Plan Review Details - Permit 11050338
Plan Review Stops For Permit 11050338
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2011-06-06 Cont ID  
Sent By rmcdouga Date 2011-06-06 Time 08:09 Rev Time 0.00
Received By rmcdouga Date 2011-06-06 Time 08:09 Sent To  
Notes
2011-06-06 08:10:19PROCESS PLANS

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2011-05-24 Cont ID  
Sent By rmcdouga Date 2011-05-24 Time 13:07 Rev Time 0.00
Received By rmcdouga Date 2011-05-24 Time 07:30 Sent To  
Notes
2011-05-24 13:11:12BUILDING PROVISO
  
 PROVIDE TWO COPIES OF FLORIDA OR MIAMI-DADE PRODUCT
 APPROVALS FOR THE USP PA 28 CONNECTORS AS REQUIRED BY
 DCA RULE 9B-72.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-05-13 Cont ID  
Sent By rmcdouga Date 2011-05-13 Time 11:55 Rev Time 0.00
Received By rmcdouga Date 2011-05-13 Time 07:03 Sent To  
Notes
2011-05-13 11:54:012007 FBC W/2009 REVISIONS
  
 DENIED BY BUILDING
  
 1) SUBMIT A COPY OF THE PAID RECEIPT FOR THE COUNTY
 IMPACT FEES.
  
 2) FBC R401.4 AREA OF QUESTIONABLE
 SOIL. SUBMIT A GEOTECHNICAL REPORT
 TO VERIFY THE SAFE BEARING CAPACITY OF
 THE SOIL.
  
 3) SPECIFY THE DESIGN CRITERIA ON THE PLANS. SPECIFY
 WINDSPEED (140 MPH, 3 SECOND GUST), EXPOSURE CATEGORY
 (C), MEAN ROOF HEIGHT, ROOF LOADS, ETC. SEE FBC R301.1
  
 4) UPDATE THE MASONRY NOTES ON C-1 FOR ACI/ASCE/TMS
 FROM THE 99 TO THE 05 EDITIONS FBC R REFERENCED
 STANDARDS IN CHAPTER 43.
  
 5) PROVIDE THE BASE PLATE DESIGN AND ANCHORING
 REQUIREMENTS FOR THE STEEL COLUMNS (C-5). CITY
 AMENDMENTS* 106.1.2 AND FBC R407.3
  
 6) SUBMIT 2 SETS OF PRODUCT APPROVALS FOR THE SLIDING
 GLASS DOORS, THE 8" LINTELS AND TRUSS CONNECTORS AS
 REQUIRED BY DCA RULE 9B-72.
  
 7) THE PRODUCT APPROVAL NOAS FOR THE SINGLE OVERHEAD
 GARAGE DOOR, THE PW-701 FIXED WINDOWS AND THE SH-700
 SINGLE HUNG WINDOWS HAVE BEEN SUPERSEDED ACCORDING TO
 THE MIAMI-DADE PRODUCT CONTROL WEB-SITE. PLEASE SUBMIT
 TWO SETS OF CURRENT PRODUCT APPROVALS FOR THESES ITEMS.
 NOTE: THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED
 AND APPROVED BY THE DESIGNER OF RECORD. CITY AMENDMENTS
 106.3.3
  
 8) PLEASE PROVIDE A RESPONSE LETTER INDICATING HOW EACH
 COMMENT HAS BEEN ADDRESSED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2011-05-24 Cont ID  
Sent By rmcdouga Date 2011-05-24 Time 07:41 Rev Time 0.00
Received By rmcdouga Date 2011-05-24 Time 07:41 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2011-05-13 Cont ID  
Sent By rmcdouga Date 2011-05-13 Time 08:10 Rev Time 0.00
Received By rmcdouga Date 2011-05-13 Time 08:10 Sent To  
Notes
2011-05-13 08:46:202007 FBC W/2009 REVISIONS
 2008 NEC
  
 DENIED BY ELECTRICAL
  
 1) REVISE LOAD CALCULATIONS AND PANEL SCHEDULE TO
 INCLUDE THE THIRD AHU HEAT STRIP AND A/C COMPRESSOR.
 NEC 220.40
  
 2) REVISE THE ARC-FAULT CIRCUIT-INTERRUPTER PROTECTION
 NOTE ON SHEET C-1. NEC 210.12 REQUIRES ARC-FAULT
 PROTECTION ON ALL 120-VOLT, SINGLE PHASE 15 AND 20 AMP
 BRANCH CIRCUITS SUPPLYING OUTLETS DWELLING UNITS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2011-05-23 Cont ID  
Sent By BRM Date 2011-05-23 Time 09:50 Rev Time 0.00
Received By bmoree Date 2011-05-23 Time 09:47 Sent To Z
Notes
2011-05-23 09:49:51PASSED WITH PROVISO
 NO CONFLICT WITH UTILITIES
  
 1. SEPARATE DRIVEWAY PERMIT REQUIRED.
  
 BRIAN R. MOREE
 CITY OF WEST PALM BEACH
 ENGINEERING SERVICES
 401 CLEMATIS STREET
 WEST PALM BEACH, FLORIDA 33401
 561-494-1098

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2011-06-16 Cont ID  
Sent By rmcdouga Date 2011-06-16 Time 13:06 Rev Time 0.00
Received By rmcdouga Date 2011-06-10 Time 10:23 Sent To  
Notes
2011-06-10 10:23:16IN ZONING BOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-06-03 Cont ID  
Sent By lfranco Date 2011-06-02 Time 19:08 Rev Time 0.00
Received By rmcdouga Date 2011-05-22 Time 11:33 Sent To  
Notes
2011-05-24 13:12:40COMPLETED REVIEW OF RESUBMITTED ITEMS AND GAVE TO L.
 MARTINEZ ON 5/24/11.
2011-05-22 11:33:30GAVE TO ROBBIE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-06-03 Cont ID  
Sent By rmcdouga Date 2011-06-03 Time 15:20 Rev Time 0.00
Received By rmcdouga Date 2011-05-13 Time 07:05 Sent To  
Notes
2011-05-13 07:05:33EXPEDITED PLAN SENT TO R.MCDOUGAL

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2011-05-24 Cont ID  
Sent By rmcdouga Date 2011-05-24 Time 07:10 Rev Time 0.00
Received By rmcdouga Date 2011-05-24 Time 07:10 Sent To  
Notes
2011-05-24 07:11:47MU-2011-008290

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2011-05-13 Cont ID  
Sent By rmcdouga Date 2011-05-13 Time 07:03 Rev Time 0.00
Received By rmcdouga Date 2011-05-13 Time 07:03 Sent To  
Notes
2011-05-13 07:04:28SUBMIT A COPY OF THE PAID RECEIPT FOR THE IMPACT FEES.

Review Stop L LANDSCAPING
Rev No 2 Status P Date 2011-06-02 Cont ID  
Sent By ajones Date 2011-06-02 Time 15:26 Rev Time 0.00
Received By ajones Date 2011-06-02 Time 15:25 Sent To  
Notes
2011-06-02 15:30:13APPROVED WITH THE PROVISO THAT A SEPERATE LANDSCAPE AND
 IRRIGATION PERMITS IS REQUIRED TO BE APPLIED FOR,
 APPROVED AND INSTALLED PRIOR TO THE ISSUANCE OF A CO.

Review Stop L LANDSCAPING
Rev No 1 Status F Date 2011-05-27 Cont ID  
Sent By rkussner Date 2011-05-27 Time 19:09 Rev Time 0.00
Received By rkussner Date 2011-05-27 Time 19:09 Sent To  
Notes
2011-05-27 19:17:37***LANDSCAPE REVIEW FAILED***
  
 PLEASE RESPOND TO REVIEW COMMENTS IN WRITTEN FORMAT.
  
 1. PLEASE APPLY FOR A SEPARATE LANDSCAPE PERMIT. SUBMIT
 TWO (2) COPIES OF A LANDSCAPE PLAN SHOWING COMPLIANCE
 WITH SECTIONS 94-442 AND 94-445 OF THE ZLDR AND A
 CERTIFIED COST ESTIMATE THAT INCLUDES THE TOTAL COST OF
 ALL LANDSCAPE MATERIALS AND LABOR, BROKEN DOWN INTO
 UNIT COST.
  
 2. PLEASE PROVIDE THE TABULATION NECESSARY FOR THE
 EVALUATION OF COMPLIANCE WITH ARTICLE XIV OF THE ZONING
 AND LAND DEVELOPMENT REGULATIONS, INCLUDING THE
 XERISCAPE DESIGN OPTIONS.
  
 3. A SEPARATE IRRIGATION PERMIT IS REQUIRED ALONG WITH
 TWO SETS OF IRRIGATION PLANS.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2011-05-12 Cont ID  
Sent By rmcdouga Date 2011-05-12 Time 12:16 Rev Time 0.00
Received By rmcdouga Date 2011-05-12 Time 07:45 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2011-05-24 Cont ID  
Sent By rmcdouga Date 2011-05-24 Time 07:30 Rev Time 0.00
Received By rmcdouga Date 2011-05-24 Time 07:12 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2011-05-12 Cont ID  
Sent By rmcdouga Date 2011-05-12 Time 07:21 Rev Time 0.00
Received By rmcdouga Date 2011-05-12 Time 06:39 Sent To  
Notes
2011-05-12 07:45:262007 FBC W/2009 REVISIONS
  
 DENIED BY PLUMBING
  
 1) THE SANITARY ISOMETRIC RISER DIAGRAM DOES NOT
 CORRESPOND WITH THE FLOOR PLAN. THE FLOOR PLAN SHOWS
 TWO HALF BATHS, THE CABANA BATH IS SHOWN BUT THE
 LAVATORY AND WATER CLOSET LOCATED IN THE POWDER ROOM IS
 NOT. THE LAUNDRY TUB IS INCORRECTLY LABELED AS A
 LAVATORY. PLEASE CORRECT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2011-06-15 Cont ID  
Sent By lfranco Date 2011-06-15 Time 18:32 Rev Time 1.50
Received By lfranco Date 2011-06-10 Time 16:12 Sent To I
Notes
2011-06-15 18:34:41PLANNING AND ZONING: **** PASSED WITH PROVISO: THE
 APPLICANT SHALL APPLY FOR AN IRRIGATION AND LANDSCAPE
 PERMIT, GET IT APPROVED AND SUCCESSFULLY INSPECTED
 PRIOR TO CERTIFICATE OF OCCUPANCY ("CO"). ****
  
  
  
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING
 TEL: (561) 822-1443
 EMAIL: [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2011-06-02 Cont ID  
Sent By lfranco Date 2011-05-31 Time 10:12 Rev Time 1.00
Received By lfranco Date 2011-05-18 Time 14:35 Sent To I
Notes
2011-06-02 19:08:55PLANNING AND ZONING: **** FAILED *****
  
  
 1. RESPOND TO COMMENTS IN WRITING. RESUBMITTAL MAY
 GENERATE ADDITIONAL COMMENTS.
  
 2. INDICATE SETBACK DIMENSIONS FROM PROPOSED A/C
 EQUIPMENT TO ALL PROPERTY LINES. PURSUANT TO SECTION
 94-305(B)(4) OF THE ZLDR: MECHANICAL EQUIPMENT MAY NOT
 PROJECT MORE THAN 4 FEET INTO A REQUIRED SETBACK.
  
 3. PURSUANT TO SECTION 94-482 OF THE ZLDR: REQUIRED
 OFF-STREET PARKING SPACES FOR LESS THAN FOUR
 RESIDENTIAL DWELLING UNITS SHALL BE LOCATED ON THE
 PROPERTY ON WHICH THE UNITS ARE CONSTRUCTED. REQUIRED
 PARKING MAY BE LOCATED IN A FRONT YARD; HOWEVER, THE
 LESSER OF 1,000 SQUARE FEET OR 75 PERCENT OF THE FRONT
 YARD AREA MUST BE LANDSCAPED. PARKING AREAS LOCATED IN
 THE FRONT YARD SHALL BE SURFACED WITH A SMOOTH,
 NONDUSTING SURFACE IN COMPLIANCE WITH SUBSECTION
 33-485(E). IT SHALL BE A VIOLATION OF THIS CHAPTER TO
 PARK ON ANY UNPAVED AREAS AS DESCRIBED IN THIS ARTICLE.
  
 INDICATE SQUARE FOOTAGE OF ALL IMPERMEABLE SURFACES
 (EXISTING AND PROPOSED) LOCATED WITHIN THE FRONT YARD
 (FROM FRONT PROPERTY LINE TO THE FRONT BUILDING
 FACADE). THE MAXIMUM WIDTH FOR A DRIVEWAY IS 20 FEET IN
 WIDTH. THERE ARE NO DIMENSIONS ON THE PROPOSED
 DRIVEWAY. ALSO, CALCULATIONS FOR THE FRONT AREA NEED TO
 BE PROVIDED BETWEEN THE FIRST 25 FEET OF LOT DEPTH FROM
 THE FRONT PROPERTY LINE MULTIPLIED BY THE TOTAL WIDTH
 OF THE PROPERTY (I.E. 25 FEET X WIDTH OF THE LOT = X
 SQ. FT. X .75 = X SQ. FT) SINCE THE SQUARE FOOTAGE
 EXCEEDS 1,000 SQ. FT. THE APPLICANT WILL ONLY BE
 REQUIRED TO MEET THE MINIMUM 1,000 SQ. FT LANDSCAPE
 AREA. SHOW CALCULATIONS OF LANDSCAPE AREA SQUARE
 FOOTAGE ON SURVEY AND/OR PLANS.
  
 SHOW ALL DIMENSIONS OF THE DRIVEWAY AND WHAT THE
 MATERIAL WILL BE (I.E. PAVERS OVER SAND, CONCRETE
 (NON-PERVIOUS), PAVERS OVER CONCRETE SLAB ARE
 CONSIDERED NON-PERVIOUS). NON-PERVIOUS MATERIAL WILL
 NOT BE COUNTED TOWARDS MEETING THE LANDSCAPE AREA
 (PERVIOUS AREAS).
  
 4. THE PROPOSED DRIVEWAY ENCROACHES WITHIN THE UTILITY
 EASEMENT; EASEMENT CONSENT FORMS ARE REQUIRED FROM THE
 FOLLOWING UTILITY COMPANIES:
  
 WEST PALM BEACH PUBLIC UTILITIES DEPARTMENT
 401 CLEMATIS STREET
 CITY HALL, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (561)822-1300
  
 FLORIDA POWER AND LIGHT
 810 CHARLOTTE AVE
 WEST PALM BEACH, FL 33401
 (561)697-8000
  
 FLORIDA PUBLIC UTILITIES
 401 SOUTH DIXIE HWY
 WEST PALM BEACH, FL 33402
 (561)832-2461
  
 BELL SOUTH
 2021 SOUTH MILITARY TRAIL
 WEST PALM BEACH, FL 33415
 (561)439-9110
  
 COMCAST
 1401 NORTHPOINT PKWY
 WEST PALM BEACH, FL 33407
 (561)655-3842 - RESIDENTIAL
 (561)227-4261 - COMMERCIAL
  
  
 5. A SEPARATE LANDSCAPE PERMIT SHALL BE APPLIED FOR
 WITH ALL REQUIREMENTS SET FORTH IN THE LANDSCAPE REVIEW
 STOP OF THIS PERMIT. THE PERMIT SHALL BE SUBMITTED
 CONCURRENTLY WITH THIS PERMIT AND PRIOR TO FINAL CO
 APPROVAL FROM THE PLANNING ZONING DEPARTMENT AND
 LANDSCAPING INSPECTION.
  
 6. THE POOL/FENCE AND OTHER IMPROVEMENTS REQUIRE A
 SEPARATE PERMIT AND WILL NOT BE PART OF THIS PERMIT
 REVIEW.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1443
 EMAIL: [email protected]
  
  
  
  
  