Plan Review Details - Permit 11050095
Plan Review Stops For Permit 11050095
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2011-08-05 Cont ID  
Sent By jwitmer Date 2011-08-05 Time 09:51 Rev Time 1.22
Received By jwitmer Date 2011-08-05 Time 09:51 Sent To  
Notes
2011-08-05 10:52:48BUILDING PLAN REVIEW
 PERMIT: 11050095
 ADD: 301 N OLIVE AVE 6TH / 12TH FLOOR
 CONT: E H PASCHER
 TEL: (954)261-5726
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 ON THE PERMIT APPLICATION UNDER THE HEADING DESCRIBE
 PROJECT IN DETAIL , PART OF THE DESCRIPTION INDICATES
 REPLACE ROOF TOP FANS ON THE 6TH AND 12 FLOOR.
 PRODUCT APPROVAL SUBMITTED IS :
  
 NOA# 09-0511.03 GREENHECK MODEL FG1, FG3 & R -SERIES
 STEEL/ ALUMINUM ROOF FANS , MODEL NOT IDENTIFIED AS TO
 SIZE, STANDARD OR FILTERED NOR TYPE OF MATERIALS +/-
 130 PSF STEEL & ALUMINUM +/- 70.
  
 SHEET M 6.1 DETAIL FOR GRAVITY VENT DOES NOT INDICATE
 TYPE OF MATERIAL TO BE USED ON THE SHELL OF THE FAN.
 SHEET M5.0 GRAVITY ROOF VENTILATOR NOTE 2 HOUSING TO BE
 ALUMINUM WITH 13INCH BASE HEIGHT (MAXIMUM). DESIGNER OF
 RECORD VERIFICATION THAT THE GREENHECK MODEL FG1, FG3 &
 R ALUMINUM SERIES VENTILATOR MEET THE WIND PRESSURES
 FOR THE LOCATIONS ON THE 6TH AND 12TH FLOOR ROOF
 LEVELS.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-05-10 Cont ID  
Sent By jwitmer Date 2011-05-10 Time 11:51 Rev Time 0.55
Received By jwitmer Date 2011-05-10 Time 11:41 Sent To  
Notes
2011-05-10 12:17:38BUILDING PLAN REVIEW
 PERMIT: 11050095
 ADD: 301 N OLIVE AVE 6TH / 12TH FLOOR
 CONT: E H PASCHER
 TEL: (954)261-5726
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) ON THE PERMIT APPLICATION UNDER THE HEADING DESCRIBE
 PROJECT IN DETAIL , PAT OF THE DESCRIPTION INDICATES
 REPLACE DOORS ON TTHE 6TH AND 12 FLOOR.
 PRODUCT APPROVALS SUBMITTED ARE :
  
 NOA# 06-0612.03 DAYBAR INDUSTRIES LIMITED SERIES LS 18,
 FLUSH OUTSWING COMMERCIAL STEEL DOOR =/- 60 PSF.
  
 NOA# 09-0511.03 GREENHECK MODEL FG1, FG3 & R -SERIES
 STEEL/ ALUMINUM ROOF FANS , MODEL NOT IDENTIFIED AS TO
 SIZE, STANDARD OR FILTERED NOR TYPE OF MATERIALS +/-
 130 PSF STEEL & ALUMINUM +/- 70.
  
 NOA# 10-0921.09 GREENHECK MODEL ESD-635 D ALUMINUM
 LOUVER W/ WITHOUT VCD-40 DAMPER +/- 150 PSF.
  
 1A) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 1B) THE REPLACEMENT OF DOORS, EXHAUST FANS AND LOUVERS
 ON A HIGH RISE BUILDING REQUIRES ENGINEERING AAS TO
 WIND DESIN CRITERIA AS TO ASCE 7-05. NO LOCATIONS HAVE
 BEEN PROVIDED IF THESE UNITS DOORS LOUVERS ARE LOCATED
 IN AN INTERIOR ZONE OR END ZONE. THE SAME HOLDS TRUE
 FOR THE ROOF FAN, THE LOCATION IS UNKNOWNED PLEASE
 PROVIDE LOCATION TO BE LOCATED WITHIN ROOF ZONE 1,2 OR
 3. 2007/09 FBC-B 1609. COMPONENTS & CLADDING.
  
 1C) 1609.6.2 WIND DESIGN PROCEDURES
 1C)1) THE BASIC WIND SPEED, V, SHALL BE DETERMINED IN
 ACCORDANCE WITH SECTION 1609.3. THE WIND SHALL BE
 ASSUMED TO COME FROM ANY HORIZONTAL DIRECTION.
  
 1C)2) AN IMPORTANCE FACTOR, IW, SHALL BE DETERMINED IN
 ACCORDANCE WITH SECTION1609.5.
  
 1C)3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4.
  
 1C)4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.6.2.1(4)
  
 1C)5) POSITIVE / NEGATIVE PRESSURES.
  
 JAMES A. WITMER C.B.O.
 COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: (561)805-6715
 FAX:(561)805-6731
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2011-05-09 Cont ID  
Sent By rlecky Date 2011-05-09 Time 16:00 Rev Time 0.00
Received By rlecky Date 2011-05-09 Time 16:00 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status N Date 2011-05-10 Cont ID  
Sent By wjolin Date 2011-05-10 Time 14:06 Rev Time 0.00
Received By wjolin Date 2011-05-10 Time 13:54 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-08-05 Cont ID  
Sent By jwitmer Date 2011-08-05 Time 10:52 Rev Time 0.00
Received By jwitmer Date 2011-08-04 Time 14:29 Sent To  
Notes
2011-08-04 14:30:11SENT TO JIM'S DESK FOR REVIEW.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-05-23 Cont ID  
Sent By lmartine Date 2011-05-23 Time 09:45 Rev Time 0.00
Received By lmartine Date 2011-05-04 Time 09:34 Sent To  
Notes
2011-05-10 09:35:24C-3

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2011-05-09 Cont ID  
Sent By hmoser Date 2011-05-09 Time 16:21 Rev Time 0.00
Received By hmoser Date 2011-05-09 Time 07:00 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2011-05-11 Cont ID  
Sent By aaponte Date 2011-05-11 Time 10:16 Rev Time 0.05
Received By aaponte Date 2011-05-11 Time 10:16 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved