| Plan Review Stops For Permit 11050338 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2011-06-06 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2011-06-06 |
Time |
08:09 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2011-06-06 |
Time |
08:09 |
Sent To |
|
|
| Notes |
| 2011-06-06 08:10:19 | PROCESS PLANS |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2011-05-24 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2011-05-24 |
Time |
13:07 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2011-05-24 |
Time |
07:30 |
Sent To |
|
|
| Notes |
| 2011-05-24 13:11:12 | BUILDING PROVISO | | | | | | PROVIDE TWO COPIES OF FLORIDA OR MIAMI-DADE PRODUCT | | | APPROVALS FOR THE USP PA 28 CONNECTORS AS REQUIRED BY | | | DCA RULE 9B-72. | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2011-05-13 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2011-05-13 |
Time |
11:55 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2011-05-13 |
Time |
07:03 |
Sent To |
|
|
| Notes |
| 2011-05-13 11:54:01 | 2007 FBC W/2009 REVISIONS | | | | | | DENIED BY BUILDING | | | | | | 1) SUBMIT A COPY OF THE PAID RECEIPT FOR THE COUNTY | | | IMPACT FEES. | | | | | | 2) FBC R401.4 AREA OF QUESTIONABLE | | | SOIL. SUBMIT A GEOTECHNICAL REPORT | | | TO VERIFY THE SAFE BEARING CAPACITY OF | | | THE SOIL. | | | | | | 3) SPECIFY THE DESIGN CRITERIA ON THE PLANS. SPECIFY | | | WINDSPEED (140 MPH, 3 SECOND GUST), EXPOSURE CATEGORY | | | (C), MEAN ROOF HEIGHT, ROOF LOADS, ETC. SEE FBC R301.1 | | | | | | 4) UPDATE THE MASONRY NOTES ON C-1 FOR ACI/ASCE/TMS | | | FROM THE 99 TO THE 05 EDITIONS FBC R REFERENCED | | | STANDARDS IN CHAPTER 43. | | | | | | 5) PROVIDE THE BASE PLATE DESIGN AND ANCHORING | | | REQUIREMENTS FOR THE STEEL COLUMNS (C-5). CITY | | | AMENDMENTS* 106.1.2 AND FBC R407.3 | | | | | | 6) SUBMIT 2 SETS OF PRODUCT APPROVALS FOR THE SLIDING | | | GLASS DOORS, THE 8" LINTELS AND TRUSS CONNECTORS AS | | | REQUIRED BY DCA RULE 9B-72. | | | | | | 7) THE PRODUCT APPROVAL NOAS FOR THE SINGLE OVERHEAD | | | GARAGE DOOR, THE PW-701 FIXED WINDOWS AND THE SH-700 | | | SINGLE HUNG WINDOWS HAVE BEEN SUPERSEDED ACCORDING TO | | | THE MIAMI-DADE PRODUCT CONTROL WEB-SITE. PLEASE SUBMIT | | | TWO SETS OF CURRENT PRODUCT APPROVALS FOR THESES ITEMS. | | | NOTE: THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED | | | AND APPROVED BY THE DESIGNER OF RECORD. CITY AMENDMENTS | | | 106.3.3 | | | | | | 8) PLEASE PROVIDE A RESPONSE LETTER INDICATING HOW EACH | | | COMMENT HAS BEEN ADDRESSED. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2011-05-24 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2011-05-24 |
Time |
07:41 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2011-05-24 |
Time |
07:41 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2011-05-13 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2011-05-13 |
Time |
08:10 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2011-05-13 |
Time |
08:10 |
Sent To |
|
|
| Notes |
| 2011-05-13 08:46:20 | 2007 FBC W/2009 REVISIONS | | | 2008 NEC | | | | | | DENIED BY ELECTRICAL | | | | | | 1) REVISE LOAD CALCULATIONS AND PANEL SCHEDULE TO | | | INCLUDE THE THIRD AHU HEAT STRIP AND A/C COMPRESSOR. | | | NEC 220.40 | | | | | | 2) REVISE THE ARC-FAULT CIRCUIT-INTERRUPTER PROTECTION | | | NOTE ON SHEET C-1. NEC 210.12 REQUIRES ARC-FAULT | | | PROTECTION ON ALL 120-VOLT, SINGLE PHASE 15 AND 20 AMP | | | BRANCH CIRCUITS SUPPLYING OUTLETS DWELLING UNITS. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
P |
Date |
2011-05-23 |
|
|
Cont ID |
|
| Sent By |
BRM |
Date |
2011-05-23 |
Time |
09:50 |
Rev Time |
0.00 |
| Received By |
bmoree |
Date |
2011-05-23 |
Time |
09:47 |
Sent To |
Z |
|
| Notes |
| 2011-05-23 09:49:51 | PASSED WITH PROVISO | | | NO CONFLICT WITH UTILITIES | | | | | | 1. SEPARATE DRIVEWAY PERMIT REQUIRED. | | | | | | BRIAN R. MOREE | | | CITY OF WEST PALM BEACH | | | ENGINEERING SERVICES | | | 401 CLEMATIS STREET | | | WEST PALM BEACH, FLORIDA 33401 | | | 561-494-1098 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2011-06-16 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2011-06-16 |
Time |
13:06 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2011-06-10 |
Time |
10:23 |
Sent To |
|
|
| Notes |
| 2011-06-10 10:23:16 | IN ZONING BOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2011-06-03 |
|
|
Cont ID |
|
| Sent By |
lfranco |
Date |
2011-06-02 |
Time |
19:08 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2011-05-22 |
Time |
11:33 |
Sent To |
|
|
| Notes |
| 2011-05-24 13:12:40 | COMPLETED REVIEW OF RESUBMITTED ITEMS AND GAVE TO L. | | | MARTINEZ ON 5/24/11. | | 2011-05-22 11:33:30 | GAVE TO ROBBIE |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2011-06-03 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2011-06-03 |
Time |
15:20 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2011-05-13 |
Time |
07:05 |
Sent To |
|
|
| Notes |
| 2011-05-13 07:05:33 | EXPEDITED PLAN SENT TO R.MCDOUGAL |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
P |
Date |
2011-05-24 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2011-05-24 |
Time |
07:10 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2011-05-24 |
Time |
07:10 |
Sent To |
|
|
| Notes |
| 2011-05-24 07:11:47 | MU-2011-008290 |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2011-05-13 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2011-05-13 |
Time |
07:03 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2011-05-13 |
Time |
07:03 |
Sent To |
|
|
| Notes |
| 2011-05-13 07:04:28 | SUBMIT A COPY OF THE PAID RECEIPT FOR THE IMPACT FEES. |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
2 |
Status |
P |
Date |
2011-06-02 |
|
|
Cont ID |
|
| Sent By |
ajones |
Date |
2011-06-02 |
Time |
15:26 |
Rev Time |
0.00 |
| Received By |
ajones |
Date |
2011-06-02 |
Time |
15:25 |
Sent To |
|
|
| Notes |
| 2011-06-02 15:30:13 | APPROVED WITH THE PROVISO THAT A SEPERATE LANDSCAPE AND | | | IRRIGATION PERMITS IS REQUIRED TO BE APPLIED FOR, | | | APPROVED AND INSTALLED PRIOR TO THE ISSUANCE OF A CO. |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
1 |
Status |
F |
Date |
2011-05-27 |
|
|
Cont ID |
|
| Sent By |
rkussner |
Date |
2011-05-27 |
Time |
19:09 |
Rev Time |
0.00 |
| Received By |
rkussner |
Date |
2011-05-27 |
Time |
19:09 |
Sent To |
|
|
| Notes |
| 2011-05-27 19:17:37 | ***LANDSCAPE REVIEW FAILED*** | | | | | | PLEASE RESPOND TO REVIEW COMMENTS IN WRITTEN FORMAT. | | | | | | 1. PLEASE APPLY FOR A SEPARATE LANDSCAPE PERMIT. SUBMIT | | | TWO (2) COPIES OF A LANDSCAPE PLAN SHOWING COMPLIANCE | | | WITH SECTIONS 94-442 AND 94-445 OF THE ZLDR AND A | | | CERTIFIED COST ESTIMATE THAT INCLUDES THE TOTAL COST OF | | | ALL LANDSCAPE MATERIALS AND LABOR, BROKEN DOWN INTO | | | UNIT COST. | | | | | | 2. PLEASE PROVIDE THE TABULATION NECESSARY FOR THE | | | EVALUATION OF COMPLIANCE WITH ARTICLE XIV OF THE ZONING | | | AND LAND DEVELOPMENT REGULATIONS, INCLUDING THE | | | XERISCAPE DESIGN OPTIONS. | | | | | | 3. A SEPARATE IRRIGATION PERMIT IS REQUIRED ALONG WITH | | | TWO SETS OF IRRIGATION PLANS. | | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT | | | KUSSNER @ (561) 822-1462. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2011-05-12 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2011-05-12 |
Time |
12:16 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2011-05-12 |
Time |
07:45 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2011-05-24 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2011-05-24 |
Time |
07:30 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2011-05-24 |
Time |
07:12 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2011-05-12 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2011-05-12 |
Time |
07:21 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2011-05-12 |
Time |
06:39 |
Sent To |
|
|
| Notes |
| 2011-05-12 07:45:26 | 2007 FBC W/2009 REVISIONS | | | | | | DENIED BY PLUMBING | | | | | | 1) THE SANITARY ISOMETRIC RISER DIAGRAM DOES NOT | | | CORRESPOND WITH THE FLOOR PLAN. THE FLOOR PLAN SHOWS | | | TWO HALF BATHS, THE CABANA BATH IS SHOWN BUT THE | | | LAVATORY AND WATER CLOSET LOCATED IN THE POWDER ROOM IS | | | NOT. THE LAUNDRY TUB IS INCORRECTLY LABELED AS A | | | LAVATORY. PLEASE CORRECT. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2011-06-15 |
|
|
Cont ID |
|
| Sent By |
lfranco |
Date |
2011-06-15 |
Time |
18:32 |
Rev Time |
1.50 |
| Received By |
lfranco |
Date |
2011-06-10 |
Time |
16:12 |
Sent To |
I |
|
| Notes |
| 2011-06-15 18:34:41 | PLANNING AND ZONING: **** PASSED WITH PROVISO: THE | | | APPLICANT SHALL APPLY FOR AN IRRIGATION AND LANDSCAPE | | | PERMIT, GET IT APPROVED AND SUCCESSFULLY INSPECTED | | | PRIOR TO CERTIFICATE OF OCCUPANCY ("CO"). **** | | | | | | | | | | | | | | | LINDA MIA FRANCO | | | SENIOR PLANNER | | | PLANNING AND ZONING | | | TEL: (561) 822-1443 | | | EMAIL: [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2011-06-02 |
|
|
Cont ID |
|
| Sent By |
lfranco |
Date |
2011-05-31 |
Time |
10:12 |
Rev Time |
1.00 |
| Received By |
lfranco |
Date |
2011-05-18 |
Time |
14:35 |
Sent To |
I |
|
| Notes |
| 2011-06-02 19:08:55 | PLANNING AND ZONING: **** FAILED ***** | | | | | | | | | 1. RESPOND TO COMMENTS IN WRITING. RESUBMITTAL MAY | | | GENERATE ADDITIONAL COMMENTS. | | | | | | 2. INDICATE SETBACK DIMENSIONS FROM PROPOSED A/C | | | EQUIPMENT TO ALL PROPERTY LINES. PURSUANT TO SECTION | | | 94-305(B)(4) OF THE ZLDR: MECHANICAL EQUIPMENT MAY NOT | | | PROJECT MORE THAN 4 FEET INTO A REQUIRED SETBACK. | | | | | | 3. PURSUANT TO SECTION 94-482 OF THE ZLDR: REQUIRED | | | OFF-STREET PARKING SPACES FOR LESS THAN FOUR | | | RESIDENTIAL DWELLING UNITS SHALL BE LOCATED ON THE | | | PROPERTY ON WHICH THE UNITS ARE CONSTRUCTED. REQUIRED | | | PARKING MAY BE LOCATED IN A FRONT YARD; HOWEVER, THE | | | LESSER OF 1,000 SQUARE FEET OR 75 PERCENT OF THE FRONT | | | YARD AREA MUST BE LANDSCAPED. PARKING AREAS LOCATED IN | | | THE FRONT YARD SHALL BE SURFACED WITH A SMOOTH, | | | NONDUSTING SURFACE IN COMPLIANCE WITH SUBSECTION | | | 33-485(E). IT SHALL BE A VIOLATION OF THIS CHAPTER TO | | | PARK ON ANY UNPAVED AREAS AS DESCRIBED IN THIS ARTICLE. | | | | | | INDICATE SQUARE FOOTAGE OF ALL IMPERMEABLE SURFACES | | | (EXISTING AND PROPOSED) LOCATED WITHIN THE FRONT YARD | | | (FROM FRONT PROPERTY LINE TO THE FRONT BUILDING | | | FACADE). THE MAXIMUM WIDTH FOR A DRIVEWAY IS 20 FEET IN | | | WIDTH. THERE ARE NO DIMENSIONS ON THE PROPOSED | | | DRIVEWAY. ALSO, CALCULATIONS FOR THE FRONT AREA NEED TO | | | BE PROVIDED BETWEEN THE FIRST 25 FEET OF LOT DEPTH FROM | | | THE FRONT PROPERTY LINE MULTIPLIED BY THE TOTAL WIDTH | | | OF THE PROPERTY (I.E. 25 FEET X WIDTH OF THE LOT = X | | | SQ. FT. X .75 = X SQ. FT) SINCE THE SQUARE FOOTAGE | | | EXCEEDS 1,000 SQ. FT. THE APPLICANT WILL ONLY BE | | | REQUIRED TO MEET THE MINIMUM 1,000 SQ. FT LANDSCAPE | | | AREA. SHOW CALCULATIONS OF LANDSCAPE AREA SQUARE | | | FOOTAGE ON SURVEY AND/OR PLANS. | | | | | | SHOW ALL DIMENSIONS OF THE DRIVEWAY AND WHAT THE | | | MATERIAL WILL BE (I.E. PAVERS OVER SAND, CONCRETE | | | (NON-PERVIOUS), PAVERS OVER CONCRETE SLAB ARE | | | CONSIDERED NON-PERVIOUS). NON-PERVIOUS MATERIAL WILL | | | NOT BE COUNTED TOWARDS MEETING THE LANDSCAPE AREA | | | (PERVIOUS AREAS). | | | | | | 4. THE PROPOSED DRIVEWAY ENCROACHES WITHIN THE UTILITY | | | EASEMENT; EASEMENT CONSENT FORMS ARE REQUIRED FROM THE | | | FOLLOWING UTILITY COMPANIES: | | | | | | WEST PALM BEACH PUBLIC UTILITIES DEPARTMENT | | | 401 CLEMATIS STREET | | | CITY HALL, 4TH FLOOR | | | WEST PALM BEACH, FL 33401 | | | (561)822-1300 | | | | | | FLORIDA POWER AND LIGHT | | | 810 CHARLOTTE AVE | | | WEST PALM BEACH, FL 33401 | | | (561)697-8000 | | | | | | FLORIDA PUBLIC UTILITIES | | | 401 SOUTH DIXIE HWY | | | WEST PALM BEACH, FL 33402 | | | (561)832-2461 | | | | | | BELL SOUTH | | | 2021 SOUTH MILITARY TRAIL | | | WEST PALM BEACH, FL 33415 | | | (561)439-9110 | | | | | | COMCAST | | | 1401 NORTHPOINT PKWY | | | WEST PALM BEACH, FL 33407 | | | (561)655-3842 - RESIDENTIAL | | | (561)227-4261 - COMMERCIAL | | | | | | | | | 5. A SEPARATE LANDSCAPE PERMIT SHALL BE APPLIED FOR | | | WITH ALL REQUIREMENTS SET FORTH IN THE LANDSCAPE REVIEW | | | STOP OF THIS PERMIT. THE PERMIT SHALL BE SUBMITTED | | | CONCURRENTLY WITH THIS PERMIT AND PRIOR TO FINAL CO | | | APPROVAL FROM THE PLANNING ZONING DEPARTMENT AND | | | LANDSCAPING INSPECTION. | | | | | | 6. THE POOL/FENCE AND OTHER IMPROVEMENTS REQUIRE A | | | SEPARATE PERMIT AND WILL NOT BE PART OF THIS PERMIT | | | REVIEW. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME. | | | | | | LINDA MIA FRANCO | | | SENIOR PLANNER | | | PLANNING AND ZONING DEPARTMENT | | | TEL: (561) 822-1443 | | | EMAIL: [email protected] | | | | | | | | | | | | | | | |
|
|