| 2011-05-25 14:13:39 | RESIDENTIAL (R3) ADDITION, BUILDING REVIEW CHECKLIST. |
| | 2007 FBC-EXISTING AND 2007 FLORIDA RESIDENTIAL CODE. |
| | |
| | 1- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH |
| | COUNTY (2300 N. JOG RD) TO VERIFY IF IMPACT FEES ARE |
| | DUE. BRING BACK STAMPED PLANS AND COPY OF PAID RECEIPT |
| | IF FEES ARE DUE. |
| | |
| | 2- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. |
| | 713.13. |
| | ***NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK |
| | UP. |
| | |
| | 3- REVISE THE DESIGN CRITERIA SHOWN ON THE BOTTOM RIGHT |
| | SIDE OF SHEET A-1: A) ACCORDING TO 2009 REVISIONS SEC. |
| | R301.2.1.4.3 THIS BUILDING IS LOCATED ON EXPOSURE "C" |
| | NOT "B". REVISE ALL THE DESIGN PRESSURES FOR DOORS AND |
| | WINDOWS AND FOR ROOF. ALSO, THE CORRECT CODE IS THE |
| | 2007 FLORIDA RESIDENTIAL CODE NO THE 2007 FBC. THIS |
| | APPLIES TO ONE & TWO FAMILY DWELLINGS ONLY. |
| | |
| | B) SPECIFY ALL THE DESIGN LOADS INCLUDING THE ATTIC |
| | LIVE LOADS AS REQUIRED BY TABLE R301.5. |
| | |
| | C) CLARIFY WHY THE ROOF DEAD LOAD IS 12PSF. CONSIDER |
| | THAT PLANS SHOW CONCRETE ROOF TILE. ALSO, COORDINATE |
| | INFORMATION WITH THE TRUSS LOADING DESIGN NOTE SHOWN ON |
| | THE UPPER RIGHT HAND SIDE OF SHEET A-9. SEC. R301. |
| | |
| | 4- SHEET A-4: A) CLARIFY HOW THE ATTIC ACCESS PANEL |
| | SHOWN ON THE GARAGE SIDE IS PROVIDING ACCESS TO THE |
| | ATTIC IF IT'S LOCATED ON THE WALL AND ABOVE THE BEAM?. |
| | PROVIDE SECTION/DETAIL. SEC. 106.1.1 CITY AMENDMENTS TO |
| | FBC. |
| | |
| | B) FINISH FLOOR ELEVATION SHOWN ON THE CABANA SIDE, |
| | GARAGE SIDE AND COVERED PATIO IS (0'-0"). BUT, THERE IS |
| | A 6" DROP SHOWN AT THE CABANA DOUBLE DOOR AND AT THE |
| | GARAGE SWING DOOR. CLARIFY/REVISE AS REQUIRED. SEC. |
| | 106.1.1 CITY AMENDMENTS TO FBC. |
| | |
| | 5- SHEET A-5: A) REVISE DIAPHRAGM SCHEDULE AT BOTTOM |
| | LEFT SPECIFICATIONS FOR PANEL GRADE AND PANEL THICKNESS |
| | TO MATCH INFORMATION SHOWN ON ROOF COVERINGS NOTE ON |
| | TOP RIGHT SIDE OF SHEET. |
| | |
| | B) REVISE ROOF/ATTIC VENTILATION NOTE. REFER TO THE |
| | 2007 FLORIDA RESIDENTIAL CODE NOT THE FBC 2007 AND CITE |
| | CORRECT SECTION. AND, NEED TO SPECIFY ACTUAL VENT SIZE |
| | AND LOCATION AS REQUIRED BY SEC. R806. |
| | |
| | 6- SHEET A-6: ROOF PROFILE SHOWN ON THE GARAGE NORTH |
| | (REAR) ELEVATION DOESN'T MATCH ROOF FRAMING PLAN |
| | LAYOUT. REVISE AS REQUIRED TO MATCH. SEC. 106.1.1 CITY |
| | AMENDMENTS TO FBC. |
| | |
| | 7- SHEET A-7: A) PROVIDE COMPLETE SPECIFICATIONS FOR |
| | BUCK SIZE AND FASTENING FOR GARAGE DOOR. TYPICAL GARAGE |
| | DOORS DETAILS SPECIFY "REFER TO MANUFACTURER'S |
| | DETAILS". THIS IS THE RESPONSIBILITY OF THE DESIGNER OF |
| | RECORD. REVISE TYPICAL GARAGE FRAME AND DOOR DETAILS AS |
| | REQUIRED. SEC. R301. |
| | |
| | B) REVISE SIZE OF BUCK SPECIFIED FOR THE DOOR ON THE |
| | WINDOW/DOOR BUCK DETAIL. NEED SIZE THAT PROVIDE FULL |
| | SUPPORT TO THE DOOR FRAME AS REQUIRED BY SEC. |
| | R613.6.1.1. SEE DOOR PRODUCT APPROVAL FOR DOOR FRAME |
| | SIZE. |
| | |
| | C) REVISE THE WINDOW BUCK TYPE SPECIFIED ON THE TYPICAL |
| | WALL SECTION. BEVELED BUCKS ARE NOT ALLOWED. SEC. |
| | R613.6.1.1. |
| | |
| | 8- SHEET A-8: REVISE FINISH FLOOR ELEVATION SHOWN ON |
| | EXISTING KITCHEN, NEW GARAGE, NEW CABANA AND NEW |
| | COVERED PATIO. REVISE FINISH FLOOR ELEVATIONS SHOWN AND |
| | COORDINATE WITH ITEM #4(B) ABOVE. SEC. 106.1.1 CITY |
| | AMENDMENTS TO FBC. |
| | |
| | 9- SHEET A-9: A) REVISE NOTE #5 ON TOP LEFT SIDE. |
| | COORDINATE WITH ITEM #3(A) ABOVE. |
| | |
| | B) BEAM SCHEDULE SAYS WB-1 BEAM WHILE COVERED PATIO |
| | BEAM ON ROOF FRAMING PLAN SAYS WD-1. REVISE/CORRECT AS |
| | REQUIRED TO MATCH. SEC. 106.1.1 |
| | |
| | C) ROOF FRAMING PLAN IS INCOMPLETE: SPECIFY TRUSS |
| | CONNECTORS FOR ALL TRUSSES INCLUDING THE TRUSS GIRDERS |
| | AND THE TRUSSES RESTING ON THE WOOD BEAM OF THE COVERED |
| | PATIO. ONLY A PORTION OF ROOF TRUSSES ARE SHOWN WITH |
| | CONNECTORS. REVISE ROOF FRAMING PLAN AS REQUIRED. |
| | |
| | 10- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9B-72 FOR: |
| | |
| | A) PRECAST LINTELS AS SPECIFIED ON PLANS. |
| | |
| | B) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS |
| | AND SECTIONS. NOTE: PROVIDE ONLY THE PRODUCT APPROVAL |
| | COVER PAGE AND PAGE SHOWING THE CONNECTOR. |
| | |
| | C) SINGLE HUNG WINDOWS. NOA 11-0128.03 SUBMITTED WAS |
| | SUPERSEDED BY MIAMI-DADE. VISIT THE MIAMI-DADE WEBSITE |
| | AND DOWNLOAD CURRENT NOA. |
| | |
| | D) GARAGE EXTERIOR SWING DOOR. NEED TO PROVIDE PRODUCT |
| | APPROVAL FOR SIZE OF DOOR SPECIFIED ON PLANS. NOA |
| | 07-0709.07 SUBMITTED IS FOR 8'-0" HIGH DOORS. |
| | |
| | E) ROOF TILE AS SPECIFIED ON PLANS. |
| | |
| | F) IF USING TILE ADHESIVE, THEN PROVIDE PRODUCT |
| | APPROVAL FOR ADHESIVE LISTED ON THE ROOF TILE PRODUCT |
| | APPROVAL. |
| | |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561)805-6712 |
| | |