Plan Review Details - Permit 11040749
Plan Review Stops For Permit 11040749
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2011-05-03 Cont ID  
Sent By rlecky Date 2011-05-03 Time 10:52 Rev Time 0.00
Received By rlecky Date 2011-05-03 Time 10:52 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2011-04-29 Cont ID  
Sent By rlecky Date 2011-04-29 Time 14:12 Rev Time 0.00
Received By rlecky Date 2011-04-29 Time 12:41 Sent To  
Notes
2011-04-29 14:14:09ELECTRICAL PLAN INSUFFICIENTLY DETAILED TO APPROVE.
 PLEASE PROVIDE THE FOLLOWING.
  
 PROVIDE TYPICAL PANEL SCHEDULE WITH BREAKER SIZES
 INCLUDING MAIN DISCONNECT.
 SUMMARIZE THE ELECTRICAL LOAD TO VERIFY THE EXISTING
 CAPACITY IS SUFFICIENT.
 SHOW AFCI PROTECTED CIRCUITS
 SHOW REQUIRED 20 AMP BRANCH CIRCUITS
 SHOW RANGE AND WATER HEATER
 SHOW HEAT AND AIR CONDITIONING
 PROVIDE INTERCONNECTED SMOKE DETECTORS AND CARBON
 MONOXIDE DETECTOR
 LOCATE ELECTRIC PANEL ON PLAN
 ADD RECEPTACLES SO THAT NO WALL SPACE IS MORE THAN 6
 FEET FROM A RECEPTACLE
 NEW RECEPTACLES MUST BE TAMPER RESISTANT
 VERIFY WORK VALUE WITH COPY OF CONTRACT.
 RESUBMIT THE SECOND FLOOR PLAN. COPY IS OF POOR QUALITY
 AND NOT REPRODUCIBLE FOR IMAGING PURPOSES.
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 561-805-6718
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-05-03 Cont ID  
Sent By rlecky Date 2011-05-03 Time 10:53 Rev Time 0.00
Received By rlecky Date 2011-05-03 Time 10:53 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-04-29 Cont ID  
Sent By rlecky Date 2011-04-29 Time 14:11 Rev Time 0.00
Received By rlecky Date 2011-04-29 Time 09:39 Sent To  
Notes
2011-04-29 09:40:29SENT TO ELECTRICAL UNDER $5000 BOX.