Plan Review Details - Permit 11040609
Plan Review Stops For Permit 11040609
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2011-06-01 Cont ID  
Sent By jwitmer Date 2011-06-01 Time 15:19 Rev Time 0.77
Received By jwitmer Date 2011-06-01 Time 15:19 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-04-27 Cont ID  
Sent By jwitmer Date 2011-04-26 Time 15:19 Rev Time 0.77
Received By jwitmer Date 2011-04-26 Time 15:19 Sent To  
Notes
2011-04-26 15:24:32BUILDING PLAN REVIEW
 PERMIT: 11040609
 ADD: 1411 N FLAGLER- LOBBY
 CONT: CLAY KOHLMEYER
 TEL: (561)719-3429
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) THE TWO NEW RESTROOMS WILL NEED TO INDICATE THE
 WALLS AS TENANT SEPERATION, 1 HOUR CONSTRUCTION AS PER
 FBC-B708.1(7) WITH OPENING PROTECTION FBC-B TABLE
 715.4.
  
  
 JAMES A. WITMER C.B.O.
 COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: (561)805-6715
 FAX:(561)805-6731
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2011-05-24 Cont ID  
Sent By rlecky Date 2011-05-24 Time 08:49 Rev Time 0.00
Received By rlecky Date 2011-05-24 Time 08:44 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2011-04-27 Cont ID  
Sent By rlecky Date 2011-04-27 Time 10:00 Rev Time 0.00
Received By rlecky Date 2011-04-27 Time 10:00 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2011-06-03 Cont ID  
Sent By wjolin Date 2011-06-03 Time 13:32 Rev Time 0.00
Received By wjolin Date 2011-06-03 Time 13:01 Sent To  
Notes
2011-06-03 13:32:531411 NORTH FLAGLER DRIVE - LOBBY
 PERMIT #11040609
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 NOTE: ON SHEET F2 THE GLAZING EAST OF THE DOORS SHOWS
 THREE SECTIONS OF GLASS; HOWEVER, ONLY TWO WINDOW
 SPRINKLERS HAVE BEEN PROVIDED.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2011-04-27 Cont ID  
Sent By wjolin Date 2011-04-27 Time 14:35 Rev Time 0.00
Received By wjolin Date 2011-04-27 Time 12:34 Sent To  
Notes
2011-04-27 13:39:121411 NORTH FLAGLER DRIVE - LOBBY
 PERMIT #11040609
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 INDENTIFY THE INTERIOR PHARMACY ROOM LOCATED ADJACENT
 TO THE STAIR ENCLOSURE ON SHEET A1.
  
 CEILING NOTES O AND P ARE NOT IDENTIFIED IN THE LEGEND
 ON SHEET A2.
  
 CLEARLY IDENTIFY CEILING HEIGHTS ON SHEET A2. GYPSUM
 BOARD SOFFIT IS INDICATED AS 12'-6" ON SHEET A2,
 HOWEVER, DETAIL 3 OF SHEET A1 INDICATES THE SOFFIT
 ELEVATION IS 8'-1".
  
 MEPF DRAWINGS INDICATE THE 2004 EDITION OF THE FLORIDA
 FIRE PREVENTION CODE. THE 2007 EDITION OF THE FLORIDA
 FIRE PREVENTION CODE IS CURRENTLY IN EFFECT (2006
 EDITION OF NFPA 1 AND NFPA 101).
  
 THE FIRE ALARM SYMBOL (TRIANGLE WITH S) CALLED OUT ON
 SHEET E3 DOES NOT CORRESPOND TO THE LEGEND SHEET.
  
 IDENTIFY THE SPRINKLER HAZARD CLASSIFICATION AND
 SPRINKLER DENSITY ASSOCIATED WITH THE SCOPE OF WORK
 SHOWN ON SHEET F2.
  
 SHEET F2 INDICATES THE USE OF TYCO WINDOW SPRINKLERS;
 HOWEVER, SHEET A1 INDICATES THE GLASS DOORS AND GLASS
 CURTAIN WALLS ARE FIRE RATED. COORDINATE THE INTENDED
 DESIGN. ALSO, STANDARD SPRAY SPRINKLERS ARE LOCATED
 CLOSER THAN SIX FROM ADJACENT WINDOW SPRINKLERS AND MAY
 CAUSE COLD SOLDERING. FOR WINDOW ASSEMBLIES WITH
 VERTICAL MULLIONS, SPRINKLERS ARE REQUIRED TO BE
 LOCATED WITHIN EACH MULLION.
  
 NOTE: IF THE DESIGN INTENT IS TO USE TYCO WINDOW
 SPRINKLERS TO ACHIEVE A FIRE RATED SEPARATION, THE
 SPRINKLERS MUST BE INSTALLED ACCORDING TO THE UL
 LISTING DATA AND SHALL WET THE ENTIRE GLAZING SURFACE.
 SPRINKLERS CANNOT BE USED TO PROTECT OPERABLE DOORS OR
 WINDOWS. THE WINDOW SPRINKLERS DO NOT ALLOW HORIZONTAL
 WINDOW MULLIONS AND REQUIRE THE GLASS CURTAIN WALL TO
 BE ATTACHED TO A THREE FOOT HIGH PONY WALL TO KEEP
 COMBUSTIBLE MATERIALS AT LEAST TWO INCHES AWAY FROM THE
 GLAZING. PAY SPECIAL ATTENTION TO THE GLAZING ASSEMBLY
 AS THE SPRINKLER POSITIONING VARIES FOR BUTT-GLAZED
 INSTALLATIONS COMPARED TO VERTICAL MULLION
 INSTALLATIONS. VERTICAL MULLIONS SHALL BE OF A DEPTH
 THAT PREVENTS COLD SOLDERING OF ADJACENT SPRINKLERS.
 THE SPRINKLER DESIGN SHOULD INDICATE WHICH WINDOW
 SPRINKLER MODEL WILL BE USED (HORIZONTAL SIDEWALL OR
 PENDENT VERTICAL SIDEWALL).
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-06-03 Cont ID  
Sent By wjolin Date 2011-06-03 Time 13:33 Rev Time 0.00
Received By wjolin Date 2011-05-23 Time 09:32 Sent To  
Notes
2011-05-27 15:08:36******************EXPEDITED*********************
 5/27/11
2011-05-23 09:32:24SENT TO B16.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-05-04 Cont ID  
Sent By lmartine Date 2011-05-02 Time 12:47 Rev Time 0.00
Received By lmartine Date 2011-04-25 Time 15:56 Sent To  
Notes
2011-04-25 15:56:50SENT TO B-8.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2011-05-31 Cont ID  
Sent By hmoser Date 2011-05-31 Time 14:26 Rev Time 0.00
Received By hmoser Date 2011-05-31 Time 14:26 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2011-04-26 Cont ID  
Sent By hmoser Date 2011-04-26 Time 11:12 Rev Time 0.00
Received By hmoser Date 2011-04-26 Time 11:12 Sent To  
Notes
2011-04-26 11:22:15PLANS DENIED
 PROVIDE ACCESS DOORS FOR DUCT DETECTOR.
 PROVIDE DUCT SIZE ON THE PLANS FOR ALL DUCT.
 PROVIDE FIRE DAMPERS IN 6X6 DUCT AND 24X18 DUCT'S IN
 ROOM 101 TOILET.
 PROVIDE A HANGING DETAIL FOR THE AIR HANDLER ON THE
 PLANS.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2011-04-28 Cont ID  
Sent By lwagner Date 2011-04-28 Time 12:12 Rev Time 0.00
Received By lwagner Date 2011-04-28 Time 09:53 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2011-05-02 Cont ID  
Sent By eschneid Date 2011-05-02 Time 09:52 Rev Time 0.25
Received By eschneid Date 2011-05-02 Time 09:52 Sent To  
Notes
2011-05-02 09:55:33INTERIOR WORK ONLY, LESS THEN 50% OF BUILDING VALUE.