Plan Review Details - Permit 11050669
Plan Review Stops For Permit 11050669
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2011-08-15 Cont ID  
Sent By shill Date 2011-08-15 Time 14:12 Rev Time 0.00
Received By shill Date 2011-08-15 Time 14:12 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2011-06-07 Cont ID  
Sent By shill Date 2011-06-07 Time 09:00 Rev Time 0.00
Received By shill Date 2011-06-03 Time 13:12 Sent To  
Notes
2011-06-07 09:01:13PROVISOS
  
 1. SEE PLUMBING COMMENTS RE: ACCESSIBLE LAV FBC FIGURE
 11-30E.
  
 2. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIED FOR
 EXTERIOR COMPONENTS & CLADDING, FAC9N-3. EITHER PROVIDE
 AT TIME OF RESUBMITTAL FOR REVIEW OR SUBMIT AS A
 REVISION AFTER ISSUANCE.
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2011-08-15 Cont ID  
Sent By rlecky Date 2011-08-15 Time 14:47 Rev Time 0.00
Received By rlecky Date 2011-08-15 Time 14:19 Sent To  
Notes
2011-08-15 14:46:56 
 PROVISO:
  
 PROVIDE REVISED ELECTRICAL RISER PLAN. NEC 215.5
 RECEPTACLES IN BATHROOMS MUST BE GFCI PROTECTED. NEC
 210.8
 FIXTURES LOCATED IN THE TENT WASHING AREA MUST BE RATED
 FOR DAMP OR WET LOCATIONS. NEC 410.10
  
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2011-08-15 Cont ID  
Sent By rlecky Date 2011-08-15 Time 14:47 Rev Time 0.00
Received By rlecky Date 2011-08-12 Time 09:22 Sent To  
Notes
2011-08-12 09:29:03PROVIDE REVISED ELECTRICAL RISER PLAN. NEC 215.5
 RECEPTACLES IN BATHROOMS MUST BE GFCI PROTECTED. NEC
 210.8
 FIXTURES LOCATED IN THE TENT WASHING AREA MUST BE RATED
 FOR DAMP OR WET LOCATIONS. NEC 410.10
  
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2011-06-01 Cont ID  
Sent By rlecky Date 2011-06-01 Time 12:13 Rev Time 0.00
Received By rlecky Date 2011-06-01 Time 10:30 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2011-08-11 Cont ID  
Sent By wjolin Date 2011-08-11 Time 14:51 Rev Time 0.00
Received By wjolin Date 2011-08-11 Time 13:36 Sent To  
Notes
2011-08-11 14:17:215657 45TH STREET
 PERMIT #11050669
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 WAITING FOR SUBMISSION OF SHEET A-3.
  
 *****PROVISO*****
  
 PROPANE STORAGE
  
 PER NFPA 58, WHERE THE AGGREGATE QUANTITY OF PROPANE
 STORED IS IN EXCESS OF 720 LB,
 STORAGE LOCATIONS SHALL BE PROVIDED WITH AT LEAST ONE
 APPROVED PORTABLE FIRE EXTINGUISHER HAVING A MINIMUM
 CAPACITY OF 18 LB DRY CHEMICAL WITH B:C RATING. THE
 REQUIRED FIRE EXTINGUISHER SHALL BE LOCATED NOT MORE
 THAN 50 FT FROM THE STORAGE LOCATION.
  
 PER NFPA 58, PROPANE STORAGE OPEN TO THE PUBLIC SHALL
 BE PROTECTED WITH A LOCKABLE VENTILATED ENCLOSURE OF
 METAL EXTERIOR CONSTRUCTION.
  
 PROPANE STORAGE ENCLOSURE SHALL BE LABELED WITH DIAMOND
 PLACARD PER NFPA 704.
  
 POST PERMANENT, WEATHERPROOF NO SMOKING SIGNS.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  
  
  
  
  
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2011-06-03 Cont ID  
Sent By wjolin Date 2011-06-03 Time 16:30 Rev Time 0.00
Received By wjolin Date 2011-06-03 Time 14:12 Sent To  
Notes
2011-06-03 15:39:025657 45TH STREET
 PERMIT #11050669
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PROVIDE BUILDING ADDRESS VISIBLE FROM THE STREET.
 NUMBERS SHALL BE AT LEAST SIX-INCHES IN HEIGHT AND
 SHALL CONTRAST THE BACKGROUND (REFERENCE: SECTION
 10.12.1.2 OF THE FLORIDA FIRE PREVENTION CODE NFPA 1).
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE APPROVED AND SUBMITTED IN WRITING TO THE OFFICE OF
 THE FIRE MARSHAL.
  
 PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY
 RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING
 NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM
 WWW.KNOXBOX.COM.
  
 EACH NEW SMOKE OR FIRE-RATED WALL/PARTITION SHALL BE
 PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING READING
 FIRE/SMOKE BARRIER?PROTECT ALL OPENINGS. CHARACTERS
 SHALL BE AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN
 WIDTH. IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15
 FEET ON CENTER. REFERENCE SECTION 8.3.2.4 OF FLORIDA
 FIRE PREVENTION CODE NFPA 101
  
 PROVIDE PORTABLE FIRE EXTINGUISHER IN NEW
 SHOWROOM/OFFICE SPACE AS TRAVEL DISTANCE APPEARS TO
 EXCEED 75 FEET TO EXTINGUISHERS LOCATED IN WAREHOUSE
 AREA.
  
 PROVIDE SOME INFORMATION WITH REGARDS TO THE RACK
 STORAGE SUCH AS ESTIMATED STORAGE HEIGHT, STORAGE TYPE
 (PILED, PALLET, ETC.), COMMODITY ETC.
  
 PROVIDE ADDITIONAL INFORMATION FOR THE PROPANE STORAGE
 BUILDING. INDICATE CONTAINER SIZES, QUANTITIES ETC.
  
 SHEET E-300: REMOVE WAREHOUSE EXIT SIGNS LEADING BACK
 INTO NEW OFFICE SPACE BECUASE DOOR #10 AND #12 REQUIRE
 A CARD OR KEY PAD FOR ENTRY.
  
 SHEET F-100 DOES NOT PROVIDE ANY SCOPE OF WORK FOR THE
 WAREHOUSE/STORAGE AREA.
  
 SHEET P-302: UNDERGROUND LP STORAGE TANK SHALL CONFORM
 TO THE REQUIREMENTS OF THE FLORIDA FIRE PREVENTION
 CODE, NFPA 54 AND NFPA 58. INDICATE THE SIZE OF THE LP
 STORAGE TANK AND ANY INTENDED SAFEGUARDS.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2011-08-10 Cont ID  
Sent By lwagner Date 2011-08-10 Time 13:23 Rev Time 0.00
Received By lwagner Date 2011-08-10 Time 12:43 Sent To  
Notes
2011-08-10 13:24:24GAS APPLICATION - PERMIT REQUIRED

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-08-15 Cont ID  
Sent By shill Date 2011-08-15 Time 14:52 Rev Time 0.00
Received By shill Date 2011-08-05 Time 13:36 Sent To  
Notes
2011-08-05 14:14:48*****************EXPEDITED*******************
 B--6

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-06-09 Cont ID  
Sent By shill Date 2011-06-09 Time 08:39 Rev Time 0.00
Received By shill Date 2011-05-24 Time 12:05 Sent To  
Notes
2011-05-24 12:11:02*********************EXPEDITED************************
 B--1

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2011-06-09 Cont ID  
Sent By shill Date 2011-06-09 Time 08:15 Rev Time 0.00
Received By shill Date 2011-06-09 Time 08:15 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2011-08-15 Cont ID  
Sent By shill Date 2011-08-15 Time 14:52 Rev Time 0.00
Received By hmoser Date 2011-08-15 Time 14:18 Sent To  
Notes
2011-08-15 14:52:28OK PER HM

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2011-06-09 Cont ID  
Sent By shill Date 2011-06-09 Time 08:16 Rev Time 0.00
Received By shill Date 2011-06-09 Time 08:16 Sent To  
Notes
2011-06-09 08:34:30****CORRECTIONS****
  
 1. PROVIDE THE ROOF STAND PRODUCT APPROVAL, FAC9N-3.
  
 2. SPECIFY THE FOLLOWING BOLT SIZES (DIAMETER, LENGTH,
 TYPE) FOR DETAIL CONDENSING UNIT MOUNTING DETAIL ON
 SHEET M 401, IF INFORMATION IS NOT INCLUDED IN THE ROOF
 STAND PRODUCT APPROVAL:
  
 STAND TO CONCRETE ROOF
 ANGLE TO STAND
  
 THIS REVIEW CAN BE PASSED WITH PROVISO (REVISION
 REQUIRED, WITH ADDITIONAL FEES) UPON REQUEST FROM THE
 ENGINEER.
  
 HAROLD MOSER, MECHANICAL PLANS EXAMINER
 561-805-6732
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2011-08-10 Cont ID  
Sent By lwagner Date 2011-08-10 Time 13:23 Rev Time 0.00
Received By lwagner Date 2011-08-10 Time 12:42 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2011-06-02 Cont ID  
Sent By lwagner Date 2011-06-02 Time 12:45 Rev Time 0.00
Received By lwagner Date 2011-06-01 Time 12:49 Sent To  
Notes
2011-06-01 14:48:38FBC PLUMBING 2007 REVIEW #1
 DENIED:
  
 1. SHEET A-6 ADA STALL - LAVATORY WOULD BE 1'-3" FROM
 SIDE WALL TO CENTER OF LAV IN 7'-1" STALL TO COMPLY
 WITH
 11-4.17 TOILET STALLS. FIGURE 30(E)
  
 2. SHEET P-200 SHOWS A TRENCH DRAIN ATTACHED TO THE
 GREASE LINE AND SHEET P-300 SHOWS IT ATTACHED TO THE
 OIL AND SAND INTERCEPTOR.
  
 3. SHEET P-200 + P-300 THE MOP SINK IS SHOWN CONNECTING
 TO THE W.C. WET VENT. CONNECTING THE STANDARD LAVS TO
 THE WC WOULD COMPLY WITH 909.1
 909.1 HORIZONTAL WET VENT PERMITTED. ANY COMBINATION OF
 FIXTURES WITHIN TWO BATHROOM GROUPS LOCATED ON THE SAME
 FLOOR LEVEL IS PERMITTED TO BE VENTED BY A HORIZONTAL
 WET VENT. THE WET VENT SHALL BE CONSIDERED THE VENT FOR
 THE FIXTURES AND SHALL EXTEND FROM THE CONNECTION OF
 THE DRY VENT ALONG THE DIRECTION OF THE FLOW IN THE
 DRAIN PIPE TO THE MOST DOWNSTREAM FIXTURE DRAIN
 CONNECTION TO THE HORIZONTAL BRANCH DRAIN. ONLY THE
 FIXTURES WITHIN THE BATHROOM GROUPS SHALL CONNECT TO
 THE WET-VENTED HORIZONTAL BRANCH DRAIN. ANY ADDITIONAL
 FIXTURES SHALL DISCHARGE DOWNSTREAM OF THE HORIZONTAL
 WET VENT.
  
 4. SHEET P-400 GREASE TRAP DETAIL IS MISSING THE
 REQUIRED INLET DROP.
 1003.5.3 INLET AND OUTLET PIPING. INLET PIPING SHALL
 ENTER AT 2 1/2 INCHES (64 MM) ABOVE THE LIQUID LEVEL.
 INLET PIPING SHALL CONNECT TO A TEE, SWEEP OR BAFFLE,
 WHICH SHALL EXTEND TO 24 INCHES (610 MM) BELOW THE
 WATER LEVEL.
  
 5. 180 DEGREE WATER IS SHOWN TO DISH WASHERS.
 701.7 CONNECTIONS. DIRECT CONNECTION OF A STEAM
 EXHAUST, BLOWOFF OR DRIP PIPE SHALL NOT BE MADE WITH
 THE BUILDING DRAINAGE SYSTEM. WASTEWATER WHEN
 DISCHARGED INTO THE BUILDING DRAINAGE SYSTEM SHALL BE
 AT A TEMPERATURE NOT HIGHER THAN 140 DEGREE F (60?C).
 WHEN HIGHER TEMPERATURES EXIST, APPROVED COOLING
 METHODS SHALL BE PROVIDED.
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  
  
  
  
  

Review Stop Z ZONING
Rev No 3 Status P Date 2011-08-15 Cont ID  
Sent By shill Date 2011-08-15 Time 15:52 Rev Time 1.00
Received By eschneid Date 2011-08-15 Time 15:52 Sent To  
Notes
2011-08-16 12:12:18PASSED W/PROVISOS
  
 1) SEE REDLINES TO SHEETS A-1, M-210, AND P-200 SHOWS
 THE INSTALLATION OF A NEW A/C UNIT WHICH WAS NOT SHOWN
 ON THE ORIGINAL SUBMITTAL.
  
 2) THERE ARE EXISTING TREES ALONG THE WEST SIDE OF THE
 BUILDING. IN ORDER TO PREVENT LONG TERM CONFLICT WITH
 THE TREE GROWTH AND THE A/C LOCATION, THE A/C SHALL BE
 INSTALLED CENTERED BETWEEN THE EXISTING TREES.
  
 3) GROUND MOUNTED A/C UNIT SHALL BE SCREENED ON THE
 45TH STREET SIDE WITH A HEDGE.
  
 4) THE GAS LINES TO THE UNDERGROUND TANKS SHALL BE
 INSTALLED TO AVOID THE EXISTING TREES ALONG THE WESTERN
 SIDE OF THE BUILDING.
  
 5) A PERMIT IS REQUIRED FOR THE NEW STORAGE ENCLOSURE
 PAD AND PVC FENCE.
  
 6) THE NEW TREE IN FRONT OF THE BUILDING (BY NEW ENTRY
 LOCATION) AND THE SCREEN HEDGES REQUIRE A LANDSCAPE
 PERMIT.
  
 7) PRIOR TO THE FINAL INSPECTION FOR THIS PERMIT, THE
 LANDSCAPE SHALL BE INSTALLED (AFTER ISSUANCE OF A
 PERMIT) AND PASS INSPECTION.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  

Review Stop Z ZONING
Rev No 2 Status F Date 2011-08-11 Cont ID  
Sent By eschneid Date 2011-08-11 Time 11:53 Rev Time 1.50
Received By eschneid Date 2011-08-11 Time 11:53 Sent To  
Notes
2011-08-11 12:06:57FAILED
  
 SPOKE WITH MIGUEL FROM CORRALES GROUP ARCHITECTS WHO
 PUT THE PLANS TOGETHER. IF ZONING IS ONLY REVIEWER TO
 FAIL THE RESUBMITTAL, THEN COMMENTS BELOW WILL BE ADDED
 AS REDLINES. IF OTHER DISCIPLINE FAILS THE PERMIT THEN
 REVISED SHEETS ARE REQUIRED TO ADDRESS COMMENTS.
  
 1) SHEET M-210 SHOWS THE INSTALLATION OF A NEW A/C UNIT
 WHICH WAS NOT SHOWN ON THE ORIGINAL SUBMITTAL.
  
 A. THE A/C UNIT SHALL BE SHOWN ON SHEET A-1.
 B. THE A/C NEEDS TO BE SCREENED ON THE 45TH STREET SIDE
 WITH A HEDGE. THE HEDGE SHALL BE SHOWN ON SHEET A-1.
 C. THERE ARE EXISTING TREES ALONG THE WEST SIDE OF THE
 BUILDING. BY SCALING THE LANDSCAPE AND THE MECHANICAL
 PLANS, THE A/C APPEARS TO AVOID THE TREES. IN ORDER TO
 PREVENT LONG TERM CONFLICT WITH THE TREE GROWTH AND THE
 A/C LOCATION, THE A/C SHALL BE INSTALLED CENTERED
 BETWEEN THE EXISTING TREES.
  
 2) SHEET P-200 SHOWS THE PROPOSED LOCATION FOR THE NEW
 UNDERGROUND TANK (INSTALLATION ON PERMIT 11080160. THE
 PROPOSED TANK LOCATION IS UNDER AN EXISTING OAK TREE.
 THE TANK LOCATION SHALL BE SHOWN CORRECTLY.
  
 3) THE GAS LINES TO THE UNDERGROUND TANKS SHALL BE
 INSTALLED TO AVOID THE EXISTING TREES ALONG THE WESTERN
 SIDE OF THE BUILDING.
  
 4) A PERMIT IS REQUIRED FOR THE NEW STORAGE ENCLOSURE
 PAD AND PVC FENCE.
  
 5) THE NEW TREE IN FRONT OF THE BUILDING (BY NEW ENTRY
 LOCATION) AND THE SCREEN HEDGES REQUIRE A LANDSCAPE
 PERMIT.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  

Review Stop Z ZONING
Rev No 1 Status F Date 2011-05-31 Cont ID  
Sent By eschneid Date 2011-05-31 Time 13:12 Rev Time 1.75
Received By eschneid Date 2011-05-31 Time 13:11 Sent To  
Notes
2011-05-31 15:27:40PERMIT NO. 11050669 PANACHE
  
 FAILED
  
 PROVIDE RESPONSES IN WRITING.
  
 1) ORDINANCE NO. 3987-06 REQUIRES THE FOLLOWING
 INFORMATION TO BE PROVIDED CONCURRENT WITH THE BUILDING
 PERMIT APPLICATION:
  
 A. A USE CHART SHALL BE SUBMITTED TO THE PLANNING AND
 ZONING AND CONSTRUCTION SERVICES DEPARTMENTS CONCURRENT
 WITH ALL BUILDING PERMIT AND/OR OCCUPATIONAL LICENSE
 APPLICATIONS STATING THE SQUARE FOOTAGE DEVOTED TO THE
 USES WITHIN BUILDINGS 1, 2 AND 3. THE SPECIFIC SQUARE
 FOOTAGE USE WITHIN EACH BUILDING MAY NOT EXCEED THE
 ALLOWANCES OUTLINED IN THE BUILDING USE SQUARE FOOTAGE
 TABLE (BELOW FOR BUILDING #1), UNLESS THE PROPERTY
 OWNER PROVIDES A TRAFFIC EQUIVALENCY STATEMENT,
 PREPARED BY A LICENSED TRAFFIC ENGINEER, DEMONSTRATING
 THAT THE APPROVED TRAFFIC CONCURRENCY FOR THE PROJECT
 IS NOT EXCEEDED.
  
 USE MAXIMUM SQUARE FOOTAGE
 OFFICE/SHOWROOM 13,607
 INDUSTRIAL 8,164
 WHOLESALE 8,164
 WAREHOUSE 24,957
 STORAGE MEZZANINE 13,760
  
 B. A TRAFFIC STATEMENT, PREPARED BY A LICENSED TRAFFIC
 ENGINEER, SHALL BE SUBMITTED TO THE PLANNING AND ZONING
 AND CONSTRUCTION SERVICES DEPARTMENTS CONCURRENT WITH
 ALL BUILDING PERMIT APPLICATIONS OUTLINING THE NUMBER
 OF DAILY TRIPS, AM TRIPS AND PM TRIPS GENERATED FOR
 EACH USE AND ITS SQUARE FOOTAGE FOR EACH BUILDING. THE
 TRAFFIC STATEMENT SHALL INCLUDE THE TRIPS ASSOCIATED
 WITH THE SPECIFIC USE AND A CUMULATIVE TABLE FOR ALL OF
 THE USES APPROVED IN THE PREMIER PARK OF COMMERCE CPD.
  
 2) THE PLANS SHOW A NEW ENTRY DOOR ON THE SOUTH FACADE
 OF THE BUILDING WITH A NEW WALKWAY LEADING TO THE
 EXISTING SIDEWALK AND A NEW STORAGE ENCLOSURE WITH
 SIDEWALK ON THE NORTHWEST CORNER OF THE BUILDING. THESE
 MODIFICATIONS TO THE SITE PLAN, THE LANDSCAPE PLAN
 (PALM TREES APPROVED AS PART OF THE ORIGINAL APPROVAL
 ARE LOCATED IN FRONT OF THE NEW DOOR), AND THE
 ELEVATIONS REQUIRE THE APPROVAL OF A MINOR PLANNED
 DEVELOPMENT AMENDMENT BY THE PLANNING AND ZONING
 DEPARTMENT PRIOR TO ZONING APPROVAL OF THE BUILDING
 PERMIT.
  
 3) PROVIDE CROSS SECTION/ELEVATION DRAWINGS SHOWING THE
 HEIGHT OF ALL OF THE NEW ROOFTOP MECHANICAL EQUIPMENT
 AND THE HEIGHT OF THE PARAPETS. THE MECHANICAL
 EQUIPMENT SHALL BE SCREENED.
  
 4) SHEET A-1 MENTIONS A DRYER VENT, WHICH APPEARS TO BE
 PROPOSED ON THE FRONT FACADE OF THE BUILDING. GREAT
 CARE WAS TAKEN IN THE DESIGN OF THE FRONT (SOUTH)
 FACADE OF BUILDING #1. A DRYER VENT IS NOT APPROPRIATE
 ON THIS FACADE, AND WILL NOT BE SUPPORTED BY STAFF.
 SUGGEST VENTING THE DRYER THROUGH THE ROOF.
  
 5) THE CURRENTLY INSTALLED LANDSCAPE IS REQUIRED TO BE
 MODIFIED AS PART OF THE NEW DOOR AND WALKWAY
 INSTALLATION. STAFF SUGGESTS PUTTING A GROUPING OF 3
 PALMS ON EITHER SIDE OF THE NEW DOOR IN ORDER TO
 MAINTAIN CODE COMPLIANCE. ANY PALMS THAT CAN REMAIN IN
 PLACE SHOULD DO SO. PLEASE NOTE THAT PALM RELOCATION
 REQUIRES A TREE ALTERATION PERMIT FROM THE PLANNING &
 ZONING DEPARTMENT.
  
 6) THE NEW STORAGE AREA REQUIRES A SEPARATE PERMIT. THE
 NEW HEDGE MATERIAL MAY BE INCLUDED WITH THAT PERMIT.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  
  