| 2011-05-03 09:36:55 | BUILDING PLAN REVIEW |
| | PERMIT: 11040736 |
| | ADD: 777 S FLAGLER DR #900W |
| | CONT: ALL FLAGS CONSTRUCTION |
| | TEL: (561)904-6005 |
| | |
| | FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| | W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 2007 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1) THE HIGH DENSITY FILE ROOMS # 902 & 916 ARE BOTH |
| | OVER 100 SQUARE FEET AND NEED TO MEET THE REQUIREMENTS |
| | FOUND IN 2007 FBC-B TABLE |
| | 508.2 AND SECTION 508.2.2.1 FOR CONSTRUCTION. TABLE |
| | 508.2 DOES GIVE ALLOWANCES FOR FIRE PROTECTION AS FAR |
| | AS NOT NEEDING FIRE RATING ON THE WALLS, BUT THE ROOMS |
| | WILL STILL NEED TO BE CONSTRUCTED TO MEET THE |
| | REQUIREMENTS OF 508.2.2.1. |
| | WHERE TABLE 508.2 PERMITS AN AUTOMATIC |
| | FIRE-EXTINGUISHING SYSTEM WITHOUT A FIRE BARRIER, THE |
| | INCIDENTAL USE AREA SHALL BE SEPARATED FROM THE |
| | REMAINDER OF THE BUILDING BY CONSTRUCTION CAPABLE OF |
| | RESISTING THE PASSAGE OF SMOKE. THE PARTITIONS SHALL |
| | EXTEND FROM THE FLOOR TO THE UNDERSIDE OF THE |
| | FIRE-RESISTANCE-RATED FLOOR/CEILING ASSEMBLY OR |
| | FIRE-RESISTANCE-RATED ROOF/CEILING ASSEMBLY ABOVE OR TO |
| | THE UNDERSIDE OF THE FLOOR OR ROOF SHEATHING, OR SUB |
| | DECK ABOVE. DOORS SHALL BE SELF- OR AUTOMATIC CLOSING |
| | UPON DETECTION OF SMOKE IN ACCORDANCE WITH SECTION |
| | 715.4.7.3. DOORS SHALL NOT HAVE AIR TRANSFER OPENINGS |
| | AND SHALL NOT BE UNDERCUT IN EXCESS OF THE CLEARANCE |
| | PERMITTED IN ACCORDANCE WITH NFPA 80. |
| | |
| | JAMES A. WITMER C.B.O. |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: (561)805-6715 |
| | FAX:(561)805-6731 |
| | E-MAIL: [email protected] |
| | |