Plan Review Details - Permit 11050554
Plan Review Stops For Permit 11050554
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2011-07-20 Cont ID  
Sent By jwitmer Date 2011-07-20 Time 11:29 Rev Time 0.33
Received By jwitmer Date 2011-07-20 Time 11:29 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2011-06-10 Cont ID  
Sent By jwitmer Date 2011-06-10 Time 13:34 Rev Time 2.20
Received By jwitmer Date 2011-06-10 Time 11:04 Sent To  
Notes
2011-06-10 13:34:19BUILDING PLAN REVIEW
 PERMIT: 11050554
 ADD: 1601 BELVEDERE RD
 CONT: TO BE DETERMINED
 TEL: (561)###-####
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 FRONT COUNTER TO VERIFY LICENSURE.
  
 1) CONTRACTOR TO BE SIGNEDONTO THE PERMIT AND LICENSURE
 VERIFIED BEFORE THE ISSUANCE OF PERMIT.
  
 PROVISOS:
 2) RECEPTION DESK A3.3 DETAILS 1A, 2A & 2C DO NOT
 INDICATE COMPLIANCE WITH 2007/09 FBC-B 11-4-7. 2(2).
  
 3) GUEST LAUNDRY A-1.6, A2.3 VENDING MACHINE LOCATED ON
 WALL DOES NOT PROVIDE COMPLIANCE WITH 2007/09 FBC-B
 11-4.27 (1-4) .
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2011-06-21 Cont ID  
Sent By rlecky Date 2011-06-21 Time 08:41 Rev Time 0.00
Received By rlecky Date 2011-06-20 Time 15:38 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2011-07-25 Cont ID  
Sent By wjolin Date 2011-07-25 Time 10:54 Rev Time 0.00
Received By wjolin Date 2011-07-25 Time 10:10 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2011-06-15 Cont ID  
Sent By wjolin Date 2011-06-15 Time 11:50 Rev Time 0.00
Received By wjolin Date 2011-06-15 Time 10:24 Sent To  
Notes
2011-06-15 11:26:091601 BELVEDERE ROAD
 PERMIT #11050554
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SEPARATE PLANS AND PERMITS REQUIRED FOR FIRE ALARM AND
 FIRE SPRINKLER WORK.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-08-10 Cont ID  
Sent By rregueir Date 2011-08-10 Time 14:41 Rev Time 0.00
Received By rregueir Date 2011-07-18 Time 14:40 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-08-10 Cont ID  
Sent By rregueir Date 2011-06-20 Time 14:40 Rev Time 0.00
Received By rregueir Date 2011-05-18 Time 15:52 Sent To  
Notes
2011-05-18 15:53:04INCOMING SENT TO RON REGUEIRO DESK. JW

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2011-08-10 Cont ID  
Sent By rregueir Date 2011-08-10 Time 14:37 Rev Time 0.00
Received By rregueir Date 2011-08-10 Time 14:37 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2011-06-20 Cont ID  
Sent By rregueir Date 2011-06-20 Time 09:55 Rev Time 0.00
Received By rregueir Date 2011-06-20 Time 09:35 Sent To  
Notes
2011-06-20 09:54:59REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PAGE M-2.2: DRYER EXHAUST IS SHOWN BEING ROUTED
 THROUGH A RETURN AIR PLENUM CEILING SPACE. EXHAUST
 TUCTS UNDER POSITIVE PRESSURE SHALL NOT PASS THROUGH A
 PLENUM PER FBC-M 601.5.
  
 2. PAGE M-2.2: PLAN SHOWS A DRYER BOOSTER FAN TO BE
 USED. PROVIDE DRYER MANUFACTURER'S INSTALLATION
 INSTRUCTIONS SHOWING THAT A BOOSTER FAN MAY BE USED
 WITH THESE SPECIFIC DRYERS. CLOTHES DRYERS SHALL BE
 EXHAUSTED IN ACCORDANCE WITH THE DRYER MANUFACTURER'S
 INSTRUCTIONS PER FBC-M 504.1.
  
 3. PAGE M-2.2 SHOWS TWO DRYER EXHAUST DUCTS BEING
 MANIFOLDED INTO ONE DUCT. NO DUCT SIZES ARE PROVIDED ON
 PLAN. THIS CONDITION MUST ALSO BE COVERED BY THE DRYER
 MANUFACTURER'S INSTALLATION INSTRUCTIONS PER FBC-M
 504.1.
  
 4. PAGE M-2.2: PLAN CALLS FOR DRYER EXHAUST TO
 TERMINATE AT A GRS-8 ROOF VENT. WHERE WILL THE
 BACKDRAFT DAMPER FOR THE DRYER EXHAUST BE LOCATED? IS
 THE GRS-8 ROOF VENT OPENING SCREENED? BACKDRAFT DAMPER
 IS REQUIRED ON DRYER EXHAUST DUCT OUTLETS AND SCREENS
 ARE PROHIBITED PER FBC-M 504.4.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status P Date 2011-06-20 Cont ID  
Sent By lwagner Date 2011-06-20 Time 10:33 Rev Time 0.00
Received By lwagner Date 2011-06-08 Time 11:59 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2011-08-22 Cont ID  
Sent By rregueir Date 2011-08-22 Time 13:37 Rev Time 0.00
Received By rregueir Date 2011-08-22 Time 13:37 Sent To  
Notes
***NONE***