Plan Review Details - Permit 11040705
Plan Review Stops For Permit 11040705
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2011-05-10 Cont ID  
Sent By shill Date 2011-05-10 Time 10:01 Rev Time 0.00
Received By shill Date 2011-05-10 Time 10:01 Sent To  
Notes
2011-05-10 10:02:17PROVISO
  
 LETTER FROM ARCHITECT WITH CORRECT LICENSE # AND
 LEGIBLE SEAL REQUIRED AT TIME OF PERMIT PICKUP
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-05-03 Cont ID  
Sent By shill Date 2011-05-03 Time 10:15 Rev Time 0.00
Received By shill Date 2011-05-03 Time 10:15 Sent To  
Notes
2011-05-03 10:25:48****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. IT IS NOT EVIDENT WHO IS TAKING RESPONSIBILITY FOR
 THE PLAN; SEE ALL A SHEETS SUBMITTED. PLEASE SEE
 FLORIDA STATUTE 481.221 REGARDING SEAL AND TITLE BLOCK.
 I WAS UNABLE TO LOCATE THE FLORIDA BUSINESS LICENSE #
 ON THE TITLE BLOCK (APPEARS TO BE AAC001619, 1618 OR
 1819? DIFFICULT TO READ) ON THE DBPR WEBSITE
 (WWW.MYFLORIDALICENSE.COM). THE ARCHITECT BUSINESS
 LICENSE NUMBER FOR ASD ON THE WEBSITE IS A DIFFERENT
 NUMBER THAN THE ONE PRINTED ON THE PLAN. IT APPEARS
 THAT KENNETH COWART HAS SIGNED THE PLAN, BUT HIS
 PRINTED LICENSE NUMBER IS NOT INCLUDED IN THE TITLE
 BLOCK, AND BOTH THE SIGNATURE AND THE SEAL ARE
 ILLEGIBLE.
  
 IF ALL OTHER TRADES PASS REVIEW, PLEASE CONTACT ME TO
 DISCUSS A POSSIBLE PROVISO.
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2011-05-04 Cont ID  
Sent By rlecky Date 2011-05-04 Time 12:17 Rev Time 0.00
Received By rlecky Date 2011-05-04 Time 12:17 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2011-05-04 Cont ID  
Sent By ddaniels Date 2011-05-04 Time 12:21 Rev Time 0.00
Received By ddaniels Date 2011-05-02 Time 13:22 Sent To  
Notes
2011-05-02 13:25:345/02/11 PLANS REVIEWED BY FIRE **APPROVED**
  
 1. REQUIRED BY NFPA 241. ACCUMULATION OF UNECCESSARY
 COMBUSTIBLE FORMS OR DEBRIS SHALL BE PROHIBITED.
 2. DAILY REMOVAL OF CONSTRUCTION DEBRIS IS REQUIRED BY
 AHJ.
  
 CAPATAIN DERRICK DANIELS
 BUREAU OF FIRE PREVENTION

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-05-10 Cont ID  
Sent By shill Date 2011-05-10 Time 10:02 Rev Time 0.00
Received By shill Date 2011-04-28 Time 12:36 Sent To  
Notes
2011-04-28 12:51:45*****************EXPEDITED******************
 B--1

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2011-05-05 Cont ID  
Sent By hmoser Date 2011-05-05 Time 10:47 Rev Time 0.00
Received By hmoser Date 2011-05-05 Time 10:47 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2011-05-05 Cont ID  
Sent By aaponte Date 2011-05-05 Time 11:33 Rev Time 0.10
Received By aaponte Date 2011-05-05 Time 11:33 Sent To  
Notes
***NONE***