Review Stop E ELECTRICAL
Rev No 2 Status P Date 2011-05-27 Cont ID  
Sent By rlecky Date 2011-05-27 Time 15:24 Rev Time 0.00
Received By rlecky Date 2011-05-27 Time 15:24 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2011-05-23 Cont ID  
Sent By rlecky Date 2011-05-23 Time 10:51 Rev Time 0.00
Received By rlecky Date 2011-05-23 Time 10:33 Sent To  
Notes
2011-05-23 10:51:28PROVIDE AN ELECTRIC SERVICE RISER PLAN FOR NEW SERVICE.
 SHOW GROUNDING, WIRE SIZE AND MAIN DISCONNECT. INDICATE
 LOCATION OF PANEL BOARD. PROVIDE A PANEL SCHEDULE
 SHOWING NEW AND EXISTING LOADS. NEC 215.5
 REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE DETECTORS IF THEY DO NOT
 ALREADY EXIST WITHIN THE RESIDENCE. IF THE RESIDENCE
 HAS GAS APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE
 A CARBON MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET
 OF EACH ROOM USED FOR SLEEPING. FBC R313
 NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11
 PROVIDE AN INTERSYSTEM BONDING STRIP AT THE SERVICE
 GROUND. NEC 250.94
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 561-805-6718
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-05-23 Cont ID  
Sent By rlecky Date 2011-05-23 Time 10:51 Rev Time 0.00
Received By rlecky Date 2011-05-23 Time 10:51 Sent To  
Notes
***NONE***