Plan Review Details - Permit 11050596
Plan Review Stops For Permit 11050596
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2012-06-25 Cont ID  
Sent By jwitmer Date 2012-06-25 Time 11:01 Rev Time 0.00
Received By jwitmer Date 2012-06-25 Time 10:25 Sent To  
Notes
2012-06-25 16:51:38BUILDING PLAN REVIEW
 PERMIT: 11050596
 ADD: 114 S OLIVE AVE
 CONT: LAKESIDE CONTRACTING CORP
 TEL: (954)553-8398
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 2007/09 FLORIDA EXISTING BUILDING CODE W/ SUPPLEMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 4TH REVIEW
 JUNE 25,/ 2012
 ACTION: DENIED
  
 NOTE: WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY
 MAKING TWO COMPLETE SETS OF PLANS. PLANS WERE SUBMITTED
 IN INCOMPLETE SETS MAKING A PLAN REVIEW OF 4 PARTIAL
 SETS VERY TIME CONSUMING AND WHAT STILL LOOKS OR
 APPEARS TO BE INCOMPLETE PLANS! A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 1) COMPLIED.
  
 2) 4TH REQUEST, NOT FOUND ON EITHER THE COVER SHEET NOR
 LS-01. WHAT WAS THE LAST KNOWN USE FOR THIS BUILDING,
 IS THIS A CHANGE OF OCCUPANCY? THE PLANS DO NOT
 REFERENCE THE FLORIDA EXISTING BUILDING CODE AND TO
 WHICH TYPE OF COMPLIANCE METHOD THE PLANS WERE DESIGNED
 TOO? FL EXST BLDG CODE 101.5 (.1-.3).RESPONCE INDICATES
 THE LAST KNOWN USE A RESTARAUNT. THE PALM BEACH COUNTY
 IMPACT FEE OFFICE INDICATES THE LAST KNOWN USE TO BE A
 BUSINESS OFFICE NOT A RESTARAUNT, THIS TRIGGERS THE
 2007 EXISTING BUILDING CODE CHAPTER 9 SECTION 901.3AND
 THE PROVISIONS OF 902 THROUGH 912 OF THE EXISTING
 BUILDING CODE SHALL APPLY.
  
 3A) FOURTH REQUEST, PLEASE REFER TO THE 2007 FBC-B FOR
 BUILDING TYPE, NOTE THE 2007FBC-B 603.1.3 REQUIRES ALL
 ROOF CONSTRUCTION GIRDERS, JOIST, TRUSSES AND DECKING
 ARE TO BE FIRE RETARDANT TREATED WOOD. SHEET S-5
 INDICATES THE EXISTING 2X6 ROOF FRAMING, IS THE
 EXISTING STRUCTURE TRULY A BUILDING TYPE II-B? PLEASE
 NOTE THE NEW FRAMING MEMBERS LOCATED ON SHEET S-5 DO
 NOT INDICATE THE USE OF FIRE RETARDANT TREATED WOOD.
 SHEET INDICATES THE USE OF EXISTING 2X6 ROOF JOISST AND
 DECKING TO REMAIN. HOW WILL THIS ISSUE BE
 RESOLVED??????? PLANS INDICATE THIS IS A TYPE II-B
 CONSTRUCTION.
  
 3B) COMPLIED.
  
 4-7) COMPLIED.
  
 8) SEMI-COMPLIED, RE
  
 THE RESPONCE LETTER INDICATES THE ELEVATOR TO BE A
 SCHINDLER 3300 MRL ELECTRIC TRACTION ELEVATOR, PLEASE
 PROVIDE DOCUMENTATION THIS ELEVATOR MEETS THE
 REQUIREMENTS OF 3001.2 REFERENCED STANDARDS AND
 ACCESSIBILITY REQUIREMENTS. FORMER COMMENT .PLEASE
 INDICATE WHERE THE ELEVATOR HYDROLIC PUMP (MACHINE
 ROOM) WILL BE LOCATED. . PLEASE PROVIDE INFORMATION AS
 TO SHEET A2-01 & LS-01 WHAT IS THE ROOM # 119 USED FOR
 IS THIS THE ELEVATOR MACHINE ROOM? IF SO IT NEEDS TO BE
 RATED AS DOES THE DOOR.
  
  
 THIS REVIEW WILL CONTINUE TUESDAY 6/26/2012
  
  
 9) 4TH REQUEST. SHEET A2-01 INDICATES NEW RAISED
 PLATFORM FLOORING PLEASE PROVIDE SQUARE FOOTAGE OF
 RAISED PLATFORM FLOORING, PLEASE REVIEW SECTION 2007/09
 FBC-B 410.4 FIRE RETARDANT TREATED WOOD REQUIREMENT.
 THE STRUCTURAL S-4 DATED 01-04-12 STILL INDICATES WOOD
 FRAMING THE NEW S-2 05/04/12 INDICATES STEEL JOIST,
 STEEL PAN AND CONCRETE
 FLOOR FINISH PLEASE REVIEW ALL SHEETS FOR CODE
 COMPLIANCE.
  
 10) 4TH REQUEST. STRUCTURAL PLANS SUBMITTED S-2 DATED
 05-04-12 STILL HAS A DISCREPANCY AS TO WHAT APPEARS TO
 BE A DOORWAY THAT WOULD LED INTO THE LADIES RESTROOM
 FROM THE STAIR.DISCREPANCY IN PLANS. 106.1.2 ADDITIONAL
 INFORMATION REQUIRED.
  
 11) 4TH REQUEST ROOF HATCH PLEASE BE AWARE OF
 ADDITIONAL INFORMATION REQUIRED, SHEET A2.04 INDICATES
 THE USE OF A NEW ROOF HATCH ANS DETAIL TO BE LOCATED ON
 SHEET DETAIL # 11 A7.02. MISSING SHEET A7.02. PLEASE
 SEE FBC-B 1013.5. & 2007/09 MECH CODE 304.10 FOR GUARD
 REQUIREMENTS WHEN UNITS ARE WITHIN 10'-0" OF THE ROOF
 EDGE.
  
 ***** NOTED RESPONCE TO KEEP EQUIPMENT 10'-0" AWAY FROM
 EDGE OF ROOF.*****
  
 11A) GUARDS SHALL BE PROVIDED WHERE APPLIANCES,
 EQUIPMENT, FANS, ROOF HATCH OPENINGS OR OTHER
 COMPONENTS THAT REQUIRE SERVICE ARE LOCATED WITHIN 10
 FEET (3048 MM) OF A ROOF EDGE OR OPEN SIDE OF A WALKING
 SURFACE AND SUCH EDGE OR OPEN SIDE IS LOCATED MORE THAN
 30 INCHES (762 MM) ABOVE THE FLOOR, ROOF OR GRADE
 BELOW. THE GUARD SHALL BE CONSTRUCTED SO AS TO PREVENT
 THE PASSAGE OF A 21-INCH-DIAMETER (533 MM) SPHERE. THE
 GUARD SHALL EXTEND NOT LESS THAN 30 INCHES (762 MM)
 BEYOND EACH END OF SUCH APPLIANCE, EQUIPMENT, FAN OR
 COMPONENT.
  
 11B) 1013.6 ROOF ACCESS. GUARDS SHALL BE PROVIDED WHERE
 THE ROOF HATCH OPENING IS LOCATED WITHIN 10 FEET (3048
 MM) OF A ROOF EDGE OR OPEN SIDE OF A WALKING SURFACE
 AND SUCH EDGE OR OPEN SIDE IS LOCATED MORE THAN 30
 INCHES (762 MM) ABOVE THE FLOOR, ROOF OR GRADE BELOW.
 THE GUARD SHALL BE CONSTRUCTED SO AS TO PREVENT THE
 PASSAGE OF A 21-INCH-DIAMETER (533 MM) SPHERE.
  
  
 12) COMPLIED.
  
 13) 4TH REQUEST. FL BLD CODE 1609.6.2.2 COMPONENTS &
 CLADDING, PROVIDE 2 COPIES, 3 IF THRESHOLD OR RESIDENT
 INSPECTOR OF PRODUCT TESTING REPORTS, MISSING REPORTS
 ARE AS FOLLOWS:
 13A) WINDOWS
 13B) EXTERIOR DOORS
 13C) ROOF HATCH
 13D) A/C PRE-MANUFACTURED STANDS
  
 14) 4TH REQUEST. 106.3.3 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9B-72
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 15) COMPLIED.
  
 16)4TH REQUEST, SHEET A-2.01 THE PLANS DO NOT PROVIDE
 ELEVATION CHANGE FROM THE CONCRETE DECK TO FINISHED
 MAIN SEATING AREA NOT THE VIP PLATFORM. FBC-B 1003.5.2.
 NOR IS THERE A CUT SECTION THROUGH STAIRS FOR ACCESS TO
 PLATFROM AREAS. 2007 FBC 1009.3. RISE & RUN.
  
 17) 4TH REQUEST. RESPONCE COMMENTS INDICATE STAIR
 DETAILS FOR STAIR # 2 ARE TO BE FOUND ON A4-03, A4-04
 AND DETAIL #4 ON SHEET A4-06.
 THE NUMBERED SHEETS STATED IN RESPONCE WERE NOT FOUND
 IN THE FOURTH SUBMITAL, NOR ON SHEETS DATED 2/16/12 NOR
 1/06/12/
 SHEET A-5.02 STAIRWELL # 2. NO STRUCTURAL PLANS WERE
 SUBMITTED THE TYPE OF MATEIAL FOR STAIR CONSTRUCTION IS
 NOT PROVIDED 2007/09 FBC-B 1009.5 NOR IS THE RISE NOR
 RUN OF THE STAIRSFBC-B 1009.3.
  
 18) 4TH REVIEW NO NEW LS02 SHEETS SUBMITTED . SHEET
 LS-02 MEZZANINE RESTROOMS PLEASE SEE 11-4,11-4.1.3(11)
 IF TOILET ROOMS ARE PROVIDED, THEN EACH PUBLIC & COMMON
 USE TOILET ROOM SHALL COMPLY WITH 11-4.22.
 PLEASE REVIEW 11-4.22(1) DOORS SHALL NOT SWING INTO THE
 CLEAR FLOOR SPACE REQUIRED FOR ANY FIXTURE SEE 202 &
 205 RESTROOM STALL DOOR SWINGS INTO THE REQUIRED CLEAR
 FLOOR SPACE FOR THE LAVATORY.
  
 19)4TH REVIEW 2007 EXISTING BUILDING CODE LEVEL II
 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
 LS-01 THE VIP PLATFORM #108 & DANCE FLOOR # 107 WILL
 NEED TO COMPLY WITH VERTICAL ACCESSIBILITY REQUIREMENTS
 11-4.1.3(5).
  
 20) COMPLIED.
  
 21)4TH REVIEW, THIS COMMENT MAY OR MAY NOT BE RELEVENT.
 COMMENTS RESPONCE SHEET INDICATES THE USE OF A
 SCHINDLERE 3300 MRL ELEVATOR, TO DATE NO PRODUCT SPECS
 HAVE BEEN SUBMITTED FOR REVIEW.
 SHEET A4-04 & S-7 DETAIL #2 THE ELEVATOR SHAFT DETAIL
 IS MISSING THE SUMP PUMP DETAIL 09/A6.121 DETAIL NOT
 PROVIDED.
  
 22) NOT REQUIRED.
 -------------------------------------------------------
 ----------
  
 23) 4TH REQUEST. THERE IS A NEW 8X11 INTRODUCTORY
 OVERVIEW STATEMENT SHEET, INCLUDED IN THE PERMIT
 PACKAGE, AUTHOR UNKNOWN BUT THE COMMENT INDICATING THAT
 ALL INTERIOR FINISHES AND FINISH MATERIALS WILL BE
 SELECTED BY OWNER AND UNDER A SEPERATE CONTRACT SAID
 MATERIALS INCLUDE ALL FLOOR FINISHES, CEILING MATERIALS
 & FINISHES ALL WINDOW AND DOOR FINISHES, AND WALL
 SURFACE FINISHES.
  
 WITH THE ABOVE STATEMENT THE PERMIT CAN BE ISSUED AS A
 PROVISO, BUT A SECONDARY PERMIT WILL NEED TO BE APPLIED
 FOR BEFORE A C.O. WILL BE ISSUED.
 THE ARCHITECT OF RECORD SHOULD HAVE A STATEMENT ON THE
 PLANS INDICATING THAT FINISHES TO BE UNDER A SEPERATE
 PERMIT. 106.3.5.1.1. COMMERCIAL PLAN REVIEW CRITERIA
 WOULD REQUIRE THIS INFORMATION BEFORE A PERMIT COULD BE
 ISSUED, THAT WOULD BE THE REASON IT WOULD BE EXEMPTED
 FROM THIS PERMIT.
  
 24) THE NEW A SHEETS ARE SIGNED AND SEALED BUT NOT
 DATED.
 61G1-16.004 FL. ADMIN. CODE. PLANS PREPARED BY A
 REGISTERED ARCHITECT SHALL INCLUDE A TITLE BLOCK WHICH
 MUST:
 X= MISSING INFORMATION
 X - STATE THE FIRM NAME, ADDRESS AND TELEPHONE NUMBER
 X - STATE THE FIRM LICENSE NUMBER
 - STATE PROJECT NAME OR IDENTIFICATION
 - STATE DATE PREPARED
 X - INCLUDE AN ORIGINAL SIGNATURE AND DATED SEALED
 INCLUDE THE PRINTED NAME OF THE ARCHITECT SEALING THE
 PLANS
  
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER C.B.O.
 COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: (561)805-6715
 FAX:(561)805-6731
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2012-04-13 Cont ID  
Sent By jwitmer Date 2012-04-13 Time 10:01 Rev Time 0.00
Received By jwitmer Date 2012-04-13 Time 07:37 Sent To  
Notes
2012-04-13 10:02:36BUILDING PLAN REVIEW
 PERMIT: 11050596
 ADD: 114 S OLIVE AVE
 CONT: LAKESIDE CONTRACTING CORP
 TEL: (954)553-8398
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 2007/09 FLORIDA EXISTING BUILDING CODE W/ SUPPLEMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 APRIL 13,/ 2012
 ACTION: DENIED
  
 NOTE: THERE ARE NO STRUCTURAL SHEETS IN EITHER SET OF
 PLANS!!!!! NO S SHEETS!!!!
  
 1) COMPLIED.
  
 2) 3RD REQUEST, NOT FOUND ON EITHER THECOVER SHEET NOR
 LS-01. WHAT WAS THE LAST KNOWN USE FOR THIS BUILDING,
 IS THIS A CHANGE OF OCCUPANCY? THE PLANS DO NOT
 REFERENCE THE FLORIDA EXISTING BUILDING CODE AND TO
 WHICH TYPE OF COMPLIANCE METHOD THE PLANS WERE DESIGNED
 TOO? FL EXST BLDG CODE 101.5 (.1-.3).
  
 3A) THIRD REQUEST, NO STRUCTURAL SHEETS WERE SUBMITTED
 FOR THIS REVIEW. PLEASE REFER TO THE 2007 FBC-B FOR
 BUILDING TYPE, NOTE THE 2007FBC-B 603.1.3 REQUIRES ALL
 ROOF CONSTRUCTION GIRDERS, JOIST, TRUSSES AND DECKING
 ARE TO BE FIRE RETARDANT TREATED WOOD. SHEET S-5
 INDICATES THE EXISTING 2X6 ROOF FRAMING, IS THE
 EXISTING STRUCTURE TRULY A BUILDING TYPE II-B? PLEASE
 NOTE THE NEW FRAMING MEMBERS LOCATED ON SHEET S-5 DO
 NOT INDICATE THE USE OF FIRE RETARDANT TREATED WOOD.
 SHEET INDICATES THE USE OF EXISTING 2X6 ROOF JOISST AND
 DECKING TO REMAIN. HOW WILL THIS ISSUE BE
 RESOLVED??????? THIS IS A TYPE II-B CONSTRUCTION.
  
 3B) COMPLIED.
  
 4-7) COMPLIED.
  
 8) SEMI-COMPLIED, PLEASE INDICATE WHERE THE ELEVATOR
 HYDROLIC PUMP (MACHINE ROOM) WILL BE LOCATED. . PLEASE
 PROVIDE INFORMATION AS TO SHEET A2-01 & LS-01 WHAT IS
 THE ROOM # 119 USED FOR IS THIS THE ELEVATOR MACHINE
 ROOM? IF SO IT NEEDS TO BE RATED AS DOES THE DOOR.
  
 9) 3RD REQUEST. SHEET A2-01 INDICATES NEW RAISED
 PLATFORM FLOORING PLEASE PROVIDE SQUARE FOOTAGE OF
 RAISED PLATFORM FLOORING, PLEASE REVIEW SECTION 2007/09
 FBC-B 410.4 FIRE RETARDANT TREATED WOOD REQUIREMENT.
 SECTION 410.4 ONLY ALLOWS 1/3RD OFTHE FLOOR AREA WITHIN
 A ROOM TO BE ELEVATED. SHEET LS-01 THE ROOM SIZE
 TABULATION IS NOT CLOSE IN AREAS MISSING ONE MENS
 RESTROOM AND IT APPEARS THAT FOR ONE OF THE LADIES
 RESTROOM THE UNISEX RESTROOM WAS PUT IN TWICE AS A
 LADIES RESTROOM.
  
 10) 3RD REQUEST. NO STRUCTURAL PLANS WERE BROUGHT IN AT
 THIS TIME TO VERIFY.IT APPEARS THERE MAY BE A
 DISCREPANCY BETWEEN A2-01 & S-2, ON SHEET S-2 IT
 APPEARS THERE IS A DOORWAY THAT LEADS FROM THE RAISED
 DECK IN TO THE STAIRWELL WITH NO LANDING OR STAIRS.
 106.1.2 ADDITIONAL INFORMATION REQUIRED.
  
 11) ROOF HATCH PLEASE BE AWARE OF ADDITIONAL
 INFORMATION REQUIRED, SHEET A2.04 INDICATES THE USE OF
 A NEW ROOF HATCH ANS DEETAIL TO BE LOCATED ON SHEET
 DETAIL # 11 A7.02. MISSING SHEET A7.02. PLEASE SEE
 FBC-B 1013.5. & 2007/09 MECH CODE 304.10 FOR GUARD
 REQUIREMENTS WHEN UNITS ARE WITHIN 10'-0" OF THE ROOF
 EDGE.
  
 11A) GUARDS SHALL BE PROVIDED WHERE APPLIANCES,
 EQUIPMENT, FANS, ROOF HATCH OPENINGS OR OTHER
 COMPONENTS THAT REQUIRE SERVICE ARE LOCATED WITHIN 10
 FEET (3048 MM) OF A ROOF EDGE OR OPEN SIDE OF A WALKING
 SURFACE AND SUCH EDGE OR OPEN SIDE IS LOCATED MORE THAN
 30 INCHES (762 MM) ABOVE THE FLOOR, ROOF OR GRADE
 BELOW. THE GUARD SHALL BE CONSTRUCTED SO AS TO PREVENT
 THE PASSAGE OF A 21-INCH-DIAMETER (533 MM) SPHERE. THE
 GUARD SHALL EXTEND NOT LESS THAN 30 INCHES (762 MM)
 BEYOND EACH END OF SUCH APPLIANCE, EQUIPMENT, FAN OR
 COMPONENT.
  
 11B) 1013.6 ROOF ACCESS. GUARDS SHALL BE PROVIDED WHERE
 THE ROOF HATCH OPENING IS LOCATED WITHIN 10 FEET (3048
 MM) OF A ROOF EDGE OR OPEN SIDE OF A WALKING SURFACE
 AND SUCH EDGE OR OPEN SIDE IS LOCATED MORE THAN 30
 INCHES (762 MM) ABOVE THE FLOOR, ROOF OR GRADE BELOW.
 THE GUARD SHALL BE CONSTRUCTED SO AS TO PREVENT THE
 PASSAGE OF A 21-INCH-DIAMETER (533 MM) SPHERE.
  
  
 12) COMPLIED.
  
 13) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING,
 PROVIDE 2 COPIES, 3 IF THRESHOLD OR RESIDENT INSPECTOR
 OF PRODUCT TESTING REPORTS, MISSING REPORTS ARE AS
 FOLLOWS:
 13A) WINDOWS
 13B) EXTERIOR DOORS
 13C) ROOF HATCH
 13D) A/C PRE-MANUFACTURED STANDS
  
 14) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 15) SHEET A5-01 STAIR # 1 INDICATES DETAIL 01 ON A-5.03
 INDICATES THE USE OF 2X WOOD STRINGERS. 2007/09 FBC-B
 1009.5 STAIRWAY CONSTRUCTION. ALL STAIRWAYS SHALL BE
 BUILT OF MATERIALS CONSISTENT WITH THE TYPES PERMITTED
 FOR THE TYPE OF CONSTRUCTION OF THE BUILDING,
  
 15B) SHEET A5-03 DETAIL 01 DOES NOT PROVIDE THE RISER
 DIMENSION FOR STAIRS. 2007/09 FBC-B 1009.3.
  
 16) SHEET A-2.01 THE PLANS DO NOT PROVIDE ELEVATION
 CHANGE FROM THE CONCRETE DECK TO FINISHED MAIN SEATING
 AREA NOT THE VIP PLATFORM. FBC-B 1003.5.2.
  
 17) SHEET A-5.02 STAIRWELL # 2. NO STRUCTURAL PLANS
 WERE SUBMITTED THE TYPE OF MATEIAL FOR STAIR
 CONSTRUCTION IS NOT PROVIDED 2007/09 FBC-B 1009.5 NOR
 IS THE RISE NOR RUN OF THE STAIRSFBC-B 1009.3.
  
 16) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 NEW COMMENTS
  
 17) A4-03 & A4-04 :
  
 17A) SEE DETAIL # 4 ON A-34 MISSING SHEET
  
 17B) THE OLD PLANS INDICATE A ROOF / CEILING ASSEMBLY
 WITH A WIDE BLACK LINE. THE NEW PLANS INDICATE A
 SEPERATE WOOD ROOF JOIST SYSTEM AND A SEPERATE WOOD
 CEIING JOIST SYSTEM HOW ARE YOU GOING TO COMPLY AS A
 TYPE II-B BUILDING WITH NO COMBUSTIBLE FRAMING MEMBERS?
 2007/09 FBC-B 603.1 & TABLE 601.
  
 17C) A4-03 ALSO INDICATES A DETAIL # 11 SHEET A8.04 NOT
 IN PLANS?
  
 18) SHEET LS-02 MEZZANINE RESTROOMS PLEASE SEE
 11-411-4.1.3(11) IF TOILET ROOMS ARE PROVIDED, THEN
 EACH PUBLIC & COMMON USE TOILET ROOM SHALL COMPLY WITH
 11-4.22.
 PLEASE REVIEW 11-4.22(1) DOORS SHALL NOT SWING INTO THE
 CLEAR FLOOR SPACE REQUIRED FOR ANY FIXTURE.
  
 19) 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
 LS-01 THE VIP PLATFORM #108 & DANCE FLOOR # 107 WILL
 NEED TO COMPLY WITH VERTICAL ACCESSIBILITY REQUIREMENTS
 11-4.1.3(5).
  
 20) SHEET A4-05 MISSING DETAAIL 02/ A8.05.
  
 21) SHEET A4-04 & S-7 DETAIL #2 THE ELEVATOR SHAFT
 DETAIL IS MISSING THE SUMP PUMP DETAIL 09/A6.121 DETAIL
 NOT PROVIDED.
  
 22) TYPE II BUILDINGS REQUIRE A SPECIAL ONSITE
 INSPECTOR, BUILDINGS WITH UNUSUAL DESIGN OR METHODS OF
 CONSTRUCTION.
 NEW COMMENT
 -------------------------------------------------------
 ----------
  
 23) THERE IS A NEW 8X11 INTRODUCTORY OVERVIEW STATEMENT
 SHEET, INCLUDED IN THE PERMIT PACKAGE, AUTHOR UNKNOWN
 BUT THE COMMENT INDICATING THAT ALL INTERIOR FINISHES
 AND FINISH MATERIALS WILL BE SELECTED BY OWNER AND
 UNDER A SEPERATE CONTRACT SAID MATERIALS INCLUDE ALL
 FLOOR FINISHES, CEILING MATERIALS & FINISHES ALL WINDOW
 AND DOOR FINISHES, AND WALL SURFACE FINISHES.
  
 WITH THE ABOVE STATEMENT THE PERMIT CAN BE ISSUED AS A
 PROVISO, BUT A SECONDARY PERMIT WILL NEED TO BE APPLIED
 FOR BEFORE A C.O. WILL BE ISSUED.
 THE ARCHITECT OF RECORD SHOULD HAVE A STATEMENT ON THE
 PLANS INDICATING THAT FINISHES TO BE UNDER A SEPERATE
 PERMIT. 106.3.5.1.1. COMMERCIAL PLAN REVIEW CRITERIA
 WOULD REQUIRE THIS INFORMATION BEFORE A PERMIT COULD BE
 ISSUED, THAT WOULD BE THE REASON IT WOULD BE EXEMPTED
 FROM THIS PERMIT.
  
 24) THE NEW A SHEETS ARE SIGNED AND SEALED BUT NOT
 DATED.
 61G1-16.004 FL. ADMIN. CODE. PLANS PREPARED BY A
 REGISTERED ARCHITECT SHALL INCLUDE A TITLE BLOCK WHICH
 MUST:
 X= MISSING INFORMATION
 X - STATE THE FIRM NAME, ADDRESS AND TELEPHONE NUMBER
 X - STATE THE FIRM LICENSE NUMBER
 - STATE PROJECT NAME OR IDENTIFICATION
 - STATE DATE PREPARED
 X - INCLUDE AN ORIGINAL SIGNATURE AND DATED SEALED
 INCLUDE THE PRINTED NAME OF THE ARCHITECT SEALING THE
 PLANS
  
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER C.B.O.
 COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: (561)805-6715
 FAX:(561)805-6731
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2012-02-28 Cont ID  
Sent By jwitmer Date 2012-02-28 Time 14:22 Rev Time 0.00
Received By jwitmer Date 2012-02-28 Time 07:02 Sent To  
Notes
2012-02-28 14:22:16BUILDING PLAN REVIEW
 PERMIT: 11050596
 ADD: 114 S OLIVE AVE
 CONT: LAKESIDE CONTRACTING CORP
 TEL: (954)553-8398
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 2007/09 FLORIDA EXISTING BUILDING CODE W/ SUPPLEMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 FEB. 28/ 2012
 ACTION: DENIED
  
 1) COMPLIED.
  
 2) WHAT WAS THE LAST KNOWN USE FOR THIS BUILDING, IS
 THIS A CHANGE OF OCCUPANCY? THE PLANS DO NOT REFERENCE
 THE FLORIDA EXISTING BUILDING CODE AND TO WHICH TYPE OF
 COMPLIANCE METHOD THE PLANS WERE DESIGNED TOO? FL EXST
 BLDG CODE 101.5 (.1-.3).
  
 3A) SEMI-COMPLIED. PLEASE REFER TO THE 2007 FBC-B FOR
 BUILDING TYPE, NOTE THE 2007FBC-B 603.1.3 REQUIRES ALL
 ROOF CONSTRUCTION GIRDERS, JOIST, TRUSSES AND DECKING
 ARE TO BE FIRE RETARDANT TREATED WOOD. SHEET S-5
 INDICATES THE EXISTING 2X6 ROOF FRAMING, IS THE
 EXISTING STRUCTURE TRULY A BUILDING TYPE II-B? PLEASE
 NOTE THE NEW FRAMING MEMBERS LOCATED ON SHEET S-5 DO
 NOT INDICATE THE USE OF FIRE RETARDANT TREATED WOOD.
  
 3B) COMPLIED.
  
 4-7) COMPLIED.
  
 8) 2ND REQUEST. PLEASE PROVIDE INFORMATION AS TO SHEET
 A2-01 & LS-01 WHAT IS THE ROOM # 119 USED FOR IS THIS
 THE ELEVATOR MACHINE ROOM? IF SO IT NEEDS TO BE RATED
 AS DOES THE DOOR.
  
 9) 2ND REQUEST. SHEET A2-01 INDICATES NEW RAISED
 PLATFORM FLOORING PLEASE PROVIDE SQUARE FOOTAGE OF
 RAISED PLATFORM FLOORING, PLEASE REVIEW SECTION 2007/09
 FBC-B 410.4 FIRE RETARDANT TREATED WOOD REQUIREMENT.
  
 10) 2ND REQUEST. IT APPEARS THERE MAY BE A DISCREPANCY
 BETWEEN A2-01 & S-2, ON SHEET S-2 IT APPEARS THERE IS A
 DOORWAY THAT LEADS FROM THE RAISED DECK IN TO THE
 STAIRWELL WITH NO LANDING OR STAIRS. 106.1.2 ADDITIONAL
 INFORMATION REQUIRED.
  
 11) ROOF HATCH PLEASE BE AWARE OF ADDITIONAL
 INFORMATION REQUIRED, SHEET A8.01 INDICATES THE USE OF
 A NEW ROOF HATCH PLEASE SEE FBC-B 1013.5. & 2007/09
 MECH CODE 304.10 FOR GUARD REQUIREMENTS WHEN UNITS ARE
 WITHIN 10'-0" OF THE ROOF EDGE.
  
 11A) GUARDS SHALL BE PROVIDED WHERE APPLIANCES,
 EQUIPMENT, FANS, ROOF HATCH OPENINGS OR OTHER
 COMPONENTS THAT REQUIRE SERVICE ARE LOCATED WITHIN 10
 FEET (3048 MM) OF A ROOF EDGE OR OPEN SIDE OF A WALKING
 SURFACE AND SUCH EDGE OR OPEN SIDE IS LOCATED MORE THAN
 30 INCHES (762 MM) ABOVE THE FLOOR, ROOF OR GRADE
 BELOW. THE GUARD SHALL BE CONSTRUCTED SO AS TO PREVENT
 THE PASSAGE OF A 21-INCH-DIAMETER (533 MM) SPHERE. THE
 GUARD SHALL EXTEND NOT LESS THAN 30 INCHES (762 MM)
 BEYOND EACH END OF SUCH APPLIANCE, EQUIPMENT, FAN OR
 COMPONENT.
  
 11B) 1013.6 ROOF ACCESS. GUARDS SHALL BE PROVIDED WHERE
 THE ROOF HATCH OPENING IS LOCATED WITHIN 10 FEET (3048
 MM) OF A ROOF EDGE OR OPEN SIDE OF A WALKING SURFACE
 AND SUCH EDGE OR OPEN SIDE IS LOCATED MORE THAN 30
 INCHES (762 MM) ABOVE THE FLOOR, ROOF OR GRADE BELOW.
 THE GUARD SHALL BE CONSTRUCTED SO AS TO PREVENT THE
 PASSAGE OF A 21-INCH-DIAMETER (533 MM) SPHERE.
  
  
 12) COMPLIED.
 13) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING,
 PROVIDE 2 COPIES, 3 IF THRESHOLD OR RESIDENT INSPECTOR
 OF PRODUCT TESTING REPORTS, MISSING REPORTS ARE AS
 FOLLOWS:
 13A) WINDOWS
 13B) ROOF HATCH
 13C) A/C PRE-MANUFACTURED STANDS
  
 14) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 15) MISSING DETAILS SHEET A5-01 STAIR # 1 INDICATES
 DETAIL 12 ON A-13 NO SHEET IS INDICATED ON THE
 ARCHITECTURAL INDEX.
  
 15B) MISSING DETAIL SHEET A---02 STAIR # 2 IS MISSING
 DETAIL SHEET A-13 & A-14.
  
 16) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 NEW COMMENTS
  
 17) A4-03 & A4-04 :
  
 17A) SEE DETAIL # 4 ON A-34 MISSING SHEET
  
 17B) THE OLD PLANS INDICATE A ROOF / CEILING ASSEMBLY
 WITH A WIDE BLACK LINE. THE NEW PLANS INDICATE A
 SEPERATE WOOD ROOF JOIST SYSTEM AND A SEPERATE WOOD
 CEIING JOIST SYSTEM HOW ARE YOU GOING TO COMPLY AS A
 TYPE II-B BUILDING WITH NO COMBUSTIBLE FRAMING MEMBERS?
 2007/09 FBC-B 603.1 & TABLE 601.
  
 17C) A4-03 ALSO INDICATES A DETAIL # 11 SHEET A8.04 NOT
 IN PLANS?
  
 18) SHEET LS-02 MEZZANINE RESTROOMS PLEASE SEE
 11-411-4.1.3(11) IF TOILET ROOMS ARE PROVIDED, THEN
 EACH PUBLIC & COMMON USE TOILET ROOM SHALL COMPLY WITH
 11-4.22.
 PLEASE REVIEW 11-4.22(1) DOORS SHALL NOT SWING INTO THE
 CLEAR FLOOR SPACE REQUIRED FOR ANY FIXTURE.
  
 19) 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
 LS-01 THE VIP PLATFORM #108 & DANCE FLOOR # 107 WILL
 NEED TO COMPLY WITH VERTICAL ACCESSIBILITY REQUIREMENTS
 11-4.1.3(5).
  
 20) SHEET A4-05 MISSING DETAAIL 02/ A8.05.
  
 21) SHEET A4-04 & S-7 DETAIL #2 THE ELEVATOR SHAFT
 DETAIL IS MISSING THE SUMP PUMP DETAIL 09/A6.121 DETAIL
 NOT PROVIDED.
  
 22) TYPE II BUILDINGS REQUIRE A SPECIAL ONSITE
 INSPECTOR, BUILDINGS WITH UNUSUAL DESIGN OR METHODS OF
 CONSTRUCTION.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER C.B.O.
 COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: (561)805-6715
 FAX:(561)805-6731
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-05-31 Cont ID  
Sent By jwitmer Date 2011-05-31 Time 15:03 Rev Time 7.00
Received By jwitmer Date 2011-05-26 Time 12:53 Sent To  
Notes
2011-05-31 15:04:50 
 BUILDING PLAN REVIEW
 PERMIT: 11050596
 ADD: 114 S OLIVE AVE
 CONT: LAKESIDE CONTRACTING CORP
 TEL: (954)553-8398
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 2007/09 FLORIDA EXISTING BUILDING CODE W/ SUPPLEMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PLEASE PROVIDE PLANS OF THE EXISTING SPACE
 INDICATING WHERE THE STAIRWELLS AND EXISTING EXIT
 LOCATIONS. IT APPEARS THE MEZZANINE IS A NEW LEVEL?
 106.1.2 ADDITIONAL INFORMATION REQUIRED. 2007/09 FL
 EXST BLDG CODE 701.3 NEW WORK.
  
 2) WHAT WAS THE LAST KNOWN USE FOR THIS BUILDING, IS
 THIS A CHANGE OF OCCUPANCY? THE PLANS DO NOT REFERENCE
 THE FLORIDA EXISTING BUILDING CODE AND TO WHICH TYPE OF
 COMPLIANCE METHOD THE PLANS WERE DESIGNED TOO? FL EXST
 BLDG CODE 101.5 (.1-.3).
  
 3A) SHEET A-1.0 THE BUILDING & CODE INFORMATION
 INDICATES THIS BUILDING TYPE UNDER THE 1997 UBC AS A
 TYPE II-B NON-COMBUSTIBLE/ NONRATED. PLEASE REFER TO
 THE 2007 FBC-B FOR BUILDING TYPE, NOTE THE 2007FBC-B
 603.1.3 REQUIRES ALL ROOF CONSTRUCTION GIRDERS, JOIST,
 TRUSSES AND DECKING ARE TO BE FIRE RETARDANT TREATED
 WOOD. SHEET S-5 INDICATES THE EXISTING 2X6 ROOF
 FRAMING, IS THE EXISTING STRUCTURE TRULY A BUILDING
 TYPE II-B? PLEASE NOTE THE NEW FRAMING MEMBERS LOCATED
 ON SHEET S-5 DO NOT INDICATE THE USE OF FIRE RETARDANT
 TREATED WOOD.
  
 3B) THE BUILDING & CODE INFORMATION FOUND ON SHEET A-1
 DOES NOT INDICATE IF THIS IS A FIRE SPRINKLERED
 BUILDING? 2007/09 FBC-B 106.3.5.1.1. MINIMUM PLAN
 REVIEW CRITERIA.
  
 4A) PLEASE PROVIDE A LIFE SAFETY PLAN W/ FURNISHINGS
 OCCUPANT LOADS & EGRESS CAPACITIES. 2007/09 FBC-B
 106.3.5.1.1(6).
  
 4B) PLEASE PROVIDE COMMON PATH OF TRAVEL FOR THE FIRST
 FLOOR SEE LIMITATIONS 1014.3 FOR THE FIRST FLOOR AS
 WELL AS THE MEZZANINE LEVEL AND THE SECOND FLOOR.
 REVIEW SECTION 505.3 FOR THE MEZZANINE MAXIMUM TRAVEL
 DISTANCE INCLUDES THE DISTANCE TRAVELED ON THE STAIRWAY
 MEASURED IN THE PLANE OF THE TREAD NOSING.
  
 4C) PLEASE PROVIDE ADDITIONAL INFORMATION AS TO THE
 OCCUPANCY SEPARATION IN CONJUNCTION TO THE OPEN AIR
 STAIR BETWEEN THE MEZZANINE LEVEL AND THE 2ND FLOOR
 LEVEL?
 2007 FBC-B TABLE 508.3.3.
  
 4D) THE SECOND FLOOR FRONT STAIRWAY IS IN THE SAME
 STAIRWELL AS THE ELEVATOR. 2007 FBC-B 3002.7 COMMON
 ENCLOSURE WITH STAIRWAY. ELEVATORS SHALL NOT BE IN A
 COMMON SHAFT ENCLOSURE WITH A STAIRWAY. THE 1ST FLOOR
 AND MEZZANINE LEVEL WOULD BE OK SINCE THE MEZZANINE
 LEVEL IS NOT CONSIDERED A STORY. HOW WILL SMOKE
 ACCUMULATION IN THE STAIRWELL BE HANDLED SINCE THE
 FLOOR BELOW (MEZZANINE LEVEL) IS OPEN.
  
 4E) THE SECOND FLOOR FRONT STAIRWELL WILL NEED TO
 INDICATE FIRE RATING ON THE WALLS AND OPENING
 PENETRATIONS. FBC 1020.1 & TABLE 715.4. SHEET A8.03
 INDICATES WALL RATINGS BUT THE FLOOR PLANS DO NOT TIE
 THEM TO ANY WALLS WITH WALL MARKERS. THE SAME HOLDS
 TRUE FOR RATING OF FIRE RATED DOORS THE DOOR SCHEDULE
 DOES NOT PROVIDE ANY DOOR OPENINGS THAT WOULD REQUIRE
 FIRE RATING, STAIRWELL ENTRY DOORS, THE 2ND FLOOR
 STAIRWELL,
  
 5) PROVIDE THE OCCUPANT LOADS PER 2007/09 FBC-B
 106.3.5.1.1(7) OCCUPANT LOADS FOR EACH OF THE ASSEMBLY
 AREAS WITH BREAKDOWN IF 5 NET, 7 NET OR 15 NET, PER
 FLOOR AND FOR THE BUSINESS OCCUPANCY. FBC-B TABLE
 1004.1.1.
  
 6) SHEET A-1 ALSO FAILS TO PROVIDE INFORMATION ON
 OCCUPANCY SEPARATION BETWEEN THE A2 OCCUPANCY AND THE
 BUSINESS OCCUPANCY LOCATED ON THE 2ND FLOOR, PLEASE
 PROVIDE DESIGN CRITERIA 2007/09 FBC-B 508.3.1.3.
  
 7) DEPENDING ON THE OCCUPANT LOAD OF THE A2 OCCUPANCY
 THIS BUILDING MAY END UP BEING CLASSIFIED AS A
 THRESHOLD BUILDINGREQIRING THE FOLLOWING:
  
 THRESHOLD INSPECTION PLAN FL S. S. 553.71(7) "
 THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH
 HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN
 THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN
 AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
  
 7A)109.3.6.1 THE ENFORCING AGENCY SHALL REQUIRE A
 SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON
 A THRESHOLD BUILDING PURSUANT TO A STRUCTURAL
 INSPECTION PLAN PREPARED BY THE ENGINEER OF RECORD. THE
 STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE
 ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING.
 THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO
 PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO
 THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR
 COMPLIANCE WITH THE PERMITTED DOCUMENTS.
  
 7B) THRESHOLD INSPECTOR:
 WPB AMENDMENT 109.3.6.2 W.P.B. CONSTRUCTION SERVICES
 DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A SPECIAL
 INSPECTOR AS REQUIRED BY FL S S 553.79(5) FLORIDA
 STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY THIS
 CODE.
 CONTACT KEN CONRAD MANAGER OF THE SPECIAL INSPECTOR
 PROGRAM AT (561)805-6666 FOR FURTHER INFORMATION
 BEFORE THE PERMIT MAY BE ISSUED.
  
 7C) THRESHOLD BLDG, REQUIRED STATEMENT:
 W.P.B. AMENDMENT 109.3.6.4.4 ALL PLANS FOR THE BUILDING
 WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S PR ENGINEER'S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE
 LOCAL AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 7D) A HOLD WILL BE PUT ON THIS PROJECT UNTIL THESE
 ITEMS ARE COMPLETED AS REQUESTED BY THE CHIEF BUILDING
 INSPECTOR KEN CONRAD:
  
 PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR
 IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS.
  
 1) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR HISTORY
 FOR THIS TYPE OF CONCRETE RESTORATION.
 THIS MAY BE SUBMITTED TO KEN CONRAD BY E-MAIL. KEN
 CONRAD: [email protected]
  
 2) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
 CONTACT KEN CONRAD
 TEL: 561-805-6666
 E-MAIL: [email protected]
  
 8) PLEASE PROVIDE INFORMATION AS TO SHEET A-6 WHAT IS
 THE ROOM # 119 USED FOR IS THIS THE ELEVATOR MACHINE
 ROOM? IF SO IT NEEDS TO BE RATED AS DOES THE DOOR.
  
 9) SHEET A-6 & S-2 INDICATES NEW RAISED PLATFORM
 FLOORING PLEASE PROVIDE SQUARE FOOTAGE OF RAISED
 PLATFORM FLOORING, PLEASE REVIEW SECTION 2007/09 FBC-B
 410.4 FIRE RETARDANT TREATED WOOD REQUIREMENT.
  
 10) IT APPEARS THERE MAY BE A DISCREPANCY BETWEEN A-6 &
 S-2, ON SHEET S-2 IT APPEARS THERE IS A DOORWAY THAT
 LEADS FROM THE RAISED DECK IN TO THE STAIRWELL WITH NO
 LANDING OR STAIRS. 106.1.2 ADDITIONAL INFORMATION
 REQUIRED.
  
 11) ADDITIONAL INFORMATION REQUIRED, SHEET A8.01
 INDICATES THE USE OF A NEW ROOF HATCH WHICH IS NOT
 INDICATED ON EITHER THE ARCHITECTURAL NOR STRUCTURAL
 SHEETS. SHEET A8 IN STORAGE ROOM 304-A HAS WHAT APPEARS
 TO BE A LADDER AND POSSIBLE LOCATION FOR THE ROOF HATCH
 THE SECTION 11/ A-16 DOES NOT MATCH UP WITH ANY PLANS
 WITHIN THIS SET, ADDITIONAL INFORMATION IS REQUIRED.
 PLEASE REVIEW 2007/09 FBC-B 1509.6 FOR PERMANENT LADDER
 REQUIREMENTS. PLEASE REVIEW 2007/09 MECH CODE 304.10
 FOR GUARD REQUIREMENTS WHEN UNITS ARE WITHIN 10?-0? OF
 THE ROOF EDGE.
  
 12) SHEET A-21 EAST ELEVATION INDICATES THE USE OF AN
 EXISTING FIRE ESCAPE EXIT DOORS AND WINDOW # 12 BEING
 REPLACED. PLEASE REVIEW 2007/09 EXST BLDG CODE 303.5
 OPENING PROTECTION. DOORS AND WINDOWS ALONG THE FIRE
 ESCAPE SHALL BE PROTECTED WITH ? HR OPENING
 PROTECTIVES.
  
 13) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING,
 PROVIDE 2 COPIES, 3 IF THRESHOLD OR RESIDENT INSPECTOR
 OF PRODUCT TESTING REPORTS, MISSING REPORTS ARE AS
 FOLLOWS:
 13A) WINDOWS
 13B) ROOF HATCH
 13C) A/C PRE-MANUFACTURED STANDS
  
 14) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 15A) SHEET A-53 STAIR DESIGN NEEDS TO BE UPDATED FROM
 THE 1997 UBC.
  
 15B) SHEET A-53 STAIR NOTE # 3 PLEASE UPDATE NOTE TO
 THE 2007/09 FBC-B 1607.1.2
 INTERMEDIATE RAILS SHALL BE DESIGNED TO WITHSTAND
 HORIZONTALLY
  
 16) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER C.B.O.
 COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: (561)805-6715
 FAX:(561)805-6731
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2012-04-23 Cont ID  
Sent By rlecky Date 2012-04-23 Time 14:35 Rev Time 0.00
Received By rlecky Date 2012-04-23 Time 12:11 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2012-03-26 Cont ID  
Sent By rlecky Date 2012-03-26 Time 16:33 Rev Time 0.00
Received By rlecky Date 2012-03-26 Time 16:33 Sent To  
Notes
2012-03-26 16:34:13RESUB DID NOT INCLUDE A RESPONSE TO ELECTRICAL COMMENTS
 OF 6/1/2011
  
 ROBERT LECKY
 ELECTRIC PLANS EXAMINER
 [email protected]
 561-805-6718
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2012-02-29 Cont ID  
Sent By rlecky Date 2012-02-29 Time 17:12 Rev Time 0.00
Received By rlecky Date 2012-02-29 Time 17:02 Sent To  
Notes
2012-02-29 17:13:29RESUB DID NOT INCLUDE A RESPONSE TO ELECTRICAL COMMENTS
 OF 6/1/2011
  
 ROBERT LECKY
 ELECTRIC PLANS EXAMINER
 [email protected]
 561-805-6718
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2011-06-01 Cont ID  
Sent By rlecky Date 2011-06-01 Time 15:35 Rev Time 0.00
Received By rlecky Date 2011-06-01 Time 12:38 Sent To  
Notes
2011-06-01 15:39:28PROVIDE SPECIFICATIONS FOR THE NEW ELECTRICAL SERVICE
 EQUIPMENT SHOWING THE EQUIPMENT SELECTED IS CAPABLE OF
 INTERRUPTING THE AVAILABLE FAULT CURRENT. NEC 110.9,
 110.10
 PROVIDE A DETAIL SHOWING THAT THE REQUIRED WORKING
 CLEARANCES AND DEDICATED WORKING SPACE HAS BEEN
 PROVIDED FOR THE ELECTRICAL EQUIPMENT. NEC 110.26,
 240.24, 408.17
 PROVIDE SPECIFICATIONS AND LISTING FROM AN APPROVED
 TESTING AGENCY FOR THE CUSTOM LIGHTING FIXTURES. NEC
 110.3
 VERIFY ALL CUSTOM SOUND AND LIGHT SYSTEMS ARE LISTED BY
 AN APPROVED TESTING AGENCY. NEC 110.3
 PROVIDE A STRUCTURAL SUPPORT DETAIL FOR LIGHT FIXTURES
 AND LIGHTING ARRAYS RATED AT MORE THAN 50 POUNDS. NEC
 410.36, 314.27
 A SEPARATE PLAN AND ELECTRICAL PERMIT IS REQUIRED FOR
 THE FIRE ALARM SYSTEM.
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 561-805-6718
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status F Date 2012-07-12 Cont ID  
Sent By wjolin Date 2012-07-12 Time 10:50 Rev Time 0.00
Received By wjolin Date 2012-07-12 Time 10:23 Sent To  
Notes
2012-07-12 10:32:28114 SOUTH OLIVE AVENUE
 PERMIT #11050596
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 NOTE: THE RESPONSE LETTER FROM THE ARCHITECT (WILLIAM
 FRASER) DATED FEBRUARY 16, 2012 ADDRESSES THE FIRE
 REVIEW COMMENTS; HOWEVER, MUCH OF THE RESPONSE
 INFORMATION IS NOT SHOWN ON THE PLANS.
  
  
 PROVIDE TACTILE SIGNAGE AT EXIT DOORS.
  
 EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED SEATS
 SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED IN A
 CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE ROOM.
 SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF
 OCCUPANTS PERMITTED FOR EACH ROOM.
  
 SHEET A0.01: WHEN THE OCCUPANT LOAD EXCEEDS 300 PERSONS
 AND THE BUILDING IS FULLY SPRINKLERED, THE INTERIOR
 WALL AND CEILING FINISHES SHALL BE AS FOLLOWS:
 -ENCLOSED STAIRWAYS SHALL BE CLASS A OR B
  
 SHEET FP-01: STAIR LOBBY STEPS SHALL HAVE A TREAD DEPTH
 OF AT LEAST 13-INCHES. PROVIDE A CONTRASTING STRIPE ON
 EACH STEPPING SURFACE OF THE LEADING EDGE OR TREAD
 NOSING TO MAKE THE PRESENCE OF AN ELEVATION CHANGE
 READILY APPARENT TO OCCUPANTS.
  
 SHEET A2-03: STAIR DOOR #301 TO CATWALK SHALL BE LOCKED
 AT ALL TIMES. PERMANENT SIGN READING "AUTHORIZED
 PERSONNEL ONLY" SHALL BE AFFIXED TO THE DOOR.
  
 MEP SHEETS: PROJECT ADDRESS IS INCORRECTLY INDICATED AS
 "114 STONE STREET."
  
 SHEET F2-1: CIVIL PLANS NOT SUBMITTED SHOWING FIRE LINE
 CONNECTION TO CITY SUPPLY, BACKFLOW PREVENTER, FIRE
 HYDRANT LOCATION IN RELATION TO FDC, ETC.
  
 SHEET F2-1: FIRE DEPARTMENT CONNECTION SHALL BE LOCATED
 WITHIN 150 FEET OF A FIRE HYDRANT. LOCATE FDC ON OLIVE
 AVENUE.
  
 SHEET F3-1: PER FLORIDA ADMINISTRATIVE CODE SECTION
 61G15-32.004, PLANS SHALL INDICATE THE HAZARD
 CLASSIFICATIONS, DESIGN DENSITIES, AND HYDRANT FLOW
 TEST DATA.
  
 SHEET A8-01: STAIR DOORS DO NOT HAVE A FIRE-RATING.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2012-04-25 Cont ID  
Sent By wjolin Date 2012-04-25 Time 10:11 Rev Time 0.00
Received By wjolin Date 2012-04-24 Time 14:20 Sent To  
Notes
2012-04-24 15:41:19114 SOUTH OLIVE AVENUE
 PERMIT #11050596
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 NOTE: THE RESPONSE LETTER FROM THE ARCHITECT (WILLIAM
 FRASER) DATED FEBRUARY 16, 2012 ADDRESSES THE FIRE
 REVIEW COMMENTS; HOWEVER, MUCH OF THE RESPONSE
 INFORMATION IS NOT SHOWN ON THE PLANS.
  
  
 PROVIDE TACTILE SIGNAGE AT EXIT DOORS.
  
 EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED SEATS
 SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED IN A
 CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE ROOM.
 SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF
 OCCUPANTS PERMITTED FOR EACH ROOM.
  
 SHEET A0.01: WHEN THE OCCUPANT LOAD EXCEEDS 300 PERSONS
 AND THE BUILDING IS FULLY SPRINKLERED, THE INTERIOR
 WALL AND CEILING FINISHES SHALL BE AS FOLLOWS:
 -ENCLOSED STAIRWAYS SHALL BE CLASS A OR B
  
 SHEET FP-01: STAIR LOBBY STEPS SHALL HAVE A TREAD DEPTH
 OF AT LEAST 13-INCHES. PROVIDE A CONTRASTING STRIPE ON
 EACH STEPPING SURFACE OF THE LEADING EDGE OR TREAD
 NOSING TO MAKE THE PRESENCE OF AN ELEVATION CHANGE
 READILY APPARENT TO OCCUPANTS.
  
 SHEET A2-03: STAIR DOOR #301 TO CATWALK SHALL BE LOCKED
 AT ALL TIMES. PERMANENT SIGN READING "AUTHORIZED
 PERSONNEL ONLY" SHALL BE AFFIXED TO THE DOOR.
  
 MEP SHEETS: PROJECT ADDRESS IS INCORRECTLY INDICATED AS
 "114 STONE STREET."
  
 SHEET F2-1: CIVIL PLANS NOT SUBMITTED SHOWING FIRE LINE
 CONNECTION TO CITY SUPPLY, BACKFLOW PREVENTER, FIRE
 HYDRANT LOCATION IN RELATION TO FDC, ETC.
  
 SHEET F2-1: FIRE DEPARTMENT CONNECTION SHALL BE LOCATED
 WITHIN 150 FEET OF A FIRE HYDRANT. LOCATE FDC ON OLIVE
 AVENUE.
  
 SHEET F3-1: PER FLORIDA ADMINISTRATIVE CODE SECTION
 61G15-32.004, PLANS SHALL INDICATE THE HAZARD
 CLASSIFICATIONS, DESIGN DENSITIES, AND HYDRANT FLOW
 TEST DATA.
  
 SHEET A8-01: STAIR DOORS DO NOT HAVE A FIRE-RATING.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2012-03-05 Cont ID  
Sent By wjolin Date 2012-03-05 Time 11:46 Rev Time 0.00
Received By wjolin Date 2012-03-05 Time 08:50 Sent To  
Notes
2012-03-05 11:46:10114 SOUTH OLIVE AVENUE
 PERMIT #11050596
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 DESIGN SHALL CONFORM TO THE FLORIDA FIRE PREVENTION
 CODE 2007 EDITION: NFPA 1 AND NFPA 101 - 2006 EDITION
 WITH FLORIDA AMENDMENTS.
  
 ALL DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS
 OF NFPA 241.
  
 PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY
 RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING
 NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM
 WWW.KNOXBOX.COM.
  
 PROVIDE A CIVIL ENGINEERING PLAN SHOWING UNDERGROUND
 UTILITIES, CONNECTIONS, FIRE HYDRANTS, PIPE SIZES ETC.
  
 PROVIDE TACTILE SIGNAGE AT EXIT DOORS.
  
 EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED SEATS
 SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED IN A
 CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE ROOM.
 SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF
 OCCUPANTS PERMITTED FOR EACH ROOM.
  
 SHEET A0.01: NFPA 5000 IS NOT ADOPTED BY THE STATE OF
 FLORIDA.
  
 SHEET A0.01: WHEN THE OCCUPANT LOAD EXCEEDS 300 PERSONS
 AND THE BUILDING IS FULLY SPRINKLERED, THE INTERIOR
 WALL AND CEILING FINISHES SHALL BE AS FOLLOWS:
 -ENCLOSED STAIRWAYS SHALL BE CLASS A OR B
 -CORRIDORS AND LOBBIES SHALL BE CLASS A, B OR C
 -GENERAL ASSEMBLY AREAS SHALL BE CLASS A, B OR C
  
 SHEET LS-01: PROVIDE HANDRAILS FOR STAIR #111.
  
 SHEET FP-01: LOBBY STEP AND GRAND STAIR LOBBY STEP
 SHALL HAVE A TREAD DEPTH OF AT LEAST 13-INCHES. PROVIDE
 A CONTRASTING STRIPE ON EACH STEPPING SURFACE OF THE
 LEADING EDGE OR TREAD NOSING TO MAKE THE PRESENCE OF AN
 ELEVATION CHANGE READILY APPARENT TO OCCUPANTS.
  
 SHEET A2-01: NO ROOM NAMES OR DOOR SCHEDULE PROVIDED
 FOR DOOR #118 AND #119.
  
 SHEET A2-03: STAIR DOOR #301 TO CATWALK SHALL BE LOCKED
 AT ALL TIMES. PERMANENT SIGN READING "AUTHORIZED
 PERSONNEL ONLY" SHALL BE AFFIXED TO THE DOOR.
  
 MEP SHEETS: PROJECT ADDRESS IS INCORRECTLY INDICATED AS
 "114 STONE STREET."
  
 SHEET F2-1: CIVIL PLANS NOT SUBMITTED SHOWING FIRE LINE
 CONNECTION TO CITY SUPPLY, BACKFLOW PREVENTER, FIRE
 HYDRANT LOCATION IN RELATION TO FDC, ETC.
  
 SHEET F2-1: FIRE DEPARTMENT CONNECTION SHALL BE LOCATED
 WITHIN 150 FEET OF A FIRE HYDRANT. LOCATE FDC ON OLIVE
 AVENUE.
  
 SHEET F3-1: PER FLORIDA ADMINISTRATIVE CODE SECTION
 61G15-32.004, PLANS SHALL INDICATE THE HAZARD
 CLASSIFICATIONS, DESIGN DENSITIES, AND HYDRANT FLOW
 TEST DATA.
  
 SHEET E2-2: PLANS DO NOT INDICATE THE METHOD (HEAT
 DETECTOR/FLOW SWITCH WITHOUT TIME DELAY) USED TO SHUNT
 TRIP POWER TO THE ELEVATOR IN THE EVENT AN AUTOMATIC
 SPRINKLER ACTIVATES IN THE ELEVATOR MACHINE ROOM.
  
 SHEET A8-01: STAIR DOORS DO NOT HAVE A FIRE-RATING.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2011-06-03 Cont ID  
Sent By wjolin Date 2011-06-03 Time 12:55 Rev Time 0.00
Received By wjolin Date 2011-06-03 Time 09:16 Sent To  
Notes
2011-06-03 12:55:26114 SOUTH OLIVE AVENUE
 PERMIT #11050596
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 DESIGN SHALL CONFORM TO THE FLORIDA FIRE PREVENTION
 CODE 2007 EDITION: NFPA 1 AND NFPA 101 - 2006 EDITION
 WITH FLORIDA AMENDMENTS.
  
 ALL DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS
 OF NFPA 241.
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE APPROVED AND SUBMITTED IN WRITING TO THE OFFICE OF
 THE FIRE MARSHAL.
  
 PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY
 RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING
 NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM
 WWW.KNOXBOX.COM.
  
 PROVIDE BUILDING ADDRESS VISIBLE FROM THE STREET.
 NUMBERS SHALL BE AT LEAST SIX-INCHES IN HEIGHT AND
 SHALL CONTRAST THE BACKGROUND PER NFPA 1 - FLORIDA
 EDITION.
  
 PROVIDE A CIVIL ENGINEERING PLAN SHOWING UNDERGROUND
 UTILITIES, CONNECTIONS, FIRE HYDRANTS, PIPE SIZES ETC.
  
 PROVIDE A LIFE SAFETY PLAN (WITH FURNITURE) SHOWING
 OCCUPANT LOADS, TRAVEL DISTANCES TO EXITS, EXIT SIGNS,
 FIRE EXTINGUISHERS, FIRE-RATED WALLS, ETC.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 PROVIDE TACTILE SIGNAGE AT EXIT DOORS.
  
 REFLECTED CEILING PLANS DO NOT INDICATE CEILING
 ELEVATIONS.
  
 STAIR DOORS DO NOT HAVE A FIRE-RATING ACCORDING THE
 DOOR SCHEDULE ON SHEET A-71.
  
 EVERY FLOOR SERVED BY THE ELEVATOR SHALL HAVE AN
 ELEVATOR LOBBY WITH A ONE-HOUR FIRE RATING PER SECTION
 7.2.13.3 OF NFPA 101 - FLORIDA EDITION. ALSO, ELEVATORS
 SHALL NOT OPEN TO AN EXIT PER SECTION 9.4.7 OF NFPA 101
 - FLORIDA EDITION.
  
 SHEET A1-1: PROVIDE ADDITIONAL INFORMATION FOR EXISTING
 METAL CATWALK AND STAIR THAT IS TO REMAIN. INDICATE
 STAIR DISCHARGE LOCATION.
  
 SHEET A-6: GRAND STAIR #103 IS SERVING AS AN EXIT. ALL
 INSIDE STAIRS SERVING AS AN EXIT OR EXIT COMPONENT
 SHALL BE ENCLOSED PER SECTION 7.2.2.5.1.1 OF NFPA 101 -
 FLORIDA EDITION.
  
 SHEET A-6: TICKET RAMP APPEARS TO ONLY HAVE ONE
 HANDRAIL.
  
 SHEET A-7: THE PLAN IS DESIGNATED AS A MEZZANINE BUT
 DOES NOT MEET THE DEFINITION OF MEZZANINE AS PROVIDED
 IN THE FLORIDA BUILDING CODE. THIS LEVEL IS FUNCTIONING
 AS A FLOOR AND NEEDS TO HAVE OPENINGS PROTECTED.
  
 SHEET A-8: THE DOOR SWING OF #322 OBSTRUCTS ACCESS TO
 EXIT STAIR #2.
  
 SHEET A-8: SOME ROOMS REQUIRE TRAVEL THROUGH ANOTHER
 ROOM TO REACH AN EXIT. THESE DOORS CANNOT BE SUBJECT TO
 LOCKING AND PROHIBIT EGRESS.
  
 SHEET A-8: EXTERIOR STAIRS SHALL BE SEPARATED AND HAVE
 PROTECTED OPENINGS PER SECTION 7.2.2.6 OF NFPA 101 -
 FLORIDA EDITION.
  
 SHEET E2-3: PROVIDE SPEAKER/STROBE NOTIFICATION
 APPLIANCES FOR VOICE EVACUATION SYSTEM. MOST
 NOTIFICATION APPLIANCES ARE SHOWN AS HORN/STROBES.
  
 SHEET E2-3: PROVIDE NOTIFICATION APPLIANCE IN CORRIDOR
 #116.
  
 SHEET F2-1: CIVIL PLANS NOT SUBMITTED SHOWING FIRE LINE
 CONNECTION TO CITY SUPPLY, BACKFLOW PREVENTER, FIRE
 HYDRANT LOCATION IN RELATION TO FDC, ETC.
  
 SHEET F3-1: PER FLORIDA ADMINISTRATIVE CODE SECTION
 61G15-32.004, PLANS SHALL INDICATE THE HAZARD
 CLASSIFICATIONS, DESIGN DENSITIES, AND HYDRANT FLOW
 TEST DATA.
  
 NOTE: A DRAWING INDEX WOULD HELP EXPLAIN THE GAP IN
 DRAWING NUMBER SEQUENCE.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2011-05-19 Cont ID  
Sent By jpapa Date 2011-05-19 Time 14:56 Rev Time 0.25
Received By jpapa Date 2011-05-19 Time 14:56 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2012-07-24 Cont ID  
Sent By shill Date 2012-07-24 Time 17:06 Rev Time 0.00
Received By shill Date 2012-06-18 Time 10:21 Sent To  
Notes
2012-06-19 10:14:34RESUBMITTAL BUILDING ONLY
 GAVE RESUB TO JIM

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2012-07-24 Cont ID  
Sent By shill Date 2012-07-12 Time 15:54 Rev Time 0.00
Received By shill Date 2012-04-12 Time 11:02 Sent To  
Notes
2012-04-12 11:03:16EXPEDITED
 C--27

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2012-04-12 Cont ID  
Sent By lmartine Date 2012-03-26 Time 10:59 Rev Time 0.00
Received By lmartine Date 2012-02-22 Time 17:25 Sent To  
Notes
2012-02-22 17:26:23REVISED DRAWINGS
2012-02-22 17:26:07EXPEDITED
 C-27

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2012-01-13 Time   Rev Time 0.00
Received By lmartine Date 2012-01-09 Time 14:40 Sent To  
Notes
2012-01-19 13:59:00REVIEWS PLACED ON HOLD. SEE FRONT SCREEN NOTES.
2012-01-09 15:24:13**********************EXPEDITED*********************
 C--25

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2011-06-17 Time   Rev Time 0.00
Received By lmartine Date 2011-05-19 Time 15:26 Sent To  
Notes
2011-05-19 15:53:45*******************EXPEDITED********************
 B--7

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2012-02-28 Cont ID  
Sent By jwitmer Date 2012-02-28 Time 14:23 Rev Time 0.00
Received By jwitmer Date 2012-02-28 Time 14:23 Sent To  
Notes
2012-02-28 14:27:14BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2012-06-25 Cont ID  
Sent By hmoser Date 2012-06-25 Time 15:46 Rev Time 0.00
Received By hmoser Date 2012-06-25 Time 15:46 Sent To  
Notes
2012-06-27 12:42:50 
  
 1. SEE PREVIOUS COMMENT LIST REGARDING SHAFT. IT NOW
 APPEARS THAT THE SHAFT HAS BEEN REMOVED FROM FLOOR
 PLANS, BUT DOUBLE RECTANGLES DRAWN IN DASHED LINES
 APPEAR ON THE MECHANICAL PLAN SHEETS FOR MEZZANINE AND
 CATWALK. FOR INSTANCE, SEE SHEET M2-2, COLUMN LINE 2
 BETWEEN A AND B. PLEASE PROVIDE INFORMATION OR REMOVE.
  
 A HORIZONTAL SHAFT IS SHOWN ON A SHEETS, BUILDING
 SECTIONS. PLEASE COORDINATE; MECHANICAL SHEETS DO NOT
 SHOW A SHAFT, SEE FBC MECHANICAL 607.5.5.
  
 2. FBC 2010 BUILDING 3006.2, SEE PREVIOUS COMMENT LIST,
 NO ELEVATOR MACHINE ROOM SHOWN. IF A MRL ELEVATOR IS
 PROPOSED, PLEASE SPECIFY ON MECHANICAL SHEETS OR ADVISE
 WHERE THIS INFORMATION CAN BE FOUND ON THE PLAN IN
 ORDER TO VERIFY THAT A SEPARATE, INDEPENDENT
 VENTILATION SYSTEM IS NOT REQUIRED. PROVIDE
 SPECIFICATIONS FOR THE ELEVATOR PROPOSED, FBC 107.1.
  
 3. SEE PREVIOUS LIST, PROVIDE EITHER A CURB DETAIL OR
 PROVIDE FLORIDA STATE OR LOCAL PRODUCT APPROVAL FOR
 ROOF STANDS. DESIGNER IS TO SPECIFY DESIGN PRESSURES
 FOR ROOFTOP EQUIPMENT, FBC BUILDING 301.12, FAC9N-3.
  
 4. SEE PREVIOUS LIST, IF A SYSTEM SIZING SUMMARY IS
 PROVIDED IN LIEU OF A FULL COOLING LOAD CALCULATION, IT
 MUST BE SIGNED AND SEALED PER FBC BUILDING
 13-407.AB.1.1.
  
 5. FIRE DAMPERS ARE MISSING AT THE FOLLOWING LOCATIONS;
 8X10 EXHAUST DUCTS (TWO LOCATIONS), M2-1, AND RISERS
 BETWEEN FLOORS, EXHAUST THROUGH THE FLOOR M2-2. PLEASE
 CHECK ALL REQUIRED LOCATIONS AND REVISE. FBC MECHANICAL
 607.6.3, 607.5.3.
  
 6. LOCATION OF EXHAUST OUTLET NOT CLEAR, FBC MECHANICAL
 501.2.1. REVISE PLAN TO SHOW LOCATION.
  
 HAROLD MOSER, CHIEF MECHANICAL INSPECTOR
 561-805-6732
  
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2011-06-17 Cont ID  
Sent By rregueir Date 2011-06-17 Time 15:52 Rev Time 0.00
Received By rregueir Date 2011-06-15 Time 15:56 Sent To  
Notes
2011-06-17 15:52:40REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. DUCTS COMING FROM ROOF/SECOD FLOOR DOWN TO FIRST
 FLOOR ARE SHOWN IN RATED SHAFT ENCLOSURES. DUCTS WHICH
 PENETRATE SHAFT ENCLOSURES ARE REQUIRED TO BE PROTECTED
 BY BOTH FIRE AND SMOKE DAMPERS PER FBC-M 607.5.5. FYI:
 DUCTS THAT ONLY PENETRATE ONE FLOOR/CEILING ASSEMBLY
 MAY NOT NEED A SHAFT ENCLOSURE AND COULD BE COMPLIANT
 WITH A FIRE DAMPER PROTECTING THE PENETRATION AT THE
 SECOND FLOOR SLAB. THIS WOULD ELIMINATE THE NEED FOR
 SMOKE DAMPERS AND RATED SHAFTS.
  
 2. AHU 1 AND AHU 2 ON MEZZANINE LEVEL SHARE A COMMON
 RETURN AIR PLENUM. EACH UNIT IS REQUIRED TO HAVE DUCT
 MOUNTED SMOKE DTECTORS ON BUTH THE SUPPLY AND RETURN IN
 ACCORDANCE WITH FBC-M 606.2.2.
  
 3. THE ELEVATOR MACHINE ROOM DOES NOT APPEAR ON THE
 MECHANICAL FLOOR PLAN. HOW WILL THIS ROOM BE
 VENTILATED? A SEPARATE, INDEPENDENT VENTILATION OR AIR
 CONDITIONING SYSTEM IS REQUIRED FOR THE MACHINE ROOM
 PER FBC-B 3006.2.
  
 4. PAGE M2-1 SHOWS AHU-4 IN A CLOSET. NO SUCH APPLIANCE
 APPEARS ON THE EQUIPMENT SCHEDULE (PAGE M3-3). PLEASE
 COORDINATE SCHEDULES AND FLOOR PLANS.
  
 5. ROOF PLAN SHOWS A PRE-ENGINEERED A/C STAND FOR
 CONDENSING UNITS. PRODUCT APPROVAL IS REQUIRED PER FAC
 RULE 9N-3. PROVIDE PRODUCT APPROVAL WHICH IS APPROVED
 IN WRITING BY THE ENGINEER FOR THIS PROJECT PER FBC-M
 106.3.3.
  
 6. IF A SYSTEM SIZING SUMMARY IS PROVIDED IN LIEU OF A
 FULL COOLING LOAD CALCULATION, IT MUST BE SIGNED AND
 SEALED PER FBC-B 13-407.AB.1.1.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 5 Status F Date 2012-07-09 Cont ID  
Sent By lwagner Date 2012-07-09 Time 14:19 Rev Time 0.00
Received By lwagner Date 2012-07-09 Time 14:18 Sent To  
Notes
2012-07-09 14:19:16FBC 2007 PLUMBING REVIEW #5
 DENIED:
  
 FROM LAST REVIEW:
  
 2. THE SUMP PUMP SHOWN WILL BE REQUIRED TO CONNECT
 INDIRECTLY (TO A FLOOR DRAIN OR HUB DRAIN) TO THE
 **SANITARY** USING THE OIL SMART CONTROLS SHOWN ON
 P3-1.
 WITH THE USE OF THE OIL SMART CONTROLS, THE OIL
 INTERCEPTOR WOULD NOT BE REQUIRED.
 301.6 PROHIBITED LOCATIONS. PLUMBING SYSTEMS SHALL NOT
 BE LOCATED IN AN ELEVATOR SHAFT OR IN AN ELEVATOR
 EQUIPMENT ROOM.
 EXCEPTION: FLOOR DRAINS, SUMPS AND SUMP PUMPS SHALL BE
 PERMITTED AT THE BASE OF THE SHAFT PROVIDED THEY ARE
 ***INDIRECTLY*** CONNECTED TO THE PLUMBING SYSTEM.
 THE SUMP LINE WILL NOT BE CONNECTED TO THE STORM SYSTEM
 - CITY UTILITY CODE 90-203 (A)
  
 PLEASE CORRECT THE FOLLOWING:
  
 1. WHILE SHEET P3-2 FIXTURE TABLE LISTS P-2 AS A
 REGULAR WATER CLOSET P-3 AS A WALL HUNG LAV.
 A. SHEET P2-2 SHOWS REGULAR WATER CLOSETS AS P-3 AND
 WALL HUNG LAVS. AS P-2
 B. SHEET P3-3 SHOWS THE MEZZANINE A REGULAR WATER
 CLOSET (2 WC'S ARE MISSING) AS P-3 AND 2 WALL HUNG LAVS
 AS P-2
 C. SHEET P3-3 THE WATER PIPE ISO SHOWS 3 WC'S AS P-3 ,
 ALSO THE WALL HUNG LAVS APPEAR TO BE MISSING.
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  

Review Stop P PLUMBING
Rev No 4 Status F Date 2012-04-25 Cont ID  
Sent By lwagner Date 2012-04-25 Time 15:27 Rev Time 0.00
Received By lwagner Date 2012-04-25 Time 12:37 Sent To  
Notes
2012-04-25 14:46:58FBC 2007 PLUMBING REVIEW #4
 DENIED:
  
 FROM LAST REVIEW:
  
 2. THE SUMP PUMP SHOWN WILL BE REQUIRED TO CONNECT
 INDIRECTLY (TO A FLOOR DRAIN OR HUB DRAIN) TO THE
 **SANITARY** USING THE OIL SMART CONTROLS SHOWN ON
 P3-1.
 WITH THE USE OF THE OIL SMART CONTROLS, THE OIL
 INTERCEPTOR WOULD NOT BE REQUIRED.
 301.6 PROHIBITED LOCATIONS. PLUMBING SYSTEMS SHALL NOT
 BE LOCATED IN AN ELEVATOR SHAFT OR IN AN ELEVATOR
 EQUIPMENT ROOM.
 EXCEPTION: FLOOR DRAINS, SUMPS AND SUMP PUMPS SHALL BE
 PERMITTED AT THE BASE OF THE SHAFT PROVIDED THEY ARE
 ***INDIRECTLY*** CONNECTED TO THE PLUMBING SYSTEM.
 THE SUMP LINE WILL NOT BE CONNECTED TO THE STORM SYSTEM
 - CITY UTILITY CODE 90-203 (A)
  
 PLEASE CORRECT THE FOLLOWING:
  
 1. WHILE SHEET P3-2 FIXTURE TABLE LISTS P-2 AS A
 REGULAR WATER CLOSET P-3 AS A WALL HUNG LAV.
 A. SHEET P2-2 SHOWS REGULAR WATER CLOSETS AS P-3 AND
 WALL HUNG LAVS. AS P-2
 B. SHEET P3-3 SHOWS THE MEZZANINE A REGULAR WATER
 CLOSET (2 WC'S ARE MISSING) AS P-3 AND 2 WALL HUNG LAVS
 AS P-2
 C. SHEET P3-3 THE WATER PIPE ISO SHOWS 3 WC'S AS P-3 ,
 ALSO THE WALL HUNG LAVS APPEAR TO BE MISSING.
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  
  
  
  

Review Stop P PLUMBING
Rev No 3 Status F Date 2012-03-01 Cont ID  
Sent By lwagner Date 2012-03-01 Time 14:54 Rev Time 0.00
Received By lwagner Date 2012-03-01 Time 10:05 Sent To  
Notes
2012-03-01 13:26:10FBC PLUMBING 2007 REVIEW #2
 DENIED:
  
 1. THE LATEST SUBMITTED PLANS DATED 2/16/12 DO NOT
 INCLUDE PLUMBING DRAWINGS.
  
 OLD P3-3 ISOMETRIC DRAWINGS DO NOT REFLECT THE NEW
 P2-1- P2-2 PLUMBING DRAWINGS. NEW P3-3 ISOMETRICS WERE
 NOT INCLUDED WITH RE-SUBMITTAL DRAWINGS.
  
 2. THE SUMP PUMP SHOWN WILL BE REQUIRED TO CONNECT
 INDIRECTLY (TO A FLOOR DRAIN OR HUB DRAIN) TO THE
 **SANITARY** USING THE OIL SMART CONTROLS SHOWN ON
 P3-1.
 WITH THE USE OF THE OIL SMART CONTROLS, THE OIL
 INTERCEPTOR WOULD NOT BE REQUIRED.
 301.6 PROHIBITED LOCATIONS. PLUMBING SYSTEMS SHALL NOT
 BE LOCATED IN AN ELEVATOR SHAFT OR IN AN ELEVATOR
 EQUIPMENT ROOM.
 EXCEPTION: FLOOR DRAINS, SUMPS AND SUMP PUMPS SHALL BE
 PERMITTED AT THE BASE OF THE SHAFT PROVIDED THEY ARE
 INDIRECTLY CONNECTED TO THE PLUMBING SYSTEM.
 THE SUMP LINE WILL NOT BE CONNECTED TO THE STORM SYSTEM
 - CITY UTILITY CODE 90-203 (A)
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  
  
  
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2012-03-01 Cont ID  
Sent By lwagner Date 2012-01-11 Time 14:51 Rev Time 0.00
Received By lwagner Date 2012-01-11 Time 09:14 Sent To  
Notes
2012-01-11 11:21:53OWNER REMOVED PLANS. SEE FRONT SCREEN
  
 1. OLD P-3.3 ISOMETRIC DRAWINGS DO NOT MATCH WITH NEW
 PLUMBING DRAWINGS. NEW P-3.3 ISOMETRICS WERE NOT
 INCLUDED WITH RE-SUBMITTAL DRAWINGS.
  
 2. FIXTURE DESIGNATION NUMBERS ARE CROSSED. FOR EXAMPLE
 - P-2 IS WC ON ONE PAGE AND LAV ON ANOTHER.
  
 3. OCC

Review Stop P PLUMBING
Rev No 1 Status F Date 2011-05-27 Cont ID  
Sent By lwagner Date 2011-05-27 Time 14:12 Rev Time 0.00
Received By lwagner Date 2011-05-24 Time 07:55 Sent To  
Notes
2011-05-24 08:28:32FBC PLUMBING 2007 REVIEW #1
 DENIED:
  
 MORE INFORMATION REQUESTED:
 1. SHEET A-1.0 BUILDING AND CODE INFORMATION CALLS FOR
 OCCUPANCY A-2, BUT GIVES NO OCCUPANT LOAD.
 THE NUMBER OF OCCUPANTS IS NEEDED FOR A FIXTURE COUNT.
 THE 2ND FLOOR SHOWS NO FACILITIES. IN THAT CASE THE
 FIXTURES ON THE MEZZANINE WOULD BE USED BY THE
 OCCUPANTS ON THE 2ND FLOOR
  
 2. MENS ADA RESTROOM ON SHEET A-41 DOES NOT MEET THE
 REQUIREMENTS FOR 11-4.17.3 SIZE AND ARRANGEMENT. THE
 SIZE AND ARRANGEMENT OF THE STANDARD TOILET STALL SHALL
 COMPLY WITH FIGURE 30(A)
  
 3. 403.7 UNISEX TOILET ROOM MAY, DEPENDING UPON FIXTURE
 COUNT, BE REQUIRED.
 403.7 UNISEX TOILET AND BATHING ROOMS. IN ASSEMBLY AND
 MERCANTILE OCCUPANCIES, AN ACCESSIBLE UNISEX TOILET
 ROOM SHALL BE PROVIDED WHERE AN AGGREGATE OF SIX OR
 MORE MALE AND FEMALE WATER CLOSETS IS REQUIRED.
  
 4. SHEET P3-1 ELEVATOR SUMP PUMP DETAIL DOES NOT SHOW
 THE SUMP PUMP OR PIPEING. FBC 3001.2 REFRENCED
 STANDARDS ASME A17.1 WHERE DRAINS ARE NOT PROVIDED TO
 PREVENT THE ACCUMULATION OF WATER, SUMP PUMPS SHALL BE
 PROVIDED.
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  

Review Stop Z ZONING
Rev No 1 Status P Date 2011-06-01 Cont ID  
Sent By aaponte Date 2011-06-01 Time 10:16 Rev Time 0.00
Received By aaponte Date 2011-06-01 Time 10:16 Sent To  
Notes
***NONE***