE SHALL NOT EXCEED
 A ONE-DAY SUPPLY WHERE STORAGE IS LOCATED IN THE SAME
 ROOM AS THE SOLID FUELED APPLIANCE, OR IN THE SAME
 ROOMS AS THE FUEL-LOADING OR CLEAN-OUT DOORS.
  
 PER NFPA 96 SECTION14.9.3.7.3 APPLIANCES WITH FIREBOXES
 OVER 5 FT3 THE WATER SOURCE SHALL BE A FIXED PIPE WATER
 SYSTEM WITH A HOSE OF ADEQUATE LENGTH TO REACH THE
 COMBUSTION AND COOKING CHAMBERS OF THE APPLIANCE.
  
 ALL OVEN ASH SHALL BE REMOVED FROM THE ASH COMPARTMENT
 AT LEAST ONCE PER DAY. THE ASH SHALL BE SPRAYED
 ADEQUATELY WITH WATER BEFORE REMOVAL TO EXTINGUISH ANY
 HOT ASH OR CINDERS AND TO CONTROL THE DUST WHEN THE ASH
 IS MOVED.
  
 PER NFPA 96 SECTION 14.9.3.8.1 A HEAVY METAL CONTAINER
 OR CART (MINIMUM 16 GAUGE) WITH A COVER SHALL BE
 PROVIDED FOR THE REMOVAL OF ASH. THE ASH REMOVAL
 CONTAINER OR CART SHALL NOT EXCEED A MAXIMUM OF 20 GAL
 CAPACITY, SHALL BE ASSIGNED FOR THIS ONE PURPOSE, SHALL
 BE ABLE TO BE HANDLED EASILY BY ANY EMPLOYEE ASSIGNED
 THE TASK, AND SHALL PASS EASILY THROUGH ANY PASSAGEWAY
 TO THE OUTSIDE OF THE BUILDING. THE CONTAINER OR CART
 SHALL ALWAYS BE COVERED WHEN IT IS BEING MOVED THROUGH
 THE PREMISES.
  
 FOR ISSUANCE OF A GENERAL BUILDING PERMIT, SEALED
 CONSTRUCTION DOCUMENTS ARE REQUIRED FOR FIRE SPRINKLER
 AND FIRE ALARM INSTALLATION AND MODIFICATIONS. UNDER A
 SEPARATE PERMIT, SHOP DRAWINGS CONFORMING TO THE
 ENGINEER'S CONSTRUCTION DOCUMENTS WILL BE REQUIRED
 AFTER THE GENERAL BUILDING PERMIT HAS BEEN ISSUED.
  
 PROVIDE A DETAIL OF THE LARGE AMERITIC LIGHTING
 FIXTURES (P11). NOTE: THESE LIGHTING FIXTURES MAY
 OBSTRUCT THE AUTOMATIC SPRINKLERS.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW

Review Stop I INCOMING/PROCESSING
Rev No 2 Status F Date 2011-07-27 Cont ID  
Sent By hmoser Date 2011-07-27 Time 09:03 Rev Time 0.00
Received By hmoser Date 2011-07-19 Time 11:29 Sent To  
Notes
2011-07-27 09:05:347/26/11 NO CONTRACTOR SIGNED ON APPLICATION
2011-07-19 11:29:58SEND TO B16 SHELF FOR REVIEW.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-06-17 Cont ID  
Sent By jwitmer Date 2011-06-17 Time 13:31 Rev Time 0.00
Received By jwitmer Date 2011-05-25 Time 13:31 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2011-07-27 Cont ID  
Sent By hmoser Date 2011-07-27 Time 09:03 Rev Time 0.00
Received By hmoser Date 2011-07-27 Time 06:56 Sent To  
Notes
2011-07-27 07:01:59PLAN PASS PROVISO
 IF THERE IS NO FIRE DAMPER INSTALLED IN EXISTING 12 X
 12 EXHAUST DUCT ONE MUST BE INSTALLED
 PER SECTION 607.5 FBC (M)
 SEPARATE PERMITS AND PLANS REQUIRED FOR HOOD AND ANSUL
 SYSTEM.
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2011-06-14 Cont ID  
Sent By hmoser Date 2011-06-14 Time 15:49 Rev Time 0.00
Received By hmoser Date 2011-06-07 Time 11:54 Sent To  
Notes
2011-06-14 15:59:33PLANS DENIED
 1) PAGE M1 A OF THE PLANS PROVIDE FIRE DAMPERS IN 12X14
 EXHAUST DUCT AND 12X12 EXHAUST DUCT .
 SECTION 607.5.1 2007 FBC (M)
 2) PROVIDE MANUFACTURE INSTALLATION INSTRUCTIONS FOR
 PIZZA OVEN.
 SECTION 106.1.1 2007 FBC.
 3) SEPARATE PLANS AND PERMIT REQUIRED FOR PIZZA OVEN,
 WALK IN COOLER, WALK IN FREEZER.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status P Date 2011-06-03 Cont ID  
Sent By lwagner Date 2011-06-03 Time 14:37 Rev Time 0.00
Received By lwagner Date 2011-06-03 Time 13:48 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2011-06-13 Cont ID  
Sent By aaponte Date 2011-06-13 Time 10:58 Rev Time 0.00
Received By aaponte Date 2011-06-13 Time 10:58 Sent To  
Notes
***NONE***