| 2011-05-11 16:17:52 | COMMERCIAL BUILDING RE-ROOF BUILDING REVIEW CHECKLIST. |
| | 2007 FBC WITH 2009 REVISIONS. |
| | |
| | 1- PROVIDE FIELD WITHDRAWAL RESISTANCE TEST (TAS 105) |
| | RESULTS AS REQUIRED BY SYSTEM LIMITATION #1 ON LAST |
| | PAGE OF NOA 08-0410.01 SUBMITTED. TESTS RESULTS ARE |
| | REQUIRED TO DO THE RAS 117 CALCULATIONS. |
| | |
| | 2- ENGINEER TO REVISE THE RAS 117 CALCULATIONS |
| | SUBMITTED USING THE WITHDRAWAL RESISTANCE TEST RESULTS. |
| | SEE TAS 105. |
| | |
| | 3- CONTRACTOR HIGHLIGHTED BASE SHEET FASTENING OPTION |
| | #2 ON PAGE 7 OF THE NOA 08-0410.01 SUBMITTED. ENGINEER |
| | RAS 117 CALCULATIONS SUBMITTED ARE DONE CONSIDERING |
| | BASE SHEET FASTENING OPTION #4. REVISE AS REQUIRED TO |
| | MATCH. |
| | |
| | 4- CLARIFY WHY SUBMITTING NOA FOR SKYLIGHTS. PERMIT |
| | APPLICATION DOESN'T DESCRIBE SKYLIGHTS INSTALLATION. IF |
| | SO, CLARIFY IF REPLACING EXISTING SKYLIGHTS AND HOW |
| | MANY? REVISE PERMIT VALUATION ACCORDINGLY. SEC. 108.3 |
| | CITY AMENDMENTS TO FBC. |
| | |
| | 5- PERMIT VALUATION DECLARED IN THE PERMIT APPLICATION |
| | IS TOO LOW. VALUATION WAS UPDATED TO $45000. SEC. 108.3 |
| | CITY AMENDMENTS TO FBC. PERMIT FEE BALANCE DUE IS |
| | $1230.20. |
| | |
| | 6- CONTRACTOR SHOWN ON THE NOTICE OF COMMENCEMENT |
| | DOESN'T MATCH CONTRACTOR SHOWN ON THE PERMIT |
| | APPLICATION. REVISE AS REQUIRED TO MATCH. |
| | |
| | 7- FOR YOUR INFORMATION: ANY ROOF EQUIPMENT REMOVAL |
| | REQUIRES SEPARATE BUILDING PERMITS. |
| | |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561)805-6712 |