| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | THE SCOPE OF WORK INDICATES THE RELOCATION OF 17 |
| | SPRINKLERS. THIS SCOPE AND JOB VALUE IS NOT CONSISTENT |
| | WITH THE AMOUNT OF DEMOLITION WORK SHOWN ON SHEETS |
| | A2.1, A3.1 AND P1.1 OF THE ARCHITECTURAL AND MEP |
| | DRAWINGS. FOR EXAMPLE, THE SPRINKLERS SHOWN IN THE |
| | LARGE STORAGE ROOM CANNOT BE EXISTING TO REMAIN AS |
| | THERE WAS A CEILING GRID SHOWN IN THIS AREA. |
| | |
| | THE HATCHED AREA LABELED TO REMAIN "AS IS" NEEDS TO BE |
| | MODIFIED. NEW RESTROOM WALLS ARE SHOWN OBSTRUCTING |
| | SPRINKLER SPRAY. THE SPRINKLER COVERAGE IN THE JANITOR |
| | STORAGE ROOM EXCEEDS 130 SQUARE FEET AND A BRANCH LINE |
| | IS SHOWN RUNNING THROUGH THE ELECTRICAL ROOM. |
| | |
| | PER NFPA 13, INDICATE THE HAZARD CLASSIFICATION AND |
| | DENSITY OF STORAGE AREAS. |
| | |
| | INDICATE THE STRUCTURE TYPE/SIZE AND CONSTRUCTION TYPE |
| | (OBSTRUCTED OR UNOBSTRUCTED) FOR THE LARGE STORAGE ROOM |
| | THAT IS OPEN TO THE ROOF DECK. INDICATE THE SPRINKLER |
| | LOCATIONS IN RELATION TO THE CEILING OR STRUCTURE. |
| | INDICATE THE FLOOR TO ROOF DECK HEIGHT. |
| | |
| | PER NFPA 13, INDICATE WHAT MATERIALS/COMMODITIES WILL |
| | BE STORED, HOW THE MATERIALS WILL BE STORED AND |
| | PACKAGED, THE HEIGHT OF STORAGE ETC. FOR THE LARGE |
| | STORAGE ROOM. NOTE: QUICK RESPONSE SPRINKLERS MAY NOT |
| | BE APPROPRIATE FOR STORAGE PROTECTION. |
| | |
| | PER NFPA 13, PROVIDE 1.5 INCH HOSE CONNECTION(S) FOR |
| | LARGE STORAGE ROOM. |
| | |
| | PROVIDE HYDRAULIC CALCULATIONS SUPPORTING THE DESIGN IN |
| | THE LARGE STORAGE ROOM. |
| | |
| | WESLEY JOLIN |
| | WEST PALM BEACH FIRE RESCUE |
| | FIRE & LIFE SAFETY PLAN REVIEW |