Plan Review Details - Permit 11050013
Plan Review Stops For Permit 11050013
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2011-05-23 Cont ID  
Sent By ddaniels Date 2011-05-23 Time 13:40 Rev Time 0.00
Received By ddaniels Date 2011-05-23 Time 13:40 Sent To M
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2011-05-03 Cont ID  
Sent By wjolin Date 2011-05-03 Time 13:58 Rev Time 0.00
Received By wjolin Date 2011-05-03 Time 12:26 Sent To M
Notes
2011-05-03 13:58:104233 UP THE GROVE LANE
 PERMIT #11050013
 MASTER #10120325
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PROVIDE INSPECTORS TEST CONNECTION FOR MEANS OF TESTING
 WATERFLOW SWITCH.
  
 SHOP DRAWINGS INDICATE A HYDRAULICALLY REMOTE AREA OF
 1500 SQUARE FEET WHICH IS CONSISTENT WITH ENGINEER OF
 RECORD CONSTRUCTION DRAWINGS; HOWEVER, THE ACTUAL AREA
 CALCULATED APPEARS TO BE ROUGHLY 1250 SQUARE FEET. TO
 DEVIATE FROM THE CONSTRUCTION DRAWINGS AND USE THE AREA
 REDUCTION METHOD FOR QUICK RESPONSE SPRINKLERS, THE
 ENGINEER OF RECORD MUST PROVIDE DOCUMENTATION TO THE
 AHJ THAT THIS ALTERNATE DESIGN IS ACCEPTABLE.
  
 PROVIDE HYDRAULIC CALCULATIONS STARTING AT THE REMOTE
 END OF THE BRANCH LINE (DOWNSTREAM OF HYDRAULIC NODE
 1).
  
 INDICATE THE RESPONSIBLE PARTY FOR THE FIRE DEPARTMENT
 CONNECTION AND BACKFLOW PREVENTER. LOCKING KNOX CAPS
 ARE REQUIRED ON THE FIRE DEPARTMENT CONNECTION AND THE
 BACKFLOW PREVENTER REQUIRES TAMPER SWITCHES AND A CHAIN
 WITH LOCK.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-05-31 Cont ID  
Sent By hmoser Date 2011-05-31 Time 15:45 Rev Time 0.00
Received By hmoser Date 2011-05-23 Time 09:32 Sent To  
Notes
2011-05-23 09:33:09TO FIRE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-05-05 Cont ID  
Sent By hmoser Date 2011-05-05 Time 10:33 Rev Time 0.00
Received By hmoser Date 2011-05-02 Time 16:51 Sent To  
Notes
2011-05-02 16:51:56TO FIRE
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2011-05-31 Cont ID  
Sent By hmoser Date 2011-05-31 Time 15:44 Rev Time 0.00
Received By hmoser Date 2011-05-31 Time 15:38 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2011-05-05 Cont ID  
Sent By hmoser Date 2011-05-05 Time 10:28 Rev Time 0.00
Received By hmoser Date 2011-05-05 Time 09:50 Sent To  
Notes
2011-05-05 10:32:56PLAN DENIED
 CAN NOT READ PIPE SIZE ON THE PLANS .PLEASE PROVIDE A
 LARGER PLAN
 REFER TO SECTION 106.1.1 FBC
 PLAN REVIEW BY HAROLD MOSER 561-805-6732