Plan Review Details - Permit 11050621
| Plan Review Stops For Permit 11050621 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2011-05-27 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2011-05-27 |
Time |
15:24 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2011-05-27 |
Time |
15:24 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2011-05-23 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2011-05-23 |
Time |
10:51 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2011-05-23 |
Time |
10:33 |
Sent To |
|
|
| Notes |
| 2011-05-23 10:51:28 | PROVIDE AN ELECTRIC SERVICE RISER PLAN FOR NEW SERVICE. | | | SHOW GROUNDING, WIRE SIZE AND MAIN DISCONNECT. INDICATE | | | LOCATION OF PANEL BOARD. PROVIDE A PANEL SCHEDULE | | | SHOWING NEW AND EXISTING LOADS. NEC 215.5 | | | REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO | | | INCLUDE INTERCONNECTED SMOKE DETECTORS IF THEY DO NOT | | | ALREADY EXIST WITHIN THE RESIDENCE. IF THE RESIDENCE | | | HAS GAS APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE | | | A CARBON MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET | | | OF EACH ROOM USED FOR SLEEPING. FBC R313 | | | NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11 | | | PROVIDE AN INTERSYSTEM BONDING STRIP AT THE SERVICE | | | GROUND. NEC 250.94 | | | | | | ROBERT LECKY | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2011-05-23 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2011-05-23 |
Time |
10:51 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2011-05-23 |
Time |
10:51 |
Sent To |
|
|
| Notes |
|
|
|