Plan Review Details - Permit 11050023
Plan Review Stops For Permit 11050023
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2011-08-24 Cont ID  
Sent By jwitmer Date 2011-08-24 Time 14:11 Rev Time 1.30
Received By jwitmer Date 2011-08-24 Time 14:11 Sent To  
Notes
2011-08-24 14:14:10BUILDING PLAN REVIEW
 PERMIT: 11050023
 ADD: 1009 BANYAN BLVD
 CONT: TO BE DETERMINED
 TEL: (561)494-1046
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS CHAPTER 1
  
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 1) ) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING,
 PROVIDE 2 COPIES OF PRODUCT TESTING REPORTS, MISSING
 REPORTS ARE AS FOLLOWS:
  
 1A) WINDOWS
  
 1B) EXTERIOR SWING DOORS
  
 1C) EXTERIOR OVERHEAD DOORS
  
 1D) EXTERIOR WALL LOUVERS
  
 1E) ROOF ASSEMBLIES
  
 1F) FIRE RATED DOORS AND FRAMES
  
 1G) FIRE RATED LOUVERS
  
 2) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 PLEASE NOTE: THE PERMIT CAN BE ISSUED WITHOUT THE
 PRODUCT APPROVALS, BUT EACH OF THE 7 PRODUCTS LISTED
 WILL BE CONSIDERED AS REVISIONS AND REVIEWS WITH
 ASSOCIATED FEES. PRESSURES FOR COMPONENTS AND CLADDING
 ARE LOCATED ON SHEET GS-1.
  
  
 JAMES A. WITMER C.B.O.
 COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: (561)805-6715
 FAX:(561)805-6731
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2011-08-10 Cont ID  
Sent By jwitmer Date 2011-08-10 Time 10:45 Rev Time 0.00
Received By jwitmer Date 2011-08-10 Time 10:45 Sent To  
Notes
2011-08-10 10:49:53BUILDING PLAN REVIEW
 PERMIT: 11050023
 ADD: 1009 BANYAN BLVD
 CONT: TO BE DETERMINED
 TEL: (561)494-1046
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS CHAPTER 1
  
 2ND REVIEW
 ACTION: DENIED
  
 NO REVIEW COULD BE COMPLETED, PLANS ARE TO BE BOUND NOT
 PUT INTO FOLDERS. IF NEW SHEETS ARE TO PUT INTO THE
 ORIGINAL PLANS THE NEW SHEETS ARE TO PUT INTO THE PLANS
 AND OLD SHEETS PULLED OUT AND MAKE A SEPERATE SET OF
 OLD SHEETS TO SEE WHAT CHANGES WERE MADE.
  
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER C.B.O.
 COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: (561)805-6715
 FAX:(561)805-6731
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-06-08 Cont ID  
Sent By jwitmer Date 2011-06-08 Time 09:09 Rev Time 3.33
Received By jwitmer Date 2011-06-08 Time 09:09 Sent To  
Notes
2011-06-08 09:59:25BUILDING PLAN REVIEW
 PERMIT: 11050023
 ADD: 1009 BANYAN BLVD
 CONT: TO BE DETERMINED
 TEL: (561)494-1046
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS CHAPTER 1
  
 1ST REVIEW
 ACTION: DENIED
  
 1) A PROPERLY LICENSED CONTRACTOR SHALL APPLY FOR
 PERMIT BEFORE A PERMIT MAY BE ISSUED. 105.1 2004 WPB
 ADMINISTRATIVE CODE.
  
 2) ) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING,
 PROVIDE 2 COPIES OF PRODUCT TESTING REPORTS, MISSING
 REPORTS ARE AS FOLLOWS:
  
 2A) WINDOWS
  
 2B) EXTERIOR SWING DOORS
  
 2C) EXTERIOR OVERHEAD DOORS
  
 2D) EXTERIOR WALL LOUVERS
  
 2E) ROOF ASSEMBLIES
  
 2F) FIRE RATED DOORS AND FRAMES
  
 2G) FIRE RATED LOUVERS
  
 3) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 PLEASE NOTE: THE PERMIT CAN BE ISSUED WITHOUT THE
 PRODUCT APPROVALS, BUT EACH OF THE 7 PRODUCTS LISTED
 WILL BE CONSIDERED AS REVISIONS AND REVIEWS WITH
 ASSOCIATED FEES. PRESSURES FOR COMPONENTS AND CLADDING
 ARE LOCATED ON SHEET GS-1.
  
 4) SHEET GS-1 INDICATES THE SOILS DESIGN CRITERIA AS 3,
 000 DEAD PLUS LIVE LOADS AND 3,990 ALL LOADS INCLUDING
 WIND AND SEISMIC LOADS (PSF) BUT NO SOILS REPORT HAS
 BEEN PROVIDED. 1802.2.1 QUESTIONABLE SOIL. WHERE THE
 SAFE-SUSTAINING POWER OF THE SOIL IS IN DOUBT, OR WHERE
 A LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS
 CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE
 THAT THE NECESSARY INVESTIGATION BE MADE. SUCH
 INVESTIGATION SHALL COMPLY WITH THE PROVISIONS OF
 SECTIONS 1802.4 THROUGH 1802.6 .
  
 5) TRUSS DESIGN:
  
 5A) SHEET GS-6 NOTE# 8 INDICATES ADDITIONAL AXIL LOADS
 OF 1 KIP AT BOTTOM CHORD OF TRUSSES THAT PASS OVER WALL
 ON GRIDLINE "C". NEITHER THE STRUCTURAL PLANS NOR
 ARCHITECTURAL SHEETS? ADDITIONAL INFORMATION REQUIRED?
 106.1.2.
  
 5B) SHEET 15S-3 THE TRUSS LAY OUT SHEET HAS TO DETAIL
 MARKERS, S904 & S-557. IN BOTH CASES THEY ARE TO BE
 ATTACHMENT DETAILS, PART OF THE MWFRS
 FBC-B 1609.1.1. NO ATTACHMENT DETAILS WERE FOUND. NOTE
 4 FOUND ON THE SAME PAGE INDICATES THIS CONNECTION TO
 BE DESIGNED BY TRUSS ENGINEER. PLEASE PROVIDE
 CONNECTIONS AND TRUS ENGINEERING. TRUSS ENGINEERS
 NORMALLY PROVIDE TRUSS TO TRUSS CONNECTIONS. NOT THE
 TRUSS TO BEAM CONNECTIONS.
 PLEASE SHOW LOADS TO BE RESISTED INCLUDING UPLIFT,
 LATERAL & GRAVITY LOADS INCLUDING LOADS TO BE
 CONSIDERED IN COMMENT (5A).
  
  
  
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER C.B.O.
 COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: (561)805-6715
 FAX:(561)805-6731
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2011-07-25 Cont ID  
Sent By rlecky Date 2011-07-25 Time 14:51 Rev Time 0.00
Received By rlecky Date 2011-07-25 Time 13:01 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2011-05-27 Cont ID  
Sent By rlecky Date 2011-05-27 Time 16:18 Rev Time 0.00
Received By rlecky Date 2011-05-16 Time 09:13 Sent To  
Notes
2011-05-27 16:18:11GE4:
 PROVIDE NOTES ON THE PLAN OR REFERENCE THE
 SPECIFICATIONS FOR THE REQUIRED SAFETY WARNINGS AT
 ENTRANCES ETC. NEC 110.31
 PROVIDE NOTES ON THE PLAN OR REFERENCE THE
 SPECIFICATIONS FOR THE REQUIRED FIELD MARKINGS FOR
 FLASH PROTECTION. NEC 110.16
 E4:
 MINIMUM ELECTRIC DUCT SEPARATION IS 7.5 INCHES. NEC
 310.60
 15S-2:
 CONTAINMENT CURB SHOULD BE OF SUFFICIENT HEIGHT TO
 CONFINE THE OIL FROM THE LARGEST TRANSFORMER WITHIN THE
 VAULT OR NO LESS THAN 4 INCHES IN HEIGHT. NEC 450.43(B)
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 561-805-6718
  
  

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2011-09-06 Cont ID  
Sent By mgonzale Date 2011-09-06 Time 17:08 Rev Time 1.00
Received By mgonzale Date 2011-09-06 Time 17:08 Sent To  
Notes
2011-09-06 17:09:04PASSED THRU ESD
  
 MANUEL JULIAN GONZALEZ
 CSD ENGINEERING REVIEW.
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET,
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status N Date 2011-08-15 Cont ID  
Sent By mgonzale Date 2011-08-15 Time   Rev Time 1.00
Received By mgonzale Date 2011-08-15 Time   Sent To  
Notes
2011-08-15 12:58:21SITE UTILITIES ARE BEING REVIEWED THRU ESD PERMIT
 E11070023.
  
 PLAN IS ACCEPTABLE.
  
 MANUEL JULIAN GONZALEZ
 CSD ENGINEERING REVIEW
 401 CLEMATIS STREET,
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2011-05-23 Cont ID  
Sent By mgonzale Date 2011-05-23 Time   Rev Time 0.50
Received By mgonzale Date 2011-05-23 Time   Sent To  
Notes
2011-05-23 16:03:50PLEASE SUBMITT PLANS TO ENGINEERING SERVICES DEPARTMENT
 PLEASE REPLY TO COMMENTS IN WRITING.
  
 1. SITE DEVELOPMENT PERMIT IS REQUIRED.
 ALL CIVIL SITE SHEET SHOULD BE INCLUDED.
  
 2 INCLUDE CERTIFIED COST ESTIMATE AS FOUND IN LINK
 BELOW.
 HTTP://WWW.CITYOFWPB.COM/ENGINEERING/ENG_FORMS.PHP
  
 3. PROVIDE TWO COPIES OF SITE DRAINAGE CALCULATIONS.
 SIGNED AND SEALED.
  
 4. INCLUDE ALL SHEETS WITH CITY OF WPB UTILITY DETAILS.
 SUCH AS GC SHEETS.
  
 5. INCLUDE APPROVED MATERIAL LIST FOR PRODUCTS TO BE
 USED.
  
 6. RELOCATED ITEMS THAT ARE NOT ON THE APPROVED PRODUCT
 LIST MUST BE LISTED AS ADDENDUM.
  
 7. FPL EASEMENT LOCATED EAST OF PROPOSED BUILDING IS
 NOT SHOWN ON ANY CIVIL PLAN.
  
 8. ON SHEET C-8 DEPTH OF PROPOSED YARD PIPING IS NOT
 SHOWN. PLEASE SHOW CROSS SECTION OF PIPES RUNNING
 NORTH-SOUTH AND EAST-WEST ALONG PROPOSED BUILDING.
  
 9. NO WATER OR SEWER SERVICE SHOWN TO SERVE PROPOSED
 BUILDING.
  
 10. IDENTIFY SIZE OF RELOCATED BACKFLOW PREVENTERS AND
 TYPE, DCDA, RPPA, ETC.
  
 11. RELOCATED HYDRANT REFERENCES OCTAGON SYMBOL WITH
 C-626 (SUPPLY SHEET NUMBER WHERE C-626 IS FOUND)
  
  
  
 MANUEL JULIAN GONZALEZ
 CSD ENGINEERING REVIEW
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2011-07-22 Cont ID  
Sent By wjolin Date 2011-07-22 Time 10:05 Rev Time 0.00
Received By wjolin Date 2011-07-22 Time 09:16 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2011-05-18 Cont ID  
Sent By mcarsill Date 2011-05-18 Time 15:32 Rev Time 0.00
Received By mcarsill Date 2011-05-18 Time 12:51 Sent To  
Notes
2011-05-18 15:32:451009 BANYAN BOULEVARD
 PERMIT NUMBER 11050023
 'CONSTRUCTION OF A NEW ELECTRICAL / GENERATOR BUILDING
 AND ASSOCIATED FUEL TANKS"
  
  
 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241.
  
 2. DEBRIS SHALL BE REMOVED FROM THE SITE DAILY OR AS
 OFTEN AS NECESSARY.
  
 3. FIRE AND PARAMEDICAL ACCESS IS TO BE MAINTAINED TO
 THE CONSTRUCTION SITE.
  
 4. ALL CUTTING AND WELDING OPERATIONS SHALL COMPLY WITH
 NFPA 51B. CUTTING AND WELDING OPERATIONS SHALL NOT
 OCCUR IN FLAMMABLE GAS LOCATIONS AND A MINIMUM OF AT
 LEAST 35 FEET CLEARANCE IS REQUIRED TO ANY COMBUSTIBLE
 MATERIALS.
  
 5. ALL ELECTRICAL WORK TO COMPLY WITH NFPA 70, THE
 NATIONAL ELECTRICAL CODE.
  
 6. SEPARATE PLANS AND PERMITS REQUIRED FOR THE FUEL
 TANKS AND GENERATORS.
  
 7. ALL EMERGENCY SHUT-OFFS ARE TO BE PROPERLY
 IDENTIFIED WITH SIGNAGE INDICATING WHAT SYSTEM OR
 DEVICE IT SHUTS OFF.
  
 8. BUILDING ADDRESS REQUIRED. A MINIMUM OF AT LEAST 6"
 HIGH AND AT LEAST 1" WIDE NUMBERS ARE TO BE PROVIDED.
  
 9. A KNOX-BOX WILL BE REQUIRED. A KNOX-BOX CAN BE
 ORDERED AT WWW.KNOX-BOX.COM.
  
 10. DUE TO THE EQUIPMENT CONTAINED IN THE BUILDING, THE
 BUILDING NEEDS TO BE PROPERLY LABELED.
  
 11. ALL FIRE DAMPERS ARE TO BE TESTED TO ENSURE PROPER
 OPERATION AFTER INSTALLATION.
  
 12. PLEASE PROVIDE MORE DETAILS ON ACOUSTIC BLANKETS
 PLANNED BETWEEN THE TRUSSES. (FLAME SPREAD AND SMOKE
 DEVELOPMENT)
  
 13. DIESEL FUEL STORAGE TANKS AND THEIR APPURTENANCES
 SHALL COMPLY WITH NFPA 30.
  
 14. PLEASE INDICATE ALL WARNING SIGNS, LABELS, AND
 LOCATIONS OF THE NFPA 704 DIAMONDS FOR THE FUEL STORAGE
 TANKS.
  
 15. SEPARATE PLANS AND PERMITS REQUIRED FOR THE FM-200
 SYSTEM PLANNED FOR THE TRANSFORMER ROOM.
  
 16. GENERATORS TO COMPLY WITH NFPA 37 AND NFPA 110.
  
 17. MORE DETAILS NEEDED ON FIRE ALARM RISER SHOWN ON
 PAGE E-31.
  
 18. PROPER CLEARANCES ARE TO BE PROVIDED TO ELECTRICAL
 EQUIPMENT AND PANELS PER NFPA 70, THE NATIONAL
 ELECTRICAL CODE.
  
 19. ALL TEMPORARY ELECTRICAL FEEDS AND EQUIPMENT SHALL
 BE PROPERLY SAFEGUARDED TO PREVENT INJURIES OR FIRES.
  
 20. APPROPRIATE SIGNAGE WILL BE NECESSARY TO PREVENT
 STORAGE IN EXHAUST AND SUPPLY AIR AREAS.
  
 21. ALL FIRE WALLS ARE TO BE PROPERLY LABELED PER THE
 FLORIDA BUILDING AND FLORIDA FIRE PREVENTION CODE.
  
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
  
  
  
  

Review Stop HIST HISTORICAL
Rev No 1 Status N Date 2011-06-01 Cont ID  
Sent By jroach Date 2011-06-01 Time 09:51 Rev Time 0.00
Received By jroach Date 2011-06-01 Time 09:51 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-08-24 Cont ID  
Sent By hmoser Date 2011-08-24 Time 12:57 Rev Time 0.00
Received By hmoser Date 2011-07-19 Time 15:04 Sent To  
Notes
2011-07-19 15:09:32C--26

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-07-19 Cont ID  
Sent By lmartine Date 2011-06-08 Time 15:03 Rev Time 0.00
Received By lmartine Date 2011-05-02 Time 17:49 Sent To  
Notes
2011-05-02 17:52:19C26

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2011-08-24 Cont ID  
Sent By hmoser Date 2011-08-24 Time 12:57 Rev Time 0.00
Received By hmoser Date 2011-08-24 Time 10:53 Sent To  
Notes
2011-08-24 12:56:34PASS PROVISO
 PROVIDE A LETTER FROM THE ENGINEER ON FLOOR SUPPORT
 DETAIL # H-900 PAGE GH-2
 WHAT TYPE OF ANCHORING DEVICE IS BEING USED.
 PROVIDE PRODUCT APPROVALS FOR THE LOUVERS,PER SECTION
 106.3.3 2007 FBC
 SUPPLY FANS OVER 2000 CFM REQUIRE FAN SHUTDOWN PER
 SECTION 606.2.1.
 REFER TO SECTION 606.4.1 SUPERVISION.
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2011-06-07 Cont ID  
Sent By hmoser Date 2011-06-07 Time 10:39 Rev Time 0.00
Received By hmoser Date 2011-06-07 Time 09:16 Sent To  
Notes
2011-06-07 10:48:05PLANS DENIED
 1) SUBMIT PLANS TO DERM ON THE FUEL TANKS.
 2) THERE WAS NO AIRCONDITIONING DUCT PLANS SUBMITTED.
 SEE PAGE GH-1IN THE PLANS.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732
 E MAIL [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2011-08-22 Cont ID  
Sent By jroach Date 2011-08-22 Time 08:59 Rev Time 0.00
Received By jroach Date 2011-08-22 Time 08:59 Sent To  
Notes
2011-08-22 09:00:12PROVISO
  
 1. PRIOR TO THE ISSUANCE OF A CERTIFICATE OF
 COMPLETION, THE STORAGE TANKS SHALL BE SCREENED IN
 ACCORDANCE WITH SECTION 94-444(B) OF THE CITY?S ZONING
 AND LAND DEVELOPMENT REGULATIONS, INCLUDING THE
 INSTALLATION OF A WALL/FENCE AND LANDSCAPING.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.
  

Review Stop Z ZONING
Rev No 1 Status F Date 2011-06-01 Cont ID  
Sent By jroach Date 2011-06-01 Time 09:51 Rev Time 0.00
Received By jroach Date 2011-06-01 Time 09:51 Sent To  
Notes
2011-06-01 09:52:19ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 06.01.2011
 PERMIT NO.: 11050023
 ADDRESS: 1009 BANYAN BOULEVARD
 CONTRACTOR/CONTACT: CITY OF WEST PALM BEACH
 TELEPHONE NO.:
 SCOPE OF REVIEW: CONSTRUCTION OF A NEW
 ELECTRICAL/GENERATOR BUILDING AND ASSOCIATED FUEL
 TANKS.
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. TWO (2) COPIES OF A SITE PLAN SHALL BE PROVIDED
 INDICATING THE FOLLOWING:
  
 A. LOCATION OF THE PROPERTY LINE, RIGHT-OF-WAY,
 PROPOSED/EXISTING EASEMENTS, WATER COURSES AND OTHER
 ESSENTIAL FEATURES.
 B. THE OUTLINES OF ALL EXISTING BUILDINGS.
 C. THE OUTLINES OF ALL PROPOSED BUILDINGS/STRUCTURES
 SHOWING THEIR PROPOSED USES, SETBACKS, DIMENSIONS,
 FLOOR AREA, NUMBER OF STORIES, HEIGHT AND POINTS OF
 ACCESS.
 D. LOCATION AND DIMENSIONS OF ALL PERIMETER TREATMENT
 (SIDEWALKS, FENCES, WALLS, OR BERMS).
 E. LAYOUT AND LOCATION OF ALL EXISTING AND PROPOSED
 OFF-STREET PARKING, LOADING AND OTHER VEHICULAR USE
 AREAS.
 F. LOCATION OF ALL EXISTING AND PROPOSED DISABLED
 SPACES, RAMPS AND SIGNS.
 G. STANDARD CITY DETAILS OF PARKING (SMALL CAR,
 HANDICAP SPACE, STANDARD SPACE), HANDICAP RAMPS,
 DRIVEWAYS, DUMPSTERS AND SIGNS.
 H. SUPPLY A DATA TABLE WHICH INDICATES THE FOLLOWING:
 I. EXISTING/PROPOSED LAND USE AND ZONING.
 II. TOTAL ACRES OF THE PROJECT.
 III. TOTAL GROSS BUILDING SQUARE FOOTAGE.
 IV. PERCENT OF OPEN SPACE, LANDSCAPING, BUILDING
 COVERAGE & IMPERMEABLE SURFACE.
 V. ACRES AND PERCENT OF WATER BODIES.
 VI. PARKING COMPUTATIONS (PARKING REQUIRED, PROVIDED,
 ETC.)
 VII. FLOOR AREA RATIO (FAR).
  
 2. TWO (2) COPIES OF A CURRENT AND ACCURATE SURVEY
 SHALL BE PROVIDED.
  
 3. TWO (2) COPIES OF A LANDSCAPE PLAN SHALL BE
 PROVIDED. LANDSCAPING SHALL BE PROVIDED FOR ?LIMITS OF
 WORK? IN COMPLIANCE WITH ARTICLE XIV OF THE CITY?S
 ZONING AND LAND DEVELOPMENT REGULATIONS.
  
 4. IT APPEARS THAT TREES ARE BEING REMOVED TO
 ACCOMMODATE THE NEW CONSTRUCTION. AS SUCH, A TREE
 ALTERATION PERMIT SHALL BE OBTAINED FROM THE CITY?S
 PLANNING AND ZONING DEPARTMENT. PLEASE INCLUDE A COPY
 OF THE APPROVED PERMIT WITH THE BUILDING PERMIT
 APPLICATION.
  
 5. AS DISCUSSED PREVIOUSLY, BUFFER LANDSCAPING IS
 REQUIRED ALONG THE EAST PROPERTY LINE. IT IS STRONGLY
 RECOMMENDED THAT THIS REQUIRED LANDSCAPING OCCUR ON THE
 EXTERIOR OF THE PROPOSED WALL.
  
 6. DETAILS SHALL BE PROVIDED REGARDING THE PROPOSED
 PRECAST WALL. WHILE IT MAY BE PERMITTED BY ?OTHERS?,
 INFORMATION SHALL BE PROVIDED WITH THIS PERMIT
 APPLICATION, AS A FINAL INSPECTION WILL NOT OCCUR UNTIL
 SUCH WALL HAS BEEN INSTALLED.
  
 7. PURSUANT TO SECTION 94-273(D)(79)(B)(2) OF THE
 CITY?S ZONING AND LAND DEVELOPMENT REGULATIONS, ABOVE
 GROUND STORAGE TANKS ARE TO BE ENCLOSED BY A SOLID WALL
 OR FENCE. IT IS UNDERSTOOD THAT THE ENTIRE EAST
 PROPERTY LINE WILL CONTAIN A SOLID WALL AT A FUTURE
 DATE, HOWEVER, THE SECTION PROPOSED TO BE INSTALLED AT
 THIS TIME TO SCREEN THE DIESEL/FUEL STORAGE FACILITY
 SHOULD BE EXTENDED FURTHER NORTH AND SOUTH TO BETTER
 SCREEN THE TANKS FROM VIEW UNTIL THE REMAINING PORTIONS
 ARE INSTALLED.
  
 8. AS PARKING IS BEING REMOVED, DETAILED CALCULATIONS
 SHALL BE PROVIDED TO ENSURE THAT NO NEW NONCONFORMITY
 IS CREATED OR THAT AN EXISTING NONCONFORMITY IS
 INCREASED. PLEASE PROVIDE THE TOTAL GROSS SQUARE
 FOOTAGE OF ?HABITABLE? SPACE (EXCLUDE MECHANICAL
 SPACE), ALONG WITH THE NUMBER OF EXISTING SPACES,
 PROPOSED SPACES, ETC. PARKING SHALL BE PROVIDED FOR ONE
 (1) SPACE PER 500 SQUARE FEET.
  
 9. THE PAVEMENT MARKING PLAN PROVIDES A NOTE THAT
 EXISTING PARKING SHALL BE RESTRIPED TO REMOVE TWO (2)
 REGULAR PARKING SPACES, AND ADD ONE (1) HANDICAP SPACE.
 THIS IS NOTED IN TWO (2) SEPARATE AREAS. THE SITE PLAN,
 ETC. SHALL INDICATE HOW THIS WILL BE CONFIGURED. A
 PARKING STRIPING DETAIL SHALL ALSO BE PROVIDED. BE SURE
 TO ACCOUNT FOR THE LOSS OF SPACES IN THE OVERALL
 PROPOSED PARKING COUNTS.
  
 10. PLANS SHALL NOTE THE OVERALL HEIGHT OF THE PROPOSED
 FUEL TANKS AND DESCRIBE HOW THESE WILL ADEQUATELY BE
 SCREENED.
  
 11. PLANS SHALL NOTE THE OVERALL BUILDING HEIGHT OF THE
 GENERATOR BUILDING, AS MEASURED FROM GRADE TO THE MEAN
 POINT OF THE PITCHED ROOF.
  
 12. HAS ANY INFORMATION BEEN COLLECTED REGARDING THE
 NOISE LEVELS THAT WILL BE GENERATED AS A RESULT OF THE
 PROPOSED GENERATORS? AS EXPRESSED PREVIOUSLY, CONCERNS
 EXIST REGARDING THE PRODUCTION OF EXCESSIVE NOISE
 WITHIN CLOSE PROXIMITY OF THE RESIDENTIAL NEIGHBORHOOD.
 PLEASE PROVIDE ANY INFORMATION AVAILABLE REGARDING THE
 EXPECTED NOISE LEVELS GENERATED FROM THE PROPOSED
 EQUIPMENT.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, SENIOR PLANNER
 CITY OF WEST PALM BEACH
 PLANNING AND ZONING DEPARTMENT
 401 CLEMATIS STREET - P.O. BOX 3366
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1435
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.CITYOFWPB.COM
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved