Plan Review Details - Permit 11040655
Plan Review Stops For Permit 11040655
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2011-05-10 Cont ID  
Sent By shill Date 2011-05-10 Time 09:38 Rev Time 0.00
Received By shill Date 2011-05-10 Time 09:38 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2011-05-03 Cont ID  
Sent By shill Date 2011-05-03 Time 14:22 Rev Time 0.00
Received By shill Date 2011-05-03 Time 14:22 Sent To  
Notes
2011-05-03 14:27:42****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. ANCHOR SPACING DOES NOT COMPLY WITH PRODUCT APPROVAL
 FOR SEVERAL OPENINGS. FOR INSTANCE, SEE OPENING 7. ALL
 OTHER 83" SPAN OPENINGS WITH SAME CONDITIONS HAVE 10"
 SPECIFIED, BUT 12" IS PROPOSED FOR OPENING #7. 10" IS
 PROPOSED FOR CONNECTION TYPE D, BUT 8" IS REQUIRED FOR
 OPENINGS 2, 5, 6, 7. CONNECTION TYPE L FOR A 103" SPAN,
 TAPCONS REQUIRES 5" ANCHOR SPACING, 10" PROPOSED.
  
 THESE ARE EXAMPLES. PLEASE CHECK ALL. RESUBMITTAL MAY
 BE DONE VIA EMAIL FOR THIS PROJECT ONLY. PLEASE HAVE
 THE QUALIFIER REVIEW PRIOR TO RESUBMITTAL.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-04-27 Cont ID  
Sent By shill Date 2011-04-27 Time 15:59 Rev Time 0.00
Received By shill Date 2011-04-27 Time 15:59 Sent To  
Notes
2011-04-27 16:29:37****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. ON THE INSTALLATION SCHEDULE, SHUTTER MOUNTING
 CONNECTION TYPE COLUMN, PLEASE SPECIFY WHICH WALL
 MOUNTING TYPE WILL BE USED, TOP AND BOTTOM. ANCHOR
 SPACING DOES NOT COMPLY FOR MOUNTING TYPE D, WHICH IS
 HIGHLIGHTED ON THE PRODUCT APPROVAL.
  
 2. ON THE INSTALLATION SCHEDULE, SUBSTRATE, PLEASE
 SPECIFY SUBSTRATE. THIS TYPE OF CONSTRUCTION TYPICALLY
 DICTATES A CONCRETE TOP SUBSTRATE, BLOCK BOTTOM
 SUBSTRATE. NOTE THAT WALL MOUNT TYPE A REQUIRES
 CONCRETE SUBSTRATE.
  
 3. TAPCON SPECIFIED, BUT THE PRODUCT APPROVAL HAS
 ANCHOR SPACING FOR ALL POINTS SOLID SET HIGHLIGHTED.
 ANCHOR SPACING IS GENERALLY MORE STRINGENT FOR TAPCONS,
 SEE SHEET 13.
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2011-05-10 Cont ID  
Sent By shill Date 2011-05-10 Time 09:39 Rev Time 0.00
Received By shill Date 2011-05-05 Time 15:34 Sent To  
Notes
2011-05-05 15:35:12GAVE TO SAMANTHA

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-05-03 Cont ID  
Sent By shill Date 2011-05-03 Time 14:27 Rev Time 0.00
Received By shill Date 2011-05-02 Time 17:25 Sent To  
Notes
2011-05-02 17:25:39TO SH DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-04-27 Cont ID  
Sent By shill Date 2011-04-27 Time 16:32 Rev Time 0.00
Received By shill Date 2011-04-26 Time 14:33 Sent To  
Notes
2011-04-26 14:33:35TO MISC 1
  