Plan Review Details - Permit 11050202
Plan Review Stops For Permit 11050202
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2011-06-01 Cont ID  
Sent By shill Date 2011-06-01 Time 09:11 Rev Time 0.00
Received By shill Date 2011-06-01 Time 09:11 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-05-09 Cont ID  
Sent By shill Date 2011-05-09 Time 13:41 Rev Time 0.00
Received By shill Date 2011-05-09 Time 13:41 Sent To  
Notes
2011-05-09 14:00:17****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. SEE SHEET 13 OF THE PRODUCT APPROVAL AND THE
 INSTALLATION SCHEDULE. CONNECTION TYPE D W/12 IS
 CIRCLED ON THE PRODUCT APPROVAL, BUT ANCHOR SPACING
 CIRCLED IS FOR ALL POINTS SOLID SET (9"), 4.5" SPACING
 IS REQUIRED FOR TAPCONS.
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-05-09 Cont ID  
Sent By shill Date 2011-05-09 Time 13:39 Rev Time 0.00
Received By shill Date 2011-05-09 Time 13:39 Sent To  
Notes
***NONE***