Plan Review Details - Permit 11040709
Plan Review Stops For Permit 11040709
Review Stop E ELECTRICAL
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2011-04-29 Cont ID  
Sent By rlecky Date 2011-04-29 Time 15:23 Rev Time 0.00
Received By rlecky Date 2011-04-29 Time 15:23 Sent To  
Notes
2011-04-29 15:34:31REVISON REQUIRES SOME ADDITIONAL INFORMATION. PLEASE
 HAVE ELECTRICAL CONTRACTOR UPDATE THE PLAN WITH AS
 BUILT CONDITIONS.
  
 AS EXAMPLE THE REQUIRED SMOKE AND CARBON MONIXODE
 DECTORS ARE NOT CLEARLY SHOWN. THE ELECTRICAL RISER
 SHOWS TWO PANELS WITH THE SAME ( "A") DESIGNATION. WIRE
 SIZES ON THE PANEL SCHEDULES FOR THE WALL OVEN AND
 KITCHEN ARE INCORRECT. ETC.
  
 ALL REVISIONS/CHANGES SHOULD BE CLOUDED AND PROPERLY
 REFERANCED.
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 561-805-6718
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-05-06 Cont ID  
Sent By lwagner Date 2011-05-06 Time 11:12 Rev Time 0.00
Received By lwagner Date 2011-04-27 Time 16:14 Sent To  
Notes
2011-04-27 16:16:55INCOMING SENT TO R4. JW

Review Stop P PLUMBING
Rev No 1 Status P Date 2011-05-06 Cont ID  
Sent By lwagner Date 2011-05-06 Time 11:05 Rev Time 0.00
Received By lwagner Date 2011-05-06 Time 10:37 Sent To  
Notes
2011-05-06 10:59:08CHANGE TO LOCATION OF BUILDING SEWER
  