| 2011-10-20 11:44:47 | ****CORRECTIONS**** |
| | (REVISED 11/7/11) |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | FBC FLORIDA BUILDING CODE 2007 |
| | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL |
| | |
| | COMMENTS FROM PREVIOUS LIST: |
| | |
| | 1. PROVIDE MORE INFORMATION REGARDING THE OCCUPANCY OF |
| | THIS BUILDING. SEE ZONING COMMENTS. IF A CHANGE OF |
| | OCCUPANCY IS INVOLVED, SHOW COMPLIANCE. |
| | |
| | 2ND REVIEW, LETTER STATES THAT THERE IS NO BATHROOM OR |
| | KITCHEN, OWNER USING THE ADJACENT SPACE FOR STORAGE. |
| | HOWEVER, THERE IS A CURRENT BUSINESS TAX FOR APARTMENT, |
| | AND ARCHITECT'S PROPOSED SITE PLAN SHOWS THIS AS AN |
| | APARTMENT. IT APPEARS THAT A CHANGE OF OCCUPANCY WAS |
| | DONE WITHOUT PERMIT. PLEASE INCLUDE THE CONVERSION OF |
| | THE RESIDENTIAL SPACE TO STORAGE OCCUPANCY IN THE SCOPE |
| | OF THIS PERMIT. SEE FBC EXISTING BUILDING CODE FOR |
| | REQUIREMENTS FOR A CHANGE OF OCCUPANCY. |
| | |
| | COURTESY REVIEW 11/7/11 - PER ADDRESSING, THIS ADDRESS |
| | WAS IMPROPERLY USED BY ANOTHER ENTITY AND LOCATION. |
| | PLEASE CONSIDER THE COMMENT REGARDING CHANGE OF |
| | OCCUPANCY AS RESOLVED. |
| | |
| | 2. REVISE EXPOSURE CATEGORY OR PROVIDE RATIONAL |
| | ANALYSIS CALCULATIONS FOR USE OF EXPOSURE B PRESSURES. |
| | FBC1609, FBC R301.2.1.4. NOTE THAT THE CODE CHANGED |
| | EFFECTIVE MARCH 1, 2009. |
| | |
| | PLANS STILL STATE EXPOSURE B, PLEASE ADDRESS PREVIOUS |
| | COMMENT. DESIGN PRESSURES ON A4 TOO LOW FOR EXPOSURE C. |
| | LETTER REFERS TO SP1, CANNOT LOCATE THIS SHEET IN |
| | PERMIT PACKAGE. |
| | |
| | 3. IMPACT PROTECTION REQUIRED,FBC1609.1.4, ALSO SEE |
| | ARCHITECT'S REQUIREMENTS ON SHEET A3. NON IMPACT |
| | PRODUCT APPROVALS SUBMITTED. |
| | |
| | 2ND REVIEW, IMPACT PRODUCT APPROVALS SUBMITTED. |
| | HOWEVER, PLEASE NOTE THE FOLLOWING:\ |
| | |
| | PGT FRENCH DOOR PRODUCT APPROVALS SUBMITTED, NOT CLEAR |
| | WHERE THIS WILL BE INSTALLED, AND THIS BRAND IS |
| | INTENDED FOR RESIDENTIAL USE AND DOES NOT COMPLY WITH |
| | THE REQUIREMENTS OF FBC CHAPTER 11 (SEE THRESHOLD |
| | HEIGHT ON PRODUCT APPROVAL, ALSO PER MANUFACTURER). |
| | |
| | 4. SEE OTHER COMMENT REGARDING THE OCCUPANCY OF THIS |
| | BUILDING. PLANS STATE THAT THIS IS AN "EXISTING |
| | SHOWROOM" WHICH WOULD IMPLY MERCANTILE. NON IMPACT |
| | RESIDENTIAL DOOR PRODUCT APPROVAL WAS SUBMITTED. |
| | ARCHITECT HAS SPECIFIED PANIC BARS. THIS IS NOT |
| | INCLUDED IN THE PRODUCT APPROVAL. SILL HEIGHT ON THE |
| | DOOR PRODUCT APPROVAL EXCEEDS THE DIMENSION PERMITTED |
| | BY FBC11-4.5.2, PRODUCT APPROVAL DOES NOT INCLUDE PANIC |
| | BARS. |
| | |
| | IT APPEARS THAT PROPOSED USE (OR PERHAPS EXISTING USE, |
| | DONE WITHOUT PERMIT) IS MERCANTILE, BUSINESS, AND |
| | STORAGE. REVISE PLAN TO SHOW COMPLIANCE WITH CHANGE OF |
| | OCCUPANCY FROM RESIDENTIAL TO STORAGE, SEE OTHER |
| | COMMENTS. SEE FBC EXISTING BUILDING CHAPTER 9. IF YOU |
| | BELIEVE THAT A CHANGE OF OCCUPANCY WAS DONE PREVIOUSLY |
| | THROUGH THE BUILDING DEPARTMENT AS REQUIRED BY FBC |
| | 105.1, PLEASE PROVIDE DOCUMENTATION (PERMIT NUMBER) AND |
| | EXPLAIN THE APARTMENT BUSINESS TAX RECEIPT (FORMERLY |
| | CALLED "OCCUPATIONAL LICENSE") FOR THIS STRUCTURE. |
| | |
| | COURTESY REVIEW 11/7/11 - PER ARCHITECT, BUILDING IS |
| | EXISTING; MERCANTILE, BUSINESS, AND STORAGE. |
| | |
| | 5-7. ADDRESSED. |
| | |
| | NEW COMMENTS: |
| | |
| | 8. SLIDING DOORS ARE NOW SHOWN IN THE PLAN, SHOW |
| | COMPLIANCE WITH FBC1008.1.3.3. THE SLIDING GLASS DOOR |
| | PRODUCT APPROVAL IS A RESIDENTIAL DOOR, PLEASE SUBMIT |
| | APPROPRIATE PRODUCT APPROVAL. |
| | |
| | 9. AS NO MECHANICAL INFORMATION WAS PROVIDED, |
| | MECHANICAL REVIEW WILL NOT BE DONE ON THIS REVIEW. |
| | PLEASE PROVIDE INFORMATION TO SHOW COMPLIANCE WITH FBC |
| | EXISTING BUIDLING 709.1 AND 909 (EXHAUST FOR BATHROOMS, |
| | VENTILATION (OUTDOOR AIR) FBC MECHANICAL CHAPTER 4). |
| | |
| | COURTESY REVIEW 11/7/11, N/A (PLEASE DISREGARD #9) |
| | |
| | 10. PROVIDE A DETAIL FOR THE RAMP, FBC 11-4.8. ALSO SEE |
| | MANEUVERING CLEARANCE FOR DOORS, FBC 11 FIGURE 25 AND |
| | REVISE PLAN TO SHOW MINIMUM DIMENSIONS. |
| | |
| | 11. PROVIDE A COST BREAKDOWN FOR THIS JOB, SEE FBC |
| | 11-4.1.6(2). |
| | |
| | |
| | |