Plan Review Details - Permit 11040647
Plan Review Stops For Permit 11040647
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2011-06-02 Cont ID  
Sent By jwitmer Date 2011-06-02 Time 10:24 Rev Time 0.77
Received By jwitmer Date 2011-06-02 Time 10:24 Sent To  
Notes
2011-06-02 11:33:11BUILDING PROVISO:
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 1) SHEET A-1 OCCUPANCY SEPERATION WALL (1 HOUR) BETWEEN
 WAREHOUSE RESTROOM & BUSINESS/ MECANTILE SHOWROOM
 MECHANICAL IS MISSING THE FIRE DAMPER PER :
 2007/09 FBC-B 716.1 GENERAL. THE PROVISIONS OF THIS
 SECTION SHALL GOVERN THE PROTECTION OF DUCT
 PENETRATIONS AND AIR TRANSFER OPENINGS IN ASSEMBLIES
 REQUIRED TO BE PROTECTED. 716.3.1 FIRE PROTECTION
 RATING. FIRE DAMPERS SHALL HAVE THE MINIMUM FIRE
 PROTECTION RATING SPECIFIED IN TABLE 716.3.1 FOR THE
 TYPE OF PENETRATION.
  
 2ND REVIEW NO MECHANICAL SHEETS WERE SUBMITTED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-04-27 Cont ID  
Sent By jwitmer Date 2011-04-27 Time 16:39 Rev Time 0.55
Received By jwitmer Date 2011-04-27 Time 16:38 Sent To  
Notes
2011-04-27 16:56:17BUILDING PLAN REVIEW
 PERMIT: 11040647
 ADD: 1500 N FLORIDA MANGO RD
 CONT: MALSKY HOMES
 TEL: (561)329-9428
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) SHEET A-1 INDICATES NEW TENANT SEPERATION WALL
 SECTIONSWALL DETAIL W1/A-1. MISSING DETAIL AND WALL
 RATING ASSEMBLY, PLEASE REVIEW
 2007 FBC 708.1(3).
  
 2) PLEASE PROVIDE WALL STENCILING FOR RATED WALL PER
 2007 FBC-B 712.6.
  
 3) WAREHOUSE S-2 STORAGE RESTROOM WALL, A OCCUPANCY
 SEPERATION WALL 1 HR RATED IS MISSING A FIRE DAMPER SEE
 MECHANICAL PLANS.
  
 JAMES A. WITMER C.B.O.
 COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: (561)805-6715
 FAX:(561)805-6731
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2011-05-24 Cont ID  
Sent By rlecky Date 2011-05-24 Time 08:40 Rev Time 0.00
Received By rlecky Date 2011-05-24 Time 08:40 Sent To  
Notes
2011-05-24 08:41:11RESTAMP

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2011-05-02 Cont ID  
Sent By rlecky Date 2011-05-02 Time 11:52 Rev Time 0.00
Received By rlecky Date 2011-05-02 Time 11:48 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2011-05-27 Cont ID  
Sent By wjolin Date 2011-05-27 Time 13:12 Rev Time 0.00
Received By wjolin Date 2011-05-27 Time 13:00 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2011-04-27 Cont ID  
Sent By wjolin Date 2011-04-27 Time 15:43 Rev Time 0.00
Received By wjolin Date 2011-04-27 Time 15:12 Sent To  
Notes
2011-04-27 15:27:531500 NORTH FLORIDA MANGO ROAD, SUITE #1,2 8B & 9B
 PERMIT #11040647
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 EACH NEW SMOKE OR FIRE-RATED WALL/PARTITION SHALL BE
 PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING READING
 FIRE SMOKE BARRIER PROTECT ALL OPENINGS. CHARACTERS
 SHALL BE AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN
 WIDTH. IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15
 FEET ON CENTER. REFERENCE SECTION 8.3.2.4 OF FLORIDA
 FIRE PREVENTION CODE - NFPA 101
  
 PENETRATIONS THROUGH A FIRE-RATED WALL ASSEMBLY SHALL
 BE PROTECTED BY A FIRESTOP SYSTEM OR DEVICE. REFERENCE
 SECTION 8.3.5.1 OF FLORIDA FIRE PREVENTION CODE - NFPA
 101
  
 FOR ISSUANCE OF A GENERAL BUILDING PERMIT, ENGINEERING
 CONSTRUCTION DOCUMENTS FOR THE FIRE SPRINKLER AND FIRE
 ALARM WORK ARE REQUIRED.
  
 SEPARATE PLANS (SHOP DRAWINGS CONFORMING TO ENGINEERING
 CONSTRUCTION DOCUMENTS) AND PERMITS ARE REQUIRED FOR
 THE INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND FIRE ALARM SYSTEM.
  
 ALL DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS
 OF NFPA 241.
  
 FIRE RATED DOORS ARE REQUIRED TO BE AUTOMATICALLY
 CLOSING.
  
 PROVIDE BUILDING ADDRESS VISIBLE FROM THE STREET.
 NUMBERS SHALL BE AT LEAST SIX-INCHES IN HEIGHT AND
 SHALL CONTRAST THE BACKGROUND.
  
 PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY
 RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING
 NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM
 WWW.KNOXBOX.COM.
  
 PROVIDE A FURNITURE/STORAGE/SHOWROOM LAYOUT PLAN
 INDICATING WHAT, WHERE AND HOW OPERATIONS ARE BEING
 PERFORMED.
  
 EXTINGUISHERS SHALL HAVE A MINIMUM RATING OF 2A:10BC
 AND SHALL BE TAGGED BY A LICENSED FIRE EXTINGUISHER
 COMPANY.
  
 PROVIDE FIRE DAMPER ON HVAC PLAN FOR DUCT PENETRATING
 FIRE WALL SERVING SMALL RESTROON IN STORAGE OCCUPANCY.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2011-06-09 Cont ID  
Sent By hmoser Date 2011-06-09 Time 15:17 Rev Time 0.00
Received By hmoser Date 2011-06-09 Time 09:14 Sent To  
Notes
2011-06-09 09:15:16**************EXPEDITED****************
 GAVE TO HAROLD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-06-03 Cont ID  
Sent By hmoser Date 2011-06-03 Time 08:01 Rev Time 0.00
Received By hmoser Date 2011-05-19 Time 16:29 Sent To  
Notes
2011-05-19 16:30:14B15

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-05-11 Cont ID  
Sent By hmoser Date 2011-05-11 Time 11:21 Rev Time 0.00
Received By hmoser Date 2011-04-27 Time 08:02 Sent To  
Notes
2011-04-27 08:02:31B15
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2011-06-09 Cont ID  
Sent By hmoser Date 2011-06-09 Time 15:13 Rev Time 0.00
Received By hmoser Date 2011-06-09 Time 15:13 Sent To  
Notes
2011-06-09 15:17:05PASS PROVISO
 REFER TO SECTION 601.4 BALANCED RETURN AIR 2007 FBC (M)
 PLAN REVIEW BY HAROLD MOSER 561-805-6732
 E MAIL [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2011-06-03 Cont ID  
Sent By hmoser Date 2011-06-03 Time 07:18 Rev Time 0.00
Received By hmoser Date 2011-06-03 Time 06:58 Sent To  
Notes
2011-06-03 07:22:11NO MECHANICAL PLANS SUBMITTED.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732
 E MAIL [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2011-05-11 Cont ID  
Sent By hmoser Date 2011-05-11 Time 11:21 Rev Time 0.00
Received By hmoser Date 2011-05-11 Time 10:03 Sent To  
Notes
2011-05-11 11:20:49PLANS DENIED
 1) PROVIDE THE SIGNATURE AND LIC.NUMBER OF THE DESIGNER
 ON THE PLANS.
 2) REFER TO SECTION 106.1.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. 2007 FBC
 1) PROVIDE CFM ON ALL SUPPLY GRAILS. ON THE PLANS.
 2) PROVIDE MAKE UP AIR ON THE PLANS.
 3) PROVIDE BATHROOM VENTILATION ON THE PLANS.
 4) PROVIDE HANGING DETAIL FOR AIRHANDLERS ON THE PLANS.
 5) PROVIDE TIE DOWN DETAIL THE CONDENSER TO SLAB.ON
 PLANS.
 3) REFER TO SECTION 601.4 BALANCED RETURN AIR. 2007
 FBC(M)
 4) REFER TO SECTION 606.2.1 SUPPLY AIR. 2007 FBC (M)
 5) REFER TO SECTION 606.4.1 SUPERVISION. 2007 FBC (M)
 PLAN REVIEW BY HAROLD MOSER 561-805-6732
2011-05-11 10:42:27PLANS DENIED

Review Stop P PLUMBING
Rev No 2 Status P Date 2011-05-31 Cont ID  
Sent By lwagner Date 2011-05-31 Time 12:25 Rev Time 0.00
Received By lwagner Date 2011-05-31 Time 11:52 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2011-04-28 Cont ID  
Sent By lwagner Date 2011-04-28 Time 12:34 Rev Time 0.00
Received By lwagner Date 2011-04-28 Time 12:16 Sent To  
Notes
2011-04-28 12:29:08REPLACING EXISTING FIXTURES ONLY

Review Stop Z ZONING
Rev No 1 Status N Date 2011-05-10 Cont ID  
Sent By eschneid Date 2011-05-10 Time 08:33 Rev Time 0.25
Received By eschneid Date 2011-05-10 Time 08:33 Sent To  
Notes
2011-05-10 08:34:18INTERIOR WORK ONLY, LESS THAN 50% OF BUILDING VALUE.