Plan Review Details - Permit 11040776
Plan Review Stops For Permit 11040776
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2011-05-10 Cont ID  
Sent By rmcdouga Date 2011-05-10 Time 11:30 Rev Time 0.00
Received By rmcdouga Date 2011-05-10 Time 11:30 Sent To  
Notes
2011-05-10 11:34:08CHANGED FROM SPRAY FOAM TO R-30 BATT INSULATION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2011-05-05 Cont ID  
Sent By rmcdouga Date 2011-05-05 Time 08:48 Rev Time 0.00
Received By rmcdouga Date 2011-05-05 Time 07:48 Sent To  
Notes
2011-05-05 08:45:43PROVISO
  
 SUBMIT SPECIFICATIONS FOR THE SPRAY FOAM INSULATION. IF
 WOOD ROOF DECK IS COVERED WITH PEEL AND STICK
 UNDERLAYMENT, THEN SEE APA TECHNICAL BULLETIN TT-111.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2011-05-05 Cont ID  
Sent By rmcdouga Date 2011-05-05 Time 11:31 Rev Time 0.00
Received By rmcdouga Date 2011-05-05 Time 09:00 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-05-05 Cont ID  
Sent By rmcdouga Date 2011-05-05 Time 11:31 Rev Time 0.00
Received By rmcdouga Date 2011-05-02 Time 09:44 Sent To  
Notes
2011-05-02 09:45:09SENT TO R9.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2011-05-10 Cont ID  
Sent By rmcdouga Date 2011-05-10 Time 11:09 Rev Time 0.00
Received By rmcdouga Date 2011-05-10 Time 11:09 Sent To  
Notes
2011-05-10 11:16:28PER ROGER THOMAS, THE MECHANICAL CONTRACTOR WILL SUBMIT
 SEPARATELY. A SEPARATE PERMIT APPLICATION, PLANS AND
 ENERGY CALCULATIONS WILL BE REQUIRED.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2011-05-05 Cont ID  
Sent By rmcdouga Date 2011-05-05 Time 07:06 Rev Time 0.00
Received By rmcdouga Date 2011-05-05 Time 07:06 Sent To  
Notes
2011-05-05 07:39:202007 FBC W/2009 REVISIONS
  
 DENIED BY MECHANICAL
  
 1) SUBMIT TWO SETS OF MECHANICAL PLANS SPECIFYING THE
 LOCATION AND SIZES OF THE NEW SUPPLY AND RETURN DUCTS,
 TRANSFER DUCTS, TRANSFER GRILLS, ETC. SPECIFY THE GRILL
 SIZES, LOCATIONS AND CFMS ON THE PLANS. CITY AMENDMENTS
 106.3.5.4
  
 2) THE NAME, SIGNATURE AND LICENSE NUMBER OF THE HVAC
 CONTRACTOR OR TITLE BLOCK, SIGNATURE AND SEALED OF THE
 DESIGN PROFESSIONAL IS REQUIRED ON THE MECHANICAL
 PLANS. CITY AMENDMENTS 106.1.3
  
 3) SUBMIT ENERGY CALCULATIONS AND EQUIPMENT SIZING
 CALCULATIONS TO VERIFY THAT THE EXISTING HVAC SYSTEM
 WILL BE ADEQUATE FOR THE ADDITIONAL LOAD. CITY
 AMENDMENTS 106.3.5.4
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status P Date 2011-05-05 Cont ID  
Sent By rmcdouga Date 2011-05-05 Time 07:06 Rev Time 0.00
Received By rmcdouga Date 2011-05-05 Time 07:06 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2011-05-05 Cont ID  
Sent By rmcdouga Date 2011-05-05 Time 08:49 Rev Time 0.00
Received By rmcdouga Date 2011-05-05 Time 08:49 Sent To  
Notes
***NONE***