| 2011-10-19 11:14:55 | BUILDING PLAN REVIEW |
| | PERMIT: 11050304 |
| | ADD: 1225 PALM BEACH LAKES BLVD |
| | CONT: CILAS CONCRETE CONSTRUCTION |
| | TEL: (561)252-8429 |
| | |
| | 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS |
| | 2009 FLORIDA EXISTING BUILDING CODE / 2009 SUPPLEMENTS |
| | 2007 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | ACTION: DENIED |
| | |
| | 1) THE PERMIT APPLICATION SCOPE OF WORK INDICATES THE |
| | INFILL OF PATIO NEW MASONRY AND WINDOWS, PLEASE |
| | INDICATE THIS IS A CHANGE IN OCCUPANCY!!!! |
| | |
| | |
| | 2) SHEET A-1 INDICATES NEW PLAY AREA PLEASE PROVIDE THE |
| | FOLLOWING INFORMATION REQUIRED BY 2007 FBC-B |
| | 106.3.5.1.1: |
| | 2A)COMPLIED. |
| | 2B) SEMI-COMPLIED. MINIMUM BLDG TYPE WILL BE REQUIRED |
| | SINCE THIS IS A CHANGE OF OCCUPANCY/ COMPLIED |
| | SPRINKLERED- YES. |
| | SHEET A-0 UNDER THE HEADING OCCUPANCY/ USE PLEASE |
| | CORRECT BUILDING TYPE AS III-B PROTECTED THE B |
| | DESIGNATION IS UNPROTECTED, A IS PROTECTED SEE TABLE |
| | 601. |
| | 2C) COMPLIED. |
| | 2D) SEMI-COMPLIED. FLOOR PLAN/ LIFE SAFETY PLAN/ EGRESS |
| | INCLUDE; OCCUPANCY LOAD/GROSS/ NET/ EXIT ACCESS & EXITS |
| | PLEASE PROVIDE OCCUPANT LOADS FOR THE ROOMS AND |
| | INCIDENTAL USE AREAS INDICATED ON SHEET #1 AND TOTAL |
| | LOAD. |
| | |
| | 3) SEMI COMPLIED. FL BLD CODE 1609.6.2.2 COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES OF PRODUCT TESTING REPORTS, |
| | MISSING REPORTS ARE AS FOLLOWS: NEW EXTERIOR DOOR. |
| | PLEASE REVIEW REQUIREMENTS FOR: |
| | 1034.1 PANIC AND FIRE EXIT HARDWARE. |
| | 1034.1.1 ANY DOOR IN A REQUIRED MEANS OF EGRESS FROM AN |
| | AREA HAVING AN OCCUPANT LOAD OF 100 OR MORE PERSONS |
| | SHALL BE PERMITTED TO BE PROVIDED WITH A LATCH OR LOCK |
| | ONLY IF IT IS PANIC HARDWARE OR FIRE EXIT HARDWARE |
| | WHICH RELEASES WHEN A FORCE OF NO MORE THAN 15 POUNDS |
| | (67 N) IS APPLIED TO THE RELEASING DEVICES IN THE |
| | DIRECTION OF EXIT TRAVEL. SUCH RELEASING DEVICES MAY BE |
| | BARS OR PANELS EXTENDING NOT LESS THAN ONE-HALF THE |
| | WIDTH OF THE DOOR AND PLACED AT HEIGHTS SUITABLE FOR |
| | THE SERVICE REQUIRED, BUT NOT LESS THAN 34 INCHES (864 |
| | MM) NOR MORE THAN 48 INCHES (1219 MM) ABOVE THE FLOOR. |
| | WHENEVER PANIC HARDWARE IS USED ON A LABELED FIRE DOOR, |
| | THE PANIC HARDWARE SHALL BE LABELED AS FIRE EXIT |
| | HARDWARE. |
| | |
| | 4) SEMI COMPLIED WILL NEED TO REVIEW PANIC & FIRE |
| | HARDWARE FOR ALL EXTERIOR DOORS. 106.3.3 PRODUCT |
| | APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY THE |
| | DCA RULE 9B-72 SHALL BE REVIEWED AND APPROVED IN |
| | WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| | FOR JURISDICTIONAL APPROVAL. |
| | |
| | NEW COMMENTS NEW CHANGE OF OCCUPANCY PLANS AND SITE |
| | PLAN. |
| | |
| | 5) THE LANSCAPE AND SITE PLAN WILL PROBABLY BE A |
| | SEPERATE PERMIT, PLEASE NOTE ACCESSIBLE PARKING SPOTS |
| | (2) AND THE PLANS INDICATING ACCESS AISLE BEHIND THE |
| | ACCESSIBLE SPACE. FBC-B 11-4.6.2(1) (GRAY BOX FL |
| | SPECIFIC) ALL SPACES MUST BE LOCATED ON AN ACCESSIBLE |
| | ROUTE NO LESS THAN 44 INCHES (1118 MM)WIDE SO THAT |
| | USERS WILL NOT BE COMPELLED TO WALK OR WHEEL BEHIND |
| | PARKED VEHICLES. |
| | |
| | 6) IT APPEARS THIS BUILDING WILL BE A MIXED OCCUPANCY |
| | WITH DAY CARE (BABIES) AND EDUCATIONAL (KINDERGARDEN |
| | AND FIRST GRADE). THE DESIGNER WILL NEED TO INDICATE |
| | COMPLIANCE WITH EITHER FLC-B 508.313 OR 508.3.2 AND |
| | SHOW COMPLIANCE. |
| | |
| | 7) DISCREPANCY IN CLASSROOM THAT IS 25'-0" WIDE (ALL |
| | CLASSROOMS NOT LABELED OR IDENTIFIED) PLEASE REVIEW |
| | DOOR SWING BY EXIT BY STORAGE AREA SHEET A1 VERSES LIFE |
| | SAFETY SHEET. |
| | ROOM NOT IDENTIFIED FOR WHAT AGE CHILDREN PLEASE REVIEW |
| | 1028.3 DOORS THAT SWING INTO AN EXIT ACCESS CORRIDOR |
| | SHALL BE RECESSED TO PREVENT INTERFERENCE WITH CORRIDOR |
| | TRAFFIC; ANY DOORS NOT RECESSED SHALL OPEN 180 DEGREES |
| | (3.1 RAD) TO STOP AGAINST THE WALL. DOORS IN ANY |
| | POSITION SHALL NOT REDUCE THE REQUIRED CORRIDOR WIDTH |
| | BY MORE THAN ONE-HALF. |
| | |
| | 8) SHEET A1 WALL LEGEND INDICATES WALL TYPE 3 TO BE A |
| | EXISTING 1 HOUR WALL WHERE AS DETAIL W3 INDICATES THE |
| | WALL STOPPING 6 INCHES ABOVE THE CEILING. PLEASE SEE |
| | WALL LEGEND |
| | W4 IS AN EXISTING INTERIOR WALL WHERE AS DETAIL W4 |
| | INDICATES A 1-0 HOUR RATED WALL TO THE ROOF DECK ABOVE, |
| | DISCREPANCY PLEASE CORRECT. |
| | |
| | 9) SHEET A1 INDICATES WHAT APEARS TO BE 1-0 RATED |
| | CORRIDOR BY THE WALL LEGEND BUT THERE IS A 1ST GRADE |
| | CLASS IN THE MIDDLE OF THIS CORRIDOR? PLEASE PROVIDE |
| | EXPLANATION. |
| | 106.1.2 ADDITIONAL INFORMATION REQUIRED. |
| | |
| | 10) PLANS INDICATE BUILDING TO BE SPRINKLERED NOTE 5 ON |
| | LS SHEET, PLEASE PROVIDE SPRINKLER PLANS, PLEASE NOTE |
| | IF SPRINKLER SYSTEM IS SUPERVISED. |
| | 2007/09 FBC-B 1026.4.1 EVERY ROOM OR SPACE GREATER THAN |
| | 250 SQUARE FEET (23.2 M2) IN EDUCATIONAL OCCUPANCIES |
| | USED FOR CLASSROOM OR OTHER EDUCATIONAL PURPOSES OR |
| | NORMALLY SUBJECT TO STUDENT OCCUPANCY AND EVERY ROOM OR |
| | SPACE NORMALLY SUBJECT TO CLIENT OCCUPANCY, OTHER THAN |
| | BATHROOMS, IN GROUP D OCCUPANCIES SHALL HAVE NOT LESS |
| | THAN ONE OUTSIDE WINDOW FOR EMERGENCY RESCUE THAT |
| | COMPLIES WITH THE FOLLOWING: |
| | |
| | 1. SUCH WINDOWS SHALL BE OPENABLE FROM THE INSIDE |
| | WITHOUT THE USE OF TOOLS AND SHALL PROVIDE A CLEAR |
| | OPENING OF NOT LESS THAN 20 INCHES (508 MM) IN WIDTH, |
| | 24 INCHES (610 MM) IN HEIGHT, AND 5.7 SQUARE FEET (0.53 |
| | M2) IN AREA. |
| | |
| | 2. THE BOTTOM OF THE OPENING SHALL BE NOT MORE THAN 44 |
| | INCHES (1118 MM) ABOVE THE FLOOR, AND ANY LATCHING |
| | DEVICE SHALL BE CAPABLE OF BEING OPERATED FROM NOT MORE |
| | THAN 54 INCHES (1372 MM) ABOVE THE FINISHED FLOOR. |
| | |
| | 11) 36.2 CLOSET DOORS. EVERY CLOSET DOOR LATCH SHALL BE |
| | SUCH THAT CLIENTS CAN OPEN THE DOOR FROM INSIDE THE |
| | CLOSET. |
| | |
| | 12) 436.3 BATHROOM DOORS. EVERY BATHROOM DOOR LOCK |
| | SHALL BE DESIGNED TO PERMIT OPENING OF THE LOCKED DOOR |
| | FROM THE OUTSIDE IN AN EMERGENCY. THE OPENING DEVICE |
| | SHALL BE READILY ACCESSIBLE TO THE STAFF. |
| | |
| | 13) 436.4 DOOR CLOSURE. ANY EXIT DOOR DESIGNED TO BE |
| | NORMALLY CLOSED SHALL BE KEPT CLOSED AND SHALL COMPLY |
| | WITH SECTION 715.3. |
| | |
| | |
| | 14) NOTE PLANS DO NOT INDICATE ANY AREA WHERE CLEANING |
| | SUPPLIES WILL BE KEPT IN A SAME ROOM NOR IF THERE IS A |
| | LAUNDRY ROOM. WATER HEATER IS ALSO MISSING FROM LS |
| | PLAN. |
| | 436.6.2 THE FOLLOWING ROOMS OR SPACES SHALL BE |
| | SEPARATED FROM THE REMAINDER OF THE BUILDING BY FIRE |
| | BARRIERS HAVING A FIRE RESISTANCE RATING OF NOT LESS |
| | THAN 1 HOUR AND SHALL BE PROTECTED BY AN APPROVED |
| | AUTOMATIC FIRE-EXTINGUISHING SYSTEM. |
| | |
| | 1. LAUNDRIES. |
| | |
| | 2. MAINTENANCE SHOPS, INCLUDING WOODWORKING AND |
| | PAINTING AREAS. |
| | |
| | 3. ROOMS OR SPACES USED FOR PROCESSING OR USE OF |
| | COMBUSTIBLE SUPPLIES DEEMED HAZARDOUS BY THE BUILDING |
| | OFFICIAL. |
| | |
| | 4. ROOMS OR SPACES USED FOR PROCESSING OR USE OF |
| | HAZARDOUS MATERIALS OR FLAMMABLE OR COMBUSTIBLE LIQUIDS |
| | IN QUANTITIES DEEMED HAZARDOUS BY RECOGNIZED STANDARDS. |
| | |
| | EXCEPTION: FOOD PREPARATION FACILITIES PROTECTED IN |
| | ACCORDANCE WITH NFPA 96 SHALL NOT BE REQUIRED TO HAVE |
| | OPENINGS PROTECTED BETWEEN FOOD PREPARATION AREAS AND |
| | DINING AREAS. WHERE DOMESTIC COOKING EQUIPMENT IS USED |
| | FOR FOOD WARMING OR LIMITED COOKING, PROTECTION OR |
| | SEGREGATION OF FOOD PREPARATION FACILITIES SHALL NOT BE |
| | REQUIRED IF APPROVED BY THE BUILDING OFFICIAL. |
| | |
| | 14) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |