Plan Review Details - Permit 11050309
Plan Review Stops For Permit 11050309
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2011-11-28 Cont ID  
Sent By rmcdouga Date 2011-11-28 Time 10:36 Rev Time 0.00
Received By rmcdouga Date 2011-11-28 Time 09:12 Sent To  
Notes
2011-11-28 10:39:12CONTRACTOR'S SET OF PLANS WAS REDLINED TO MATCHED FILE
 SET.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2011-10-24 Cont ID  
Sent By rmcdouga Date 2011-10-24 Time 07:58 Rev Time 0.00
Received By rmcdouga Date 2011-10-24 Time 07:58 Sent To E
Notes
2011-10-24 09:28:342007 FBC W/2009 REVISIONS
  
 1) THE WIND LOAD ANALYSIS FOR THE MWFRS AND COMPONENT
 AND CLADDING PRESSURES FROM THE ENGINEER, THE SHAFFER
 GROUP INC. IS NOT SIGNED AND SEALED AS REQUIRED BY FS
 471 AND FAC 61G15.23.002. SUBMIT TWO SETS OF SIGNED AND
 SEALED WIND CALCULATIONS.
  
 2) THE AWNING RECONSTRUCTION DETAIL SK-1 FROM THE
 ENGINEER, THE SHAFFER GROUP INC. IS NOT SIGNED AND
 SEALED AS REQUIRED BY FS 471 AND FAC 61G15.23.002.
 SUBMIT TWO SETS OF SIGNED AND SEALED DRAWINGS.
  
 3) ONE SET OF PLANS HAS HAND WRITTEN CHANGES MADE BY
 THE ARCHITECT, LEE KVARNBERG. THE OTHER SET WILL NEED
 TO BE MARKED UP TO MATCH. CITY AMENDMENTS 106.1
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-06-03 Cont ID  
Sent By rmcdouga Date 2011-06-03 Time 13:52 Rev Time 0.00
Received By rmcdouga Date 2011-06-01 Time 11:26 Sent To  
Notes
2011-06-03 12:11:112007 FBC W/2009 REVISIONS
  
 DENIED BY BUILDING
  
 1) THE OWNER BUILDER'S SIGNATURE ON THE APPLICATION AND
 ON THE OWNER BUILDER DISCLOSURE FORM HAS TO BE
 NOTARIZED.
  
 2) SPECIFY THE WIND DESIGN DATA ON THE PLANS FBC
 R301.1. THE WINDSPEED IS 140 MPH AND THE EXPOSURE
 CATEGORY IS 'B' FOR THIS STRUCTURE.
  
 3) SPECIFY THE COMPONENT AND CLADDING PRESSURES FOR THE
 WINDOWS AND DOORS ON THE PLANS. FBC R301.2.1
  
 4) PROVIDE STRUCTURAL DETAILS FOR THE NEW OPENINGS IN
 THE EXTERIOR WALL. FBC R601.2
  
 5) SPECIFY THE 2 X 4 WOOD RAFTER TO THE RIDGE BOARD AND
 WOOD BEAM ATTACHMENTS AT THE COVERED PORCH AND WINDOW
 AWNINGS ON THE PLANS. FBC R301.1
  
 6) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE CLAY
 ROOF TILES. SPECIFY THE ATTACHMENT METHOD FROM THE
 PRODUCT APPROVAL THAT WILL BE USED TO INSTALL THE TILE.
 DCA RULE 9N-3.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2011-11-28 Cont ID  
Sent By rmcdouga Date 2011-11-28 Time 10:36 Rev Time 0.00
Received By rmcdouga Date 2011-11-28 Time 10:36 Sent To  
Notes
2011-11-28 10:38:20CONTRACTOR'S SET OF PLANS WAS REDLINED TO MATCH FILE
 SET.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2011-10-26 Cont ID  
Sent By rlecky Date 2011-10-26 Time 09:45 Rev Time 0.00
Received By rlecky Date 2011-10-26 Time 09:45 Sent To  
Notes
2011-10-26 09:56:43ONLY ONE SET OF PLANS REVISED. TWO SETS OF REVISIONS
 FOR THE ELECTRICAL PLAN ARE REQUIRED.
 ELECTRICAL FEEDER WITH OVERCURRENT PROTECTION TO NEW
 PANEL IN GARAGE NOT SPECIFIED. MIN. #3 FEEDERS WITH # 8
 GROUND REQUIRED FOR A 100 AMPERE SUB PANEL. SMOKE
 DETECTORS REQUIRED IN ALL BEDROOMS.
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 561-805-6718
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2011-05-25 Cont ID  
Sent By rlecky Date 2011-05-25 Time 09:53 Rev Time 0.00
Received By rlecky Date 2011-05-25 Time 09:19 Sent To  
Notes
2011-05-25 09:56:06REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE DETECTORS WITH BATTERY
 BACK UP. HOMES WHICH FEATURE GAS APPLIANCES, AN
 ATTACHED GARAGE OR A FIRE PLACE REQUIRE A CARBON
 MONOXIDE DETECTOR WITHIN TEN FEET OF EACH ROOM USED FOR
 SLEEPING. FBC R313
 PROVIDE AN INTERSYSTEM BONDING STRIP AT THE SERVICE
 GROUND. NEC 250.94
 NEW RECEPTACLES MUST BE ARC FAULT CIRCUIT PROTECTED.
 NEC 210-12 (B)
 NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11
 ADD RECEPTACLES SO THAT NO WALL SPACE IS MORE THAN 6
 FEET FROM A RECEPTACLE AND ALL WALL SPACES 2 FEET OR
 MORE IN WIDTH HAVE A RECEPTACLE. NEDC 210.52
 THE PLAN SHOWS MULTIPLE ELECTRIC CIRCUITS FEEDING THE
 GARAGE. A SEPARATE DISCONNECT AND PANELBOARD IS
 REQUIRED. NEC 225-30
  
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 561-805-6718
  
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2011-05-12 Cont ID  
Sent By fmittner Date 2011-05-12 Time 09:07 Rev Time 0.00
Received By fmittner Date 2011-05-12 Time 09:07 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2011-11-28 Cont ID  
Sent By rmcdouga Date 2011-11-28 Time 10:37 Rev Time 0.00
Received By rmcdouga Date 2011-11-21 Time 14:27 Sent To  
Notes
2011-11-21 14:28:47R12

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-10-26 Cont ID  
Sent By rlecky Date 2011-10-26 Time 09:45 Rev Time 0.00
Received By rlecky Date 2011-10-14 Time 10:30 Sent To  
Notes
2011-10-14 10:30:43INCOMING SENT TO R MCDOUGALS DESK. JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-06-03 Cont ID  
Sent By rmcdouga Date 2011-06-03 Time 13:52 Rev Time 0.00
Received By rmcdouga Date 2011-05-12 Time 14:49 Sent To  
Notes
2011-05-12 14:55:41R12

Review Stop L LANDSCAPING
Rev No 2 Status N Date 2011-05-19 Cont ID  
Sent By rkussner Date 2011-05-19 Time 16:05 Rev Time 0.00
Received By rkussner Date 2011-05-19 Time 16:05 Sent To  
Notes
2011-05-19 16:07:13***LANDSCAPE NOT REQUIRED***
  
 PLEASE REFER TO PERMIT NUMBER 11050543 FOR LANDSCAPE
 PERMIT AND PLANS.--RAK
 PLEASE NOTE THAT THE LANDSCAPE PLANS MUST BE SUBMITTED,
 APPROVED AND SUCCESSFULLY INSPECTED PRIOR TO C/O.
  

Review Stop L LANDSCAPING
Rev No 1 Status F Date 2011-05-17 Cont ID  
Sent By rkussner Date 2011-05-17 Time 17:05 Rev Time 0.00
Received By rkussner Date 2011-05-17 Time 17:05 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2011-06-01 Cont ID  
Sent By rmcdouga Date 2011-06-01 Time 11:52 Rev Time 0.00
Received By rmcdouga Date 2011-06-01 Time 11:52 Sent To  
Notes
2011-06-01 11:59:22NO MECHANICAL PLANS WERE SUBMITTED AND NO MECHANICAL
 PERMIT WAS APPLIED FOR. A SEPARATE PERMIT, PLANS AND
 EQUIPMENT SIZING CALCULATIONS WILL BE REQUIRED.

Review Stop P PLUMBING
Rev No 1 Status P Date 2011-06-01 Cont ID  
Sent By rmcdouga Date 2011-06-01 Time 11:27 Rev Time 0.00
Received By rmcdouga Date 2011-06-01 Time 11:27 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2011-05-20 Cont ID  
Sent By jpapa Date 2011-05-20 Time 10:35 Rev Time 0.25
Received By jpapa Date 2011-05-20 Time 10:35 Sent To  
Notes
2011-05-20 10:42:40APPLICANT HAS SUBMITTED A LANDSCAPE PLAN TO COMPLY WITH
 PREVIOUS ZONING COMMENTS (SEE PERMIT #11050543).
  
 JILLIAN PAPA
 HISTORIC PRESERVATION PLANNER
 561-822-1454

Review Stop Z ZONING
Rev No 1 Status F Date 2011-05-13 Cont ID  
Sent By fmittner Date 2011-05-12 Time 09:06 Rev Time 0.00
Received By fmittner Date 2011-05-12 Time 09:06 Sent To  
Notes
2011-05-17 15:45:46THE VALUE OF THE CONSTRUCTION ($34,000) EXCEEDS 50% OF
 THE STRUCTURE'S VALUE ($44,498) ACCORDING TO THE P.B.C.
 PROPERTY APPRAISER'S OFFICE; THEREFORE, PURSUANT TO
 SECTION 94-441(C)(2) OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS (ZLDR), THE LANDSCAPE ON THE SITE SHALL BE
 IN COMPLIANCE WITH ALL APPLICABLE REGULATIONS FOUND IN
 ARTICLE XIV OF THE ZLDR. IF THE SITE CONFORMS TO
 ARTICLE XIV, THEN TWO (2) COPIES OF A LANDSCAPE PLAN
 DEMONSTRATING COMPLIANCE SHALL BE INCLUDED WITH THE
 PERMIT RE-SUBMITTAL. IF THE SITE DOES NOT CONFORM TO
 ARTICLE XIV, THEN PRIOR TO THE ZONING APPROVAL OF THIS
 PERMIT A SEPARATE LANDSCAPE PERMIT AND IRRIGATION
 PERMIT SHALL BE SUBMITTED SHOWING MATERIAL TO BRING THE
 SITE INTO CONFORMITY.